Plan Review Notes
Plan Review Notes For Permit 18021105
Permit Number 18021105
Review Stop G
Sequence Number 1
Notes
Date Text
2018-03-09 16:38:0603/09/2018 1ST GAS REVIEW**DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS
  
  
 1) YOU LIST A EXISTING GAS METER. SUBMIT AN ISOMETRIC
 DRAWING THAT CLEARLY SHOWS THE LENGTH OF ALL CUT
 SECTIONS OF PIPE PER 2014 FBC-FUEL GAS, SECS. 402.4.1,
 402.4.2. OR 2014 FBC-RES SEC. G2413
  
 2) TYPE OF GAS (LP OR NATURAL).
  
 3) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THIS EXISTING SYSTEM. REFER TO THE 2014
 FBC-FUEL GAS SECS.401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2413.
  
 4) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2.
  
 5) 17) SUBMIT TWO COPIES OF THE APPLICABLE SIZING
 TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON
 THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S)
 FROM THE GAS CODE OR OTHER STANDARD THAT WERE USED IN
 THE DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014
 FBC-FUEL GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES
 402.4 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC.
 G2412.4, G2412.8, G2413.1, G2413.2, & G2413.3
  
 6) YOU LIST THE BTU RATING AS 142,000 BTU. THE
 MANUFACTURES MANUAL SUPPLIED LIST FULL LOAD AS 327,000
 BTU. PER FBC-F 402.2 THE SYSTEM IS REQUIRED TO BE SIZED
 WITH APPLIANCE AT FULL LOAD.
  
 7) I CAN ONLY GUESS THAT THIS SYSTEM MAY BE 12" WC AS
 YOU DON NOT SHOW A PRESSURE REGULATOR. IF IN FACT IT IS
 THE 1" P.E PIPING WOULD BE UNDERSIZED.
  
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  