Plan Review Notes
Plan Review Notes For Permit 18021105
Permit Number 18021105
Review Stop B
Sequence Number 1
Notes
Date Text
2018-05-18 08:47:12PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW FOR THE GENERATOR
 SLAB:
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) ON SHEET 5 OF 5 OF THE 22 KW GENERAC GENERATOR
 DOCUMENTS THAT WERE SUBMITTED THE NOTE STATES THAT THE
 DIMENSIONS SHOWN ARE APPROXIMATE AND REFERS YOU TO THE
 INSTALLATION MANUAL FOR EXACT DIMENSIONS. SUBMIT TWO
 SETS OF THE INSTALLATION MANUALS FOR THE 22 KW GENERAC
 GENERATOR. FBC 107.2.1.2
  