Plan Review Notes
Plan Review Notes For Permit 18021086
Permit Number 18021086
Review Stop P
Sequence Number 1
Notes
Date Text
2018-03-01 08:43:5103/01/2018 1ST PLUMBING REVIEW**DENIED**
  
  
 1) PROVIDE FULL MANUFACTURES INSTALLATION MANUAL. FBC
 107.2.1
  
 2) SHOW HOW YOU SIZED THE SYSTEM AND THAT THIS
 INTERCEPTOR COMPLIES WITH FBC P1003.3.4
  
 3) SHOW ON YOUR ISOMETRIC DRAWING THE PIPING SIZE AND
 DEVELOPED LENGTH OF EACH SECTION OF PIPING. FBC 107.3.5
  
 4) ADD P-TRAP AND VENT COMPLYING WITH 1002.1 AND 901.2
 TO YOUR ISOMETRIC DRAWING
  
 5) OVERALL VALUE OF JOB SEEMS LOW. PROVIDE SIGN
 CONTRACT SHOWING FULL VALUE OF JOB INCLUDING ALL
 MATERIAL, LABOR, OVERHEAD, AND PROFITS. WPB AMEND TO
 FBC 109.3
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT