2018-06-20 10:41:00CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
 9. CORRECTED.
 10. THE RISER DIAGRAM PROVIDED WITH THIS SUBMISSION IS
 VERY DIFFERENT FROM THE LAST SUBMISSION. AS THERE ARE
 OTHER METERS WITH THIS SERVICE, PROVIDE LOAD
 CALCULATION FOR ENTIRE SERVICE IN ADDITION TO THE LOAD
 CALCULATION FOR THE INDIVIDUAL UNIT, INCLUDE EXISTING
 AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS
 ADEQUATE. SHOW WIRE SIZE OF SERVICE ON RISER DIAGRAM TO
 CONFIRM IT IS SIZED TO HANDLE THE ADDITIONAL LOAD. NEC
 215.2, 220, 408.30; FBC RE E3602.3 (EVEN THOUGH
 MULTIPLE METERS ARE PERMITTED FOR 3 UNITS PER THE
 PROPERTY APPRAISERS INFORMATION, ONLY ONE SERVICE IS
 PERMITTED. THIS SERVICE NEEDS TO SIZED TO HANDLE ALL
 LOADS. A SEPARATE SERVICE DROP IS NOT CODE COMPLIANT.
 NEC 230.2 THIS IS THE REASON A RISER DIAGRAM WAS
 REQUESTED AND IS STILL REQUIRED. SHOW RISER DIAGRAM
 WITH DETAILS AS PREVIOUSLY REQUESTED ABOVE.)
 11. CORRECTED.
  
 NEW COMMENTS:
  
 12. RISER DIAGRAM SHOWS A # 8 EQUIPMENT GROUNDING
 CONDUCTOR IN THE CONDUIT FROM THE MAIN DISCONNECT TO
 THE UNIT DISCONNECT. THIS WIRE IS NOT SIZED PROPERLY
 FOR A 125 AMP SERVICE. PROVIDE CORRECTION. NEC 250.122
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  