Plan Review Notes
Plan Review Notes For Permit 18021080
Permit Number 18021080
Review Stop P
Sequence Number 2
Notes
Date Text
2018-04-27 08:28:41RESIDENTIAL (R3) REVISION, SECOND PLUMBING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- PLUMBING RISER DIAGRAM SUBMITTED SHOWS 2 WET VENTED
 FIXTURES DRAINS DISCHARGING UPSTREAM OF THE DRY VENTED
 FIXTURE DRAIN CONNECTION. REVISE AS REQUIRED.
  
 RESPONSE: SECOND REJECTION. ENGINEER WILL BE CHARGED 4
 TIMES THE PLAN REVIEW IF COMMENT IS NOT ADDRESSED ON
 NEXT SUBMITTAL. REVISED PLUMBING RISER DIAGRAM ONLY
 REVISED BATHROOM #2. BATHROOM #1 STILL DOESN'T COMPLY.
 REVISE AS REQUIRED.
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS'
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 SEC. P3108.2.1 FBC-RESIDENTIAL. HORIZONTAL WET VENT.
 THE DRY-VENT CONNECTION FOR A HORIZONTAL WET-VENT
 SYSTEM SHALL BE AN INDIVIDUAL VENT OR A COMMON VENT FOR
 ANY BATHROOM GROUP FIXTURE, EXCEPT AN EMERGENCY FLOOR
 DRAIN. WHERE THE DRY VENT CONNECTS TO A WATER CLOSET
 FIXTURE DRAIN, THE DRAIN SHALL CONNECT HORIZONTALLY TO
 THE HORIZONTAL WET VENT SYSTEM. NOT MORE THAN ONE
 WET-VENTED FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF
 THE DRY-VENTED FIXTURE DRAIN CONNECTION
  
 2- REVISE THE DRAIN PIPE SIZE FOR ALL LAVATORIES AND
 KITCHEN SINKS SHOWN IN THE RISER DIAGRAM TO COMPLY WITH
 TABLE P3201.7 FBC-RESIDENTIAL.
  
 RESPONSE: SECOND REJECTION. ENGINEER WILL BE CHARGED 4
 TIMES THE PLAN REVIEW IF COMMENT IS NOT ADDRESSED ON
 NEXT SUBMITTAL. REVISED PLUMBING RISER DIAGRAM 1 STILL
 DOESN'T COMPLY. REVISE AS REQUIRED.
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS'
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DON'T STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  