2018-04-23 17:25:09 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| |
| 1. LOAD CALCULATION PROVIDED IS INCORRECT. BASED ON THE |
| NUMBERS PROVIDED: 10,000 + 16,610 + 6,500 = 33,110 VA, |
| DIVIDED BY 240 = 138 AMPS. PROVIDE CORRECTED LOAD |
| CALCULATION. NEC 220; FBC RE E3602.3 (LOAD CALCULATION |
| NOT CORRECT, SEE NEW COMMENT #9 BELOW. ALSO, MATH IS |
| NOT CORRECT.) |
| 2. IF THE NUMBERS IN COMMENT # 1 RESULT IN SERVICE |
| LARGER THAN THE 125 AMP SERVICE SPECIFIED ON PLAN, |
| PROVIDE CORRECTION TO SIZE OF SERVICE. NEC 215.2, 220, |
| 230.42, 408.30 (NOT ADDRESSED AT THIS TIME, AS THE LOAD |
| CALCULATION IS NOT CORRECT.) |
| 3. CORRECTED. |
| 4. THERE IS A DISCREPANCY ON THE PLAN FOR THE TANKLESS |
| WATER HEATER. DETAIL SHOWS THIS IS A 7KW LOAD, WHILE |
| THE LOAD CALCULATION SHOWS THIS AS A 30KW LOAD. CLARIFY |
| AND/OR CORRECT. FBC 107.2.1 (DISCREPANCY IS STILL |
| THERE, ONLY NOW IT SHOWS AS 7 KW ON PRODUCT SPEC AND 11 |
| KW IN LOAD CALCULATION. PROVIDE CORRECTION.) |
| 5. CORRECTED. |
| 6. NOTE # 3 IN ELECTRICAL NOTES STATES THAT RECEPTACLES |
| SHALL BE TAMPER RESISTANT PER NEC 406.11. THIS CODE |
| SECTION DOES NOT APPLY TO TAMPER RESISTANT RECEPTACLES. |
| PROVIDE CORRECTION. NEC 406.12; FBC RE E4002.14 (NOT |
| CORRECTED. PROVIDE NOTE THAT ALL RECEPTACLES SHALL BE |
| TAMPER RESISTANT PER NEC 406.12 AND FBC RE E4002.14) |
| 7. CORRECTED. |
| 8. CORRECTED. |
| |
| NEW COMMENTS: |
| |
| 9. THE LOAD FOR A DRYER SHALL BE CALCULATED AT 5000 |
| WATTS OR THE NAMEPLATE RATING, WHICHEVER IS GREATER. |
| PROVIDE CORRECTION. NEC 220.54; FBC RE E3602.2 |
| 10. THE RISER DIAGRAM PROVIDED WITH THIS SUBMISSION IS |
| VERY DIFFERENT FROM THE LAST SUBMISSION. AS THERE ARE |
| OTHER METERS WITH THIS SERVICE, PROVIDE LOAD |
| CALCULATION FOR ENTIRE SERVICE IN ADDITION TO THE LOAD |
| CALCULATION FOR THE INDIVIDUAL UNIT, INCLUDE EXISTING |
| AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS |
| ADEQUATE. SHOW WIRE SIZE OF SERVICE ON RISER DIAGRAM TO |
| CONFIRM IT IS SIZED TO HANDLE THE ADDITIONAL LOAD. NEC |
| 215.2, 220, 408.30; FBC RE E3602.3 |
| 11. ONLY THE RECEPTACLE OUTLETS ARE SHOWN AS AFCI |
| PROTECTED. PER CODE: "ALL 120-VOLT, SINGLE PHASE, 15 |
| AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN |
| DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, |
| RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS |
| OR ROOMS, SHALL HAVE AFCI PROTECTION." THIS INCLUDES |
| LIGHTING AND RECEPTACLE OUTLETS PROVIDE CORRECTION. IF |
| DESIRED, A NOTE WILL SUFFICE IN LIEU OF MARKING EACH |
| OUTLET WITH AFCI. NEC 210.12; FBC RE E3902.12 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |