2018-03-08 10:12:29CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. LOAD CALCULATION PROVIDED IS INCORRECT. BASED ON THE
 NUMBERS PROVIDED: 10,000 + 16,610 + 6,500 = 33,110 VA,
 DIVIDED BY 240 = 138 AMPS. PROVIDE CORRECTED LOAD
 CALCULATION. NEC 220; FBC RE E3602.3
 2. IF THE NUMBERS IN COMMENT # 1 RESULT IN SERVICE
 LARGER THAN THE 125 AMP SERVICE SPECIFIED ON PLAN,
 PROVIDE CORRECTION TO SIZE OF SERVICE. NEC 215.2, 220,
 230.42, 408.30
 3. CONDUIT FROM EXTERIOR DISCONNECT TO INTERIOR PANEL
 IS REQUIRED TO HAVE AN EQUIPMENT GROUNDING CONDUCTOR.
 PROVIDE CORRECTION. NEC 250.122
 4. THERE IS A DISCREPANCY ON THE PLAN FOR THE TANKLESS
 WATER HEATER. DETAIL SHOWS THIS IS A 7KW LOAD, WHILE
 THE LOAD CALCULATION SHOWS THIS AS A 30KW LOAD. CLARIFY
 AND/OR CORRECT. FBC 107.2.1
 5. THERE IS A CONFLICT IN THE NOTES. NOTE 4 STATES THAT
 THE WORK SHOULD COMPLY WITH THE 2008 NEC, WHILE OTHER
 AREAS SHOW THE 2011 NEC AS THE PROPER VERSION. REMOVE
 THE CONFLICTING NOTE # 4. FBC 107.2.1
 6. NOTE # 3 IN ELECTRICAL NOTES STATES THAT RECEPTACLES
 SHALL BE TAMPER RESISTANT PER NEC 406.11. THIS CODE
 SECTION DOES NOT APPLY TO TAMPER RESISTANT RECEPTACLES.
 PROVIDE CORRECTION. NEC 406.12; FBC RE E4002.14
 7. NOTE # 2 IN ELECTRICAL NOTES STATES THAT ALL WIRING
 SHALL BE 12 GAUGE WIRE ON 20 AMP CIRCUITS, BUT THE
 SCHEDULE SHOWS 15 AMP CIRCUITS. CLARIFY AND/OR CORRECT.
 FBC 107.2.1
 8. BATH GFCI CIRCUIT IS SHOWN AS A 15 AMP CIRCUIT,
 WHICH IS A CODE VIOLATION. PROVIDE CORRECTION. NEC
 210.11(C)(3) , FBC RE E3703.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  