2018-09-27 14:52:24CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 4TH REVIEW:
 PLUMBING COMMENTS: DENIED
  
 1. PLAN SHEET P-1 SHOWING WATER DISTRIBUTION IS MISSING
 FROM NEW SUBMITTAL. HAVING REVIEWED VOIDED P-1 SHEET
 REV 1, PLEASE NOTE THAT THE WATER DISTRIBUTION PLAN
 SHALL SHOW AN INDIVIDUAL COLD WATER SUPPLY WITH
 ACCESSIBLE VALVE PER FPC PL 606.1 (6) FOR EACH UNIT.
 THE DIAGRAM SHALL SHOW HOT AND COLD WATER DISTRIBUTION
 FOR EACH UNIT PER WPB FBC 702.1.
 A. PLEASE REVIEW RED LINED NOTES MADE ON VOIDED SHEET
 P-1 REV 1 FOR CLARIFICATION.
 2. ALL NEW SANITARY BRANCHES AND STACK(S) TO CONNECT,
 IN METHODS COMPLIANT WITH FBC PL 704.1 AND SECTION 706,
 TO THE EXISTING BUILDING DRAIN UPSTREAM OF THE EXTERIOR
 FOOTER AND NOTED AS SUCH ON THE SANITARY PLAN VIEW AND
 THE SANITARY ISOMETRIC PER WPB FBC 107.2.1.
 3. THE KITCHEN SINK IN APT #1 REQUIRES A VENT WHICH MAY
 BE AN AIR ADMITTANCE VALVE, RE-VENT OR THROUGH THE
 ROOF.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved