2018-09-27 14:52:24 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 4TH REVIEW: |
| PLUMBING COMMENTS: DENIED |
| |
| 1. PLAN SHEET P-1 SHOWING WATER DISTRIBUTION IS MISSING |
| FROM NEW SUBMITTAL. HAVING REVIEWED VOIDED P-1 SHEET |
| REV 1, PLEASE NOTE THAT THE WATER DISTRIBUTION PLAN |
| SHALL SHOW AN INDIVIDUAL COLD WATER SUPPLY WITH |
| ACCESSIBLE VALVE PER FPC PL 606.1 (6) FOR EACH UNIT. |
| THE DIAGRAM SHALL SHOW HOT AND COLD WATER DISTRIBUTION |
| FOR EACH UNIT PER WPB FBC 702.1. |
| A. PLEASE REVIEW RED LINED NOTES MADE ON VOIDED SHEET |
| P-1 REV 1 FOR CLARIFICATION. |
| 2. ALL NEW SANITARY BRANCHES AND STACK(S) TO CONNECT, |
| IN METHODS COMPLIANT WITH FBC PL 704.1 AND SECTION 706, |
| TO THE EXISTING BUILDING DRAIN UPSTREAM OF THE EXTERIOR |
| FOOTER AND NOTED AS SUCH ON THE SANITARY PLAN VIEW AND |
| THE SANITARY ISOMETRIC PER WPB FBC 107.2.1. |
| 3. THE KITCHEN SINK IN APT #1 REQUIRES A VENT WHICH MAY |
| BE AN AIR ADMITTANCE VALVE, RE-VENT OR THROUGH THE |
| ROOF. |
| |
| |
| |