Plan Review Notes
Plan Review Notes For Permit 18021046
Permit Number 18021046
Review Stop R
Sequence Number 3
Notes
Date Text
2018-07-17 09:40:181-- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 NOTE: THIS MAY BE SUBMITTED LATER AS DEFERRED
 SUBMITTAL, BUT BEFORE INSTALLATION (NO FEES).
  
 A) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. 1609 FBC. NOTE: IF THE
 SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR
 ALL ROOF ZONES, THEN SIGNED AND SEALED RAS 117
 CALCULATIONS ARE REQUIRED.
  
 B) ROOF TILE.
  
 C) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD. AND SPECIFY PADDY SIZE. SEE ROOF TILE PRODUCT
 APPROVAL FOR LISTED ADHESIVES.
  
 2-- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.