Plan Review Notes
Plan Review Notes For Permit 18021046
Permit Number 18021046
Review Stop P
Sequence Number 3
Notes
Date Text
2018-08-02 18:46:302ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE 2" LINE CONNECTING THE KITCHEN ON THE FIRST
 FLOOR SHALL BE VENTED BY A VENT THAT RUN THROUGH THE
 ROOF OR BE CONNECTED TO THE BUILDING DRAIN BEFORE
 EXITING BUILDING. PER FBC PL 904.1 AND MANUFACTURE
 SPECIFICATION.
  
 2. SHOW A COMPLETE BUILDING DRAIN ON THE FIRST FLOOR
 ISOMETRIC INCLUDING THE SOIL STACKS FROM SECOND FLOOR.
 PER WPB AMEND TO FBC 107.2.1.
  
 3. THE HORIZONTAL BRANCH DRAIN FOR THE WASHING MACHINE
 SHALL BE 3" IF USING AN AIR ADMITTANCE VALVE. PER
 MANUFACTURE INSTALLATION GUIDE.
  
 4. THE 3" SOIL STACKS THAT ARE RUNNING DOWN THROUGH THE
 EXTERIOR WALL MAR INTERFERE WITH THE WIDTH OF A 2 X 4
 WALL THE 3" FITTING ARE LARGER THAN THE INSIDE SPACE OF
 THE WALL ALSO WILL THE PIPE BE RUNNING DOWN THROUGH TH
 FOOTER PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  