Plan Review Notes
Plan Review Notes For Permit 18021046
Permit Number 18021046
Review Stop M
Sequence Number 3
Notes
Date Text
2018-07-17 13:55:42MECHANICAL PLAN REVIEW FAIL
  
 1 - NEED TO SUBMIT 2 COPYS OF MECHANICAL PLANS (ONLY 1
 COPY SUBMITTED)
 2 - ANY DUCTS THROUGH PARTY WALLS NEED FIRE DAMPERS
  