Plan Review Notes
Plan Review Notes For Permit 18021046
Permit Number 18021046
Review Stop B
Sequence Number 3
Notes
Date Text
2018-07-17 09:30:38RESIDENTIAL (R2) ALTERATION, THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017).
  
 1 REVISE ENERGY CALCULATIONS SUBMITTED FOR APT. #1,
 APT. #2 AND APT. #3 (NOTE: COORDINATE INFORMATION ON
 ALL 3 APARTMENTS TO AVOID CONFLICTS/DELAYS):
 A) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. NEED OWNER'S NAME. NEED CORRECT BUILDER'S NAME.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT PROPERLY ADDRESSED. NEED CORRECT
 NAME OF THE OWNER AND THE BUILDER.
  
 B)APT #1 AND APT #2: REVISE ATTIC INFORMATION SHOWN ON
 PAGE 2 OF 4. THERE IS NO ATTIC ABOVE THIS APARTMENT.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT PROPERLY ADDRESSED. THERE IS NOT
 ATTIC ABOVE THIS APARTMENT. CONSEQUENTLY THERE IS NOT
 VENTED ATTIC EITHER. THERE IS AN APARTMENT ON THE
 SECOND FLOOR. REVISE AS REQUIRED. NOTE: COORDINATE AND
 REVISE INFORMATION ON ITEM #10 ON PAGE 1 OF 4. WHY ONE
 APARTMENT HAS INSULATION AND THE OTHER DOESN'T?.
 CLARIFY WHY INFORMATION ON APT. # 2 SAYS "NO ATTIC" AND
 INFORMATION ON APT #1 SAYS "FULL ATTIC". COORDINATE ALL
 INFORMATION TO AVOID UNNECESSARY CONFLICTS/DELAYS.
  
 C)CRAWLSPACE IN APT #1 AND APT #2: : CLARIFY WHY ONE
 APARTMENT HAS INSULATION AND THE OTHER DOESN'T?. SEC.
 R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 D)APT #1 AND APT #2: : CLARIFY WHY THE WINDOW U-FACTOR
 AND SHGC FACTOR IS DIFFERENT ON EACH APARTMENT.
 TYPICALLY CONTRACTOR USES SAME WINDOWS WHEN REPLACING
 THEM. IF DIFFERENT WINDOWS ARE USED, THEN CLEARLY
 IDENTIFY EACH WINDOW. SEC. R101.5.1.1.2 FBC- ENERGY
 CONSERVATION.
  
 E) APT #3: CLARIFY WHY THERE IS NO INSULATION ON ITEM
 #8 ON PAGE 1 OF 4. COORDINATE WITH INFORMATION GIVEN ON
 APT #1 AND APT #2. SEC. R101.5.1.1.2 FBC- ENERGY
 CONSERVATION.
  
 F)APT #3: REVISE ROOF INFORMATION SHOWN ON PAGE 1 OF 4
 AND PAGE 2 OF 4. ACCORDING TO PLANS THE CEILING JOISTS
 ARE 2X6. THEREFORE, R-30 BATT INSULATION DOESN'T FIT.
 R-30 BATT INSULATION IS ABOUT 9-1/2" THICK. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 G)APT #3: REVISE ROOF INFORMATION SHOWN ON PAGE 2 OF 4.
 THERE IS ON GABLE AREA ON A FLAT ROOF. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 H)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD FOR ALL APARTMENTS. SEC. R405.4.3
 FBC- ENERGY CONSERVATION.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR IS REQUIRED WHEN THE ENERGY CALCULATIONS
 ARE NOT USING THE DEFAULT FACTOR. THIS WILL BE DONE AT
 TIME OF INSPECTIONS.
  
 2- ENGINEER OF RECORD TO REVISE INSULATION INFORMATION
 SHOWN ON PLANS. R-30 BATT INSULATION IS 9-1/2" +/-
 THICK. IT DOESN'T FIT ON ROOF JOIST AND FLOOR JOISTS
 SIZES SHOWN ON PLANS. REVISE AS REQUIRED. NOTE:
 COORDINATE WITH ENERGY CALCULATIONS TO AVOID
 CONFLICTS/DELAYS. SEC. R103.2 FBC-ENERGY CONSERVATION.
  
 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 FLOOR/CEILING ASSEMBLY FOR TENANT SEPARATION WITH THE
 APT ON THE SECOND FLOOR. REPEAT COMMENT. NOTE: TENANT
 SEPARATION WALL DETAIL "F" ON SHEET S1A DOESN'T PROVIDE
 SPECIFICATIONS FOR APPROVED HORIZONTAL ASSEMBLY. IT
 ONLY SPECIFIES THE WALL ASSEMBLY UL-U311. PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS FOR APPROVED
 HORIZONTAL FIRE RATED ASSEMBLY AS REQUIRED . SEC. 420.3
 FBC.
  
 4-SECOND FLOOR WINDOWS NEED TO COMPLY WITH THE WINDOW
 OPENING CONTROL DEVICES REQUIRED BY SEC. 702.4
 FBC-EXISTING BUILDING.
 NOTE: PROVIDE INFORMATION SHOWING COMPLIANCE WITH ASTM
 F2090.
  
 5- ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS,
 AND SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING AS REQUIRED BY SEC.
 801.3 FBC-EXISTING BUILDING. SHOW COMPLIANCE WITH THE
 SOUND TRANSMISSION FOR FLOOR/CEILING ASSEMBLY.
 FLOORING UNDERLAYMENT
 SOUND INSULATION MATERIAL:
 A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION
 (2017).
  
 B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS
 (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS
 REQUIRED BY SEC. 1207.2 OF FBC 6TH EDITION (2017).
  
 C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS
 (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS
 REQUIRED BY SEC. 1207.3 OF FBC 6TH EDITION (2017).
  
 6-DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF
 SPECIFYING SCREWS, THEN SPECIFY SIZE AND NUMBER OF
 SCREWS. IF SPECIFYING ROOF TILE ADHESIVE, THEN SPECIFY
 PADDY SIZE AND PRODUCT APPROVAL IS REQUIRED. REPEAT
 COMMENT. ENGINEER TO SPECIFY FASTENING. THIS IS NOT BY
 OTHERS.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 NOTE: THIS MAY BE SUBMITTED LATER AS DEFERRED
 SUBMITTAL, BUT BEFORE INSTALLATION (NO FEES).
  
 A) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. 1609 FBC. NOTE: IF THE
 SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR
 ALL ROOF ZONES, THEN SIGNED AND SEALED RAS 117
 CALCULATIONS ARE REQUIRED.
  
 B) ROOF TILE.
  
 C) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD. AND SPECIFY PADDY SIZE. SEE ROOF TILE PRODUCT
 APPROVAL FOR LISTED ADHESIVES.
  
 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 9- BASED ON THE MECHANICAL PLANS SUBMITTED, PROVIDE
 DETAILS AND SPECIFICATIONS SHOWING HOW THE A/C DUCTWORK
 IS GOING TO BE INSTALLED. REMEMBER THAT THERE IS A FIRE
 RATED FLOOR/CEILING ASSEMBLY SEPARATING THE APT ABOVE.
 SEC. 711 FBC-BUILDING.
 NEED PLANS AND SPECIFICATIONS FOR THE CONSTRUCTION OF
 THE SOFFITS FOR A/C WORK.
  
 10- PROVIDE COMPLETE DETAILS ANS SPECIFICATIONS FOR THE
 REPLACEMENT OF EXTERIOR WOOD STUDS. SPECIFY ALL
 CONNECTORS. SEC. 1609.1 FBC.
  
 11-ROOF FRAMING PLAN ON SHEET S1A:
 A) PROVIDE COMPLETE SECTION/DETAIL AT CANOPY ENTRY FOR
 APT #2 AND APT #3. IT'S NOT CLEAR HOW THE ROOF IS
 SUPPORTED. FRONT ELEVATION CALLS FOR COLUMNS, BUT ROOF
 FRAMING DETAIL DOESN'T SPECIFY ANY. SEC. 1609.1 FBC.
  
 B) LEDGER INFORMATION SHOWN ON THE ROOF FRAMING PLAN
 DOESN'T MATCH LEDGER INFORMATION SHOWN ON SECTION 1 ON
 SAME SHEET. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 12- PROVIDE COMPLETE INFORMATION FOR THE FIRE RATING
 ASSEMBLY BELOW THE STAIRS AND BY THE PANTRY CLOSET ON
 FIRST FLOOR KITCHEN. SEC. 420.2 AND 420.3 FBC.
  
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
 NOTE:
 ENGINEER OF RECORD TO PROVIDE RESPONSE LETTER
 ADDRESSING EACH COMMENT TO AVOID PLAN REVIEW FEES AS
 REQUIRED BY FLORIDA STATUTE 553.80(2)(B).
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DON'T STAPLE OLD DRAWINGS TO PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]