2018-07-17 09:30:38 | RESIDENTIAL (R2) ALTERATION, THIRD BUILDING REVIEW |
| CHECKLIST. |
| CODE: FBC 6TH EDITION (2017). |
| |
| 1 REVISE ENERGY CALCULATIONS SUBMITTED FOR APT. #1, |
| APT. #2 AND APT. #3 (NOTE: COORDINATE INFORMATION ON |
| ALL 3 APARTMENTS TO AVOID CONFLICTS/DELAYS): |
| A) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF |
| FORM. NEED OWNER'S NAME. NEED CORRECT BUILDER'S NAME. |
| SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT PROPERLY ADDRESSED. NEED CORRECT |
| NAME OF THE OWNER AND THE BUILDER. |
| |
| B)APT #1 AND APT #2: REVISE ATTIC INFORMATION SHOWN ON |
| PAGE 2 OF 4. THERE IS NO ATTIC ABOVE THIS APARTMENT. |
| SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT PROPERLY ADDRESSED. THERE IS NOT |
| ATTIC ABOVE THIS APARTMENT. CONSEQUENTLY THERE IS NOT |
| VENTED ATTIC EITHER. THERE IS AN APARTMENT ON THE |
| SECOND FLOOR. REVISE AS REQUIRED. NOTE: COORDINATE AND |
| REVISE INFORMATION ON ITEM #10 ON PAGE 1 OF 4. WHY ONE |
| APARTMENT HAS INSULATION AND THE OTHER DOESN'T?. |
| CLARIFY WHY INFORMATION ON APT. # 2 SAYS "NO ATTIC" AND |
| INFORMATION ON APT #1 SAYS "FULL ATTIC". COORDINATE ALL |
| INFORMATION TO AVOID UNNECESSARY CONFLICTS/DELAYS. |
| |
| C)CRAWLSPACE IN APT #1 AND APT #2: : CLARIFY WHY ONE |
| APARTMENT HAS INSULATION AND THE OTHER DOESN'T?. SEC. |
| R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| |
| D)APT #1 AND APT #2: : CLARIFY WHY THE WINDOW U-FACTOR |
| AND SHGC FACTOR IS DIFFERENT ON EACH APARTMENT. |
| TYPICALLY CONTRACTOR USES SAME WINDOWS WHEN REPLACING |
| THEM. IF DIFFERENT WINDOWS ARE USED, THEN CLEARLY |
| IDENTIFY EACH WINDOW. SEC. R101.5.1.1.2 FBC- ENERGY |
| CONSERVATION. |
| |
| E) APT #3: CLARIFY WHY THERE IS NO INSULATION ON ITEM |
| #8 ON PAGE 1 OF 4. COORDINATE WITH INFORMATION GIVEN ON |
| APT #1 AND APT #2. SEC. R101.5.1.1.2 FBC- ENERGY |
| CONSERVATION. |
| |
| F)APT #3: REVISE ROOF INFORMATION SHOWN ON PAGE 1 OF 4 |
| AND PAGE 2 OF 4. ACCORDING TO PLANS THE CEILING JOISTS |
| ARE 2X6. THEREFORE, R-30 BATT INSULATION DOESN'T FIT. |
| R-30 BATT INSULATION IS ABOUT 9-1/2" THICK. REVISE AS |
| REQUIRED. SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| |
| G)APT #3: REVISE ROOF INFORMATION SHOWN ON PAGE 2 OF 4. |
| THERE IS ON GABLE AREA ON A FLAT ROOF. REVISE AS |
| REQUIRED. SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| |
| H)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| (EPL) DISPLAY CARD FOR ALL APARTMENTS. SEC. R405.4.3 |
| FBC- ENERGY CONSERVATION. |
| |
| NOTE: |
| LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND |
| SHGC FACTOR IS REQUIRED WHEN THE ENERGY CALCULATIONS |
| ARE NOT USING THE DEFAULT FACTOR. THIS WILL BE DONE AT |
| TIME OF INSPECTIONS. |
| |
| 2- ENGINEER OF RECORD TO REVISE INSULATION INFORMATION |
| SHOWN ON PLANS. R-30 BATT INSULATION IS 9-1/2" +/- |
| THICK. IT DOESN'T FIT ON ROOF JOIST AND FLOOR JOISTS |
| SIZES SHOWN ON PLANS. REVISE AS REQUIRED. NOTE: |
| COORDINATE WITH ENERGY CALCULATIONS TO AVOID |
| CONFLICTS/DELAYS. SEC. R103.2 FBC-ENERGY CONSERVATION. |
| |
| 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| FLOOR/CEILING ASSEMBLY FOR TENANT SEPARATION WITH THE |
| APT ON THE SECOND FLOOR. REPEAT COMMENT. NOTE: TENANT |
| SEPARATION WALL DETAIL "F" ON SHEET S1A DOESN'T PROVIDE |
| SPECIFICATIONS FOR APPROVED HORIZONTAL ASSEMBLY. IT |
| ONLY SPECIFIES THE WALL ASSEMBLY UL-U311. PROVIDE |
| COMPLETE DETAILS AND SPECIFICATIONS FOR APPROVED |
| HORIZONTAL FIRE RATED ASSEMBLY AS REQUIRED . SEC. 420.3 |
| FBC. |
| |
| 4-SECOND FLOOR WINDOWS NEED TO COMPLY WITH THE WINDOW |
| OPENING CONTROL DEVICES REQUIRED BY SEC. 702.4 |
| FBC-EXISTING BUILDING. |
| NOTE: PROVIDE INFORMATION SHOWING COMPLIANCE WITH ASTM |
| F2090. |
| |
| 5- ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, |
| AND SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING AS REQUIRED BY SEC. |
| 801.3 FBC-EXISTING BUILDING. SHOW COMPLIANCE WITH THE |
| SOUND TRANSMISSION FOR FLOOR/CEILING ASSEMBLY. |
| FLOORING UNDERLAYMENT |
| SOUND INSULATION MATERIAL: |
| A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE |
| DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84 |
| OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION |
| (2017). |
| |
| B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS |
| (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS |
| REQUIRED BY SEC. 1207.2 OF FBC 6TH EDITION (2017). |
| |
| C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS |
| (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS |
| REQUIRED BY SEC. 1207.3 OF FBC 6TH EDITION (2017). |
| |
| 6-DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS |
| REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF |
| SPECIFYING SCREWS, THEN SPECIFY SIZE AND NUMBER OF |
| SCREWS. IF SPECIFYING ROOF TILE ADHESIVE, THEN SPECIFY |
| PADDY SIZE AND PRODUCT APPROVAL IS REQUIRED. REPEAT |
| COMMENT. ENGINEER TO SPECIFY FASTENING. THIS IS NOT BY |
| OTHERS. |
| |
| 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.001 FOR: |
| NOTE: THIS MAY BE SUBMITTED LATER AS DEFERRED |
| SUBMITTAL, BUT BEFORE INSTALLATION (NO FEES). |
| |
| A) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY |
| IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| DESIGN PRESSURES OF SEC. 1609 FBC. NOTE: IF THE |
| SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR |
| ALL ROOF ZONES, THEN SIGNED AND SEALED RAS 117 |
| CALCULATIONS ARE REQUIRED. |
| |
| B) ROOF TILE. |
| |
| C) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF |
| RECORD. AND SPECIFY PADDY SIZE. SEE ROOF TILE PRODUCT |
| APPROVAL FOR LISTED ADHESIVES. |
| |
| 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 9- BASED ON THE MECHANICAL PLANS SUBMITTED, PROVIDE |
| DETAILS AND SPECIFICATIONS SHOWING HOW THE A/C DUCTWORK |
| IS GOING TO BE INSTALLED. REMEMBER THAT THERE IS A FIRE |
| RATED FLOOR/CEILING ASSEMBLY SEPARATING THE APT ABOVE. |
| SEC. 711 FBC-BUILDING. |
| NEED PLANS AND SPECIFICATIONS FOR THE CONSTRUCTION OF |
| THE SOFFITS FOR A/C WORK. |
| |
| 10- PROVIDE COMPLETE DETAILS ANS SPECIFICATIONS FOR THE |
| REPLACEMENT OF EXTERIOR WOOD STUDS. SPECIFY ALL |
| CONNECTORS. SEC. 1609.1 FBC. |
| |
| 11-ROOF FRAMING PLAN ON SHEET S1A: |
| A) PROVIDE COMPLETE SECTION/DETAIL AT CANOPY ENTRY FOR |
| APT #2 AND APT #3. IT'S NOT CLEAR HOW THE ROOF IS |
| SUPPORTED. FRONT ELEVATION CALLS FOR COLUMNS, BUT ROOF |
| FRAMING DETAIL DOESN'T SPECIFY ANY. SEC. 1609.1 FBC. |
| |
| B) LEDGER INFORMATION SHOWN ON THE ROOF FRAMING PLAN |
| DOESN'T MATCH LEDGER INFORMATION SHOWN ON SECTION 1 ON |
| SAME SHEET. REVISE AS REQUIRED. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| 12- PROVIDE COMPLETE INFORMATION FOR THE FIRE RATING |
| ASSEMBLY BELOW THE STAIRS AND BY THE PANTRY CLOSET ON |
| FIRST FLOOR KITCHEN. SEC. 420.2 AND 420.3 FBC. |
| |
| |
| ARCHITECTS-ENGINEERS |
| FLORIDA STATUTE 553.80(2)(B): |
| WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| PERMIT FEE ATTRIBUTED TO PLANS REVIEW |
| |
| NOTE: |
| ENGINEER OF RECORD TO PROVIDE RESPONSE LETTER |
| ADDRESSING EACH COMMENT TO AVOID PLAN REVIEW FEES AS |
| REQUIRED BY FLORIDA STATUTE 553.80(2)(B). |
| |
| ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY |
| REVIEWED DRAWINGS. DON'T STAPLE OLD DRAWINGS TO PLANS. |
| |