2018-05-02 18:24:20 | 1- THE MINIMUM ATTACHMENT RESISTANCE (26.1 FT-LBF) OF |
| ADHESIVE SELECTED ON PAGE 5 OF 6 OF NOA 16-0112.08 |
| SUBMITTED DOESN'T MEET THE MINIMUM ATTACHMENT |
| RESISTANCE OF TABLE 2A OF FRSA 5TH EDITION (REVISED). |
| REVISE AS REQUIRED. |
| |
| ORIGINAL COMMENT: |
| DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS |
| REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF |
| SPECIFYING SCREWS, THEN SPECIFY SIZE AND NUMBER OF |
| SCREWS. IF SPECIFYING ROOF TILE ADHESIVE, THEN SPECIFY |
| PADDY SIZE AND PRODUCT APPROVAL IS REQUIRED. |
| |
| 2- SELECTED ASSEMBLY ON PAGE 28-29 OF NOA 14-1030.02 |
| SUBMITTED DOESN'T MEET THE DESIGN PRESSURES FOR ALL |
| ROOF ZONES. NEED SIGNED AND SEALED RAS 117 |
| CALCULATIONS. SEE GENERAL LIMITATION #7 ON LAST PAGE OF |
| NOA. |
| NOTE: THIS MAY BE SUBMITTED LATER AS DEFERRED |
| SUBMITTAL, BUT BEFORE INSTALLATION. |
| |
| ORIGINAL COMMENT: |
| FLAT ROOF NOA 15-1020.01 SUBMITTED: CLEARLY MARK WHICH |
| APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY |
| COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. 1609 |
| FBC-BUILDING. IF THE SELECTED ASSEMBLY DOESN'T MEET THE |
| DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND |
| SEALED RAS 117 CALCULATIONS ARE REQUIRED. RAS 117 |
| CALCULATIONS ARE REQUIRED TO HAVE THE FLORIDA |
| ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN SIGNATURE, |
| COPIES OR OTHER FACSIMILES ARE NOT ACCEPTABLE. FAC |
| 61G15 - 23.002 DIGITAL SIGNATURES ARE ONLY ACCEPTABLE |
| FOR ELECTRONICALLY TRANSMITTED PLANS AND DOCUMENTS. |
| |
| 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.001 FOR: |
| NOTE: THIS MAY BE SUBMITTED LATER AS DEFERRED |
| SUBMITTAL, BUT BEFORE INSTALLATION. |
| |
| A) NO SUBMITTED. PROVIDE ACTUAL PRODUCT APPROVAL LISTED |
| ON THE NOA FOR ROOF TILE. |
| |
| ORIGINAL COMMENT: |
| ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF |
| RECORD ON ITEM #12 ABOVE. AND SPECIFY PADDY SIZE. SEE |
| ROOF TILE PRODUCT APPROVAL FOR LISTED ADHESIVES. |
| |
| |
| ROOF TILE NOA 16-0112.08 |
| |
| |