2018-05-01 17:28:50 | RESIDENTIAL (R2) ALTERATION, SECOND BUILDING REVIEW |
| CHECKLIST. |
| CODE: FBC 6TH EDITION (2017). |
| |
| |
| 1(A)REVISE ALL ENERGY CALCULATIONS SUBMITTED. |
| A)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF |
| FORM. NEED OWNER'S NAME. NEED CORRECT BUILDER'S NAME. |
| SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| |
| B) THIS IS NOT NEW CONSTRUCTION. REVISE ITEM #1. SEC. |
| R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| |
| C) WALL INSULATION R-VALUE SHOWN ON ITEM #9A DOESN'T |
| MATCH PLANS. SEE WALL TYPE LEGEND ON SHEET CVR FOR |
| EXTERIOR WALL SPECIFICATIONS AND REVISE AS REQUIRED. |
| SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| |
| D) CLARIFY WHY THE FLOOR INFORMATION SHOWN ON PAGE 2 OF |
| 4 DOESN'T SHOW THE R-VALUE SPECIFIED FOR THE RAISED |
| FLOOR ON PAGE 1 OF 4. SEC. R101.5.1.1.2 FBC- ENERGY |
| CONSERVATION. |
| |
| E) REVISE ROOF INFORMATION SHOWN ON PAGE 2 OF 4. THERE |
| IS NO ROOF ABOVE THIS APARTMENT. SEC. R101.5.1.1.2 FBC- |
| ENERGY CONSERVATION. |
| |
| F) REVISE ATTIC INFORMATION SHOWN ON PAGE 2 OF 4. THERE |
| IS NO ATTIC ABOVE THIS APARTMENT. SEC. R101.5.1.1.2 |
| FBC- ENERGY CONSERVATION. |
| |
| G) REVISE WALLS INFORMATION SHOWN ON PAGE 2 OF 4. |
| ORIENTATION OF WALLS DON'T MATCH ACTUAL ORIENTATION OF |
| BUILDING. SEE PLANS AND REVISE AS REQUIRED. SEC. |
| R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| |
| H) REVISE WINDOWS INFORMATION SHOWN ON PAGE 3 OF 4. |
| ORIENTATION DOESN'T MATCH ACTUAL ORIENTATION OF |
| BUILDING. ALSO, REVISE AREA AND OVERHANG DEPTH AND |
| SEPARATION TO MATCH PLANS. SEC. R101.5.1.1.2 FBC- |
| ENERGY CONSERVATION. |
| |
| I) PROVIDE THE NAME OF PERSON PERFORMING THE ANALYSIS |
| AND GENERATING THE REPORT AS REQUIRED BY SEC. |
| R405.4.2.1 FBC- ENERGY CONSERVATION. |
| |
| J)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY |
| CONSERVATION. |
| |
| IMPORTANT NOTES: |
| (1) BASED ON THE ENERGY CALCULATIONS SUBMITTED, THIS |
| PROJECT REQUIRES AN ENVELOPE LEAKAGE TEST REPORT WITH |
| ENVELOPE LEAKAGE NO GREATER THAN 4.00 ACH50 |
| (R402.4.1.2) |
| |
| (2)LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND |
| SHGC FACTOR IS REQUIRED WHEN THE ENERGY CALCULATIONS |
| ARE NOT USING THE DEFAULT FACTOR. |
| |
| 1(B) ENGINEER OF RECORD TO COORDINATE WITH ENERGY |
| CALCULATIONS SUBMITTED. PROVIDE SPECIFICATIONS FOR THE |
| INSULATION ON THE RAISED FLOOR AS SPECIFIED ON ITEM 8A |
| OF THE ENERGY CALCULATIONS. SEC. R103.2 FBC- ENERGY |
| CONSERVATION. |
| |
| ORIGINAL COMMENT: |
| PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED BY |
| SEC. 908 FBC-EXISTING BUILDING. |
| |
| 2- SHEET CVR: |
| A)THIS IS NOT "MULTI-FAMILY DETACHED RESIDENCE(R2)". |
| THIS DOESN'T MAKE SENSE. IF THEY WERE DETACHED, THEN |
| THEY WOULD BE SINGLE FAMILY RESIDENCES. THE BUILDING |
| CODE IN EFFECT IS THE 2017 NOT 2014. ALTERATION LEVEL 3 |
| NEEDS TO COMPLY WITH CHAPTER 9. REVISE INFORMATION |
| SHOWN ON "SCOPE OF WORK" AS REQUIRED. |
| |
| ORIGINAL COMMENT: |
| THIS IS NOT A SINGLE FAMILY RESIDENCE. THIS IS |
| MULTIFAMILY BUILDING (R2). REVISE ALL THE INFORMATION |
| SHOWN ON THIS SHEET THAT REFERENCE THE SINGLE FAMILY |
| RESIDENCE AND ALL CODE SECTIONS REFERENCED. NEED TO |
| REFERENCE SECTIONS FROM THE FBC-BUILDING. |
| SEC. 310.4 FBC-BUILDING |
| |
| B) ALL FIRE RATED PARTITIONS NEED TO PROVIDE CONTINUITY |
| AS REQUIRED BY SEC. 708.4 FBC-BUILDING. REVISE ALL FIRE |
| RATED WALLS ASSEMBLIES AS REQUIRED TO MATCH PROPOSED |
| INSTALLATION. DETAIL "F" ON SHEET S1A IS UNFEASIBLE TO |
| BUILD THE WAY IS SHOWN. INTERIOR GYPSUM BOARD CAN NOT |
| GO THRU THE FLOOR ASSEMBLY. ALSO, BOTTOM AND TOP |
| STRUCTURAL CONNECTIONS NEED MORE INFORMATION. CLEARLY |
| SPECIFY ALL CONNECTORS SHOWING THE LOAD PATH (FOR |
| EXAMPLE: TOP AND BOTTOM PLATES TO THE EXISTING |
| STRUCTURAL FRAMING MEMBERS). NOTE: COORDINATE ALL WALL |
| DETAILS WITH FIRE RATED BEARING WALLS AND NON BEARING |
| WALLS TO MATCH PROPOSED INSTALLATION. |
| |
| ORIGINAL COMMENT: |
| WALL TYPE LEGEND: FIRE RATED WALL "F" DOESN'T MATCH |
| FIRE RATED WALL ON SHEET S2. REVISE AS REQUIRED. AND, |
| PROVIDE COMPLETE AND CLEAR WALL SECTION THAT MATCHES |
| PROPOSED INSTALLATION. |
| NOTE: NEED TO PROVIDE COMPLETE DETAILS AND SPECS FOR |
| ALL WALLS FOR TENANT SEPARATION BETWEEN APT #1 AND APT |
| #2. INCLUDING THE BEARING WALLS. SEC. 703.1 |
| FBC-BUILDING. INCLUDING THE FOYER AREA THAT WAS DIVIDED |
| TO ALLOW SEPARATE ENTRANCE TO APT ABOVE. COORDINATE |
| WITH UL ASSEMBLY U305 SPECIFIED ON SHEET S2. |
| |
| C) COMPLIED. EXISTENT RAILING TO REMAIN. |
| |
| 3- BEARING WALL DETAIL "G" ON SHEET S1 DOESN'T SEEM TO |
| COMPLY WITH A BEARING WALL. IT IS BEARING ON PLYWOOD |
| INSTEAD OF A SUPPORTING STRUCTURAL MEMBER. MISMATCHING |
| METAL AND WOOD CONNECTORS?. THERE IS NO COORDINATION |
| WITH FIRE RATED PARTITIONS SHOWN ON SHEET S1A. ALSO |
| NEED TO COORDINATE WITH ITEM #2B ABOVE. CONNECTIONS AT |
| TOP AND BOTTOM DON'T SEEM TO WORK THE WAY THEY ARE |
| SPECIFIED. FIRST FLOOR DEMOLITION PLAN CALLS FOR |
| EXISTING GIRDER BEAM BY THE STAIRWAY AREA. ACCORDING TO |
| CITY RECORDS, THERE WAS A CONTINUOUS WALL IN THIS AREA |
| NOT A BEAM. ENGINEER NEEDS TO CLEARLY IDENTIFY ALL |
| BEARING WALLS AND CLEARLY PROVIDE DETAILS AND |
| SPECIFICATIONS SHOWING REINFORCEMENT AT THE ENDS OF |
| PROPOSED OPENINGS. |
| |
| ORIGINAL COMMENT: |
| INFORMATION ON BEARING WALLS IS NOT CLEAR AND IS |
| INCOMPLETE. CLEARLY IDENTIFY ALL BEARING AND NON |
| BEARING WALLS. BEARING WALL TO BE REMOVED AND HOW ARE |
| THEY REINFORCED. COORDINATE DEMOLITION PLANS WITH |
| PROPOSED PLANS. SEC. 907 FBC-EXISTING BUILDING. |
| NOTE: CLARIFY WHY THE 18"X18" COLUMN DOESN'T ALIGN WITH |
| COLUMN ABOVE? |
| |
| 4- TYPICAL WINDOW OPENING FRAMING DETAIL SUBMITTED |
| DOESN'T PROVIDE ANY INFORMATION FOR CONNECTORS AT THE |
| TOP OF THE WALL AND WINDOW HEADER. IT DOESN'T PROVIDE |
| THE LOAD PATH. ALSO, IT DOESN'T SHOW ANY FULL LENGTH |
| STUDS AT THE ENDS OF THE OPENING. |
| |
| ORIGINAL COMMENT: |
| CLEARLY IDENTIFY ALL EXTERIOR STRUCTURAL WALLS THAT ARE |
| DAMAGED AND PROVIDE COMPLETE STRUCTURAL DETAILS |
| IDENTIFYING THE STRUCTURAL FRAMING MEMBERS AND ALL |
| CONNECTORS. TYPICAL STRAPPING PLAN ON SHEET S1 IS |
| INSUFFICIENT. SEC. 907 FBC-EXISTING BUILDING. |
| |
| 5- NO INFORMATION SUBMITTED FOR NEW COLUMNS SHOWN ON |
| THE PROPOSED SOUTH ELEVATION. |
| |
| ORIGINAL COMMENT: |
| PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR NEW |
| COLUMNS SHOWN ON SHEET S2. SPECIFY ALL FRAMING MEMBERS |
| AND CONNECTORS. SEC. 1609 FBC-BUILDING. |
| |
| 6- MISSING INFORMATION ABOUT ROOF SHEATHING SPECS AND |
| FASTENING. BEAM CONNECTIONS, ETC. |
| |
| ORIGINAL COMMENT: |
| PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS FOR |
| NEW ROOF SHOWN ON SHEET S2 ON PROPOSED SOUTH ELEVATION. |
| SPECIFY ALL FRAMING MEMBERS, PLYWOOD, CONNECTORS, ETC. |
| SEC. 1609 FBC-BUILDING. |
| |
| 7- SAME NOTE APPEARS ON PROPOSED SOUTH ELEVATION. |
| |
| ORIGINAL COMMENT: |
| PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW |
| EXISTING 4X4 POST CAN BE REPAIR/FIX AS SPECIFIED ON |
| PROPOSED SOUTH ELEVATION ON SHEET S2. SEC. 1609 |
| FBC-BUILDING. |
| |
| 8- SHEET S1: |
| A) REPEAT COMMENT. DETAIL F ON SHEET S1A REFERENCE ON |
| THE RESPONSE LETTER DOESN'T PROVIDE THE COMPLETE |
| SPECIFICATIONS FOR THE FLOOR/CEILING FIRE RATED |
| ASSEMBLY AND THE DETAIL F NEEDS TO BE REVISED. |
| COORDINATE WITH ITEM #2B ABOVE. |
| |
| ORIGINAL COMMENT: |
| PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| FLOOR/CEILING ASSEMBLY FOR TENANT SEPARATION WITH THE |
| APT ON THE SECOND FLOOR. SEC. 901.2 FBC-EXISTING |
| BUILDING. |
| |
| B)WINDOW "C" DOESN'T COMPLY. |
| |
| ORIGINAL COMMENT: |
| PROPOSED BEDROOM WINDOWS DON'T COMPLY WITH THE |
| EMERGENCY ESCAPE AND RESCUE SEC. 1030 FBC-BUILDING |
| (SEC. 702.5 FBC-EXISTING BUILDING). |
| |
| C) NOT ADDRESSED AT ALL. |
| |
| ORIGINAL COMMENT: |
| SECOND FLOOR WINDOWS NEED TO COMPLY WITH THE WINDOW |
| CONTROL DEVICES REQUIRED BY SEC. 702.4 FBC-EXISTING |
| BUILDING. |
| |
| D) NEED TO COORDINATE WITH ITEM #2B ABOVE. ALSO, NEED |
| TO PROVIDE DETAILS AND SPECIFICATIONS SHOWING HOW THE |
| NEW WALL WILL PROVIDE CONTINUOUS FIRE RATING ON BOTH |
| SIDES OF THE WALL CONSIDERING THE EXISTING STAIRS. HOW |
| THE EXISTING STAIRS WILL BE SUPPORTED. ALSO, NEED TO |
| PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR FIRE |
| SEPARATION OF KITCHEN AREA ON APT #1 AND APT ABOVE. |
| INCLUDE BOTTOM OF STAIRS AND PANTRY AREA OF FIRST FLOOR |
| KITCHEN. |
| |
| ORIGINAL COMMENT: |
| PROVIDE COMPLETE WALL SECTION FOR NEW WALL AT FOYER |
| AREA SEPARATING APT #1 FROM APT ABOVE. SEC. 903.1 |
| FBC-EXISTING BUILDING. |
| |
| E)NOT ADDRESSED. RESPONSE LETTER REFERENCES DETAIL WALL |
| G. THIS DETAIL DOESN'T APPLY TO THE REQUESTED ITEM. |
| |
| ORIGINAL COMMENT: |
| PROVIDE COMPLETE OPENING FRAMING DETAIL AND |
| SPECIFICATIONS FOR NEW DOOR AT APT ABOVE. SPECIFY ALL |
| FRAMING MEMBERS AND CONNECTORS. SEC. 907 FBC-EXISTING |
| BUILDING. |
| |
| F) STILL NOT CLEAR. SHOWING BOTH. |
| |
| ORIGINAL COMMENT: |
| TYPICAL INTERIOR PARTITION DETAIL IS NOT CLEAR. IS IT A |
| WOOD FRAMED WALL OR METAL FRAMED WALL. SEC. 107.2.1 |
| CITY AMENDMENTS. |
| |
| G)COMPLIED. |
| |
| 9- SHEET S2: |
| A) COMPLIED. |
| |
| B) REVISE SPECIFICATIONS: SPECIFY TWO LAYERS OF |
| WATER-RESISTIVE BARRIER AS REQUIRED BY SEC. 2510.6 |
| FBC-BUILDING. AND, SPECIFY NO LESS THAN THREE COATS OF |
| STUCCO AS REQUIRED BY SEC. 2512.1 FBC-BUILDING. |
| |
| ORIGINAL COMMENT: |
| PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| APPLICATION OF NEW STUCCO FINISH OVER EXISTING STUCCO |
| FINISH AS SPECIFIED ON PROPOSED SOUTH ELEVATION. SEC. |
| 2510 FBC-BUILDING. |
| |
| 10- COMPLIED. |
| |
| 11- RESPONSE LETTER STATES R-13 INSULATION ON WALLS, |
| R-30 INSULATION ON 1ST FLOOR CEILING. THERMAL |
| INSULATION AND SOUND INSULATION ARE TWO DIFFERENT |
| THINGS. NEED TO COMPLY WITH THE SOUND AND IMPACT |
| INSULATION AS REQUIRED BY SEC. 1207. PROVIDE |
| SPECIFICATIONS ON PLANS. NOTE: COPIES OF THE REQUIRED |
| TESTING FOR SPECIFIC PRODUCTS TO BE INSTALLED MAY BE |
| SUBMITTED LATER AS DEFERRED SUBMITTAL, BUT BEFORE |
| INSTALLATION. |
| |
| ORIGINAL COMMENT: |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING AS REQUIRED BY SEC. |
| 801.3 FBC-EXISTING BUILDING. SHOW COMPLIANCE WITH THE |
| SOUND TRANSMISSION FOR FLOOR/CEILING ASSEMBLY AND |
| TENANT SEPARATION WALLS AS REQUIRED BY SEC. 1207 |
| FBC-BUILDING. |
| |
| 12- THE MINIMUM ATTACHMENT RESISTANCE (26.1 FT-LBF) OF |
| ADHESIVE SELECTED ON PAGE 5 OF 6 OF NOA 16-0112.08 |
| SUBMITTED DOESN'T MEET THE MINIMUM ATTACHMENT |
| RESISTANCE OF TABLE 2A OF FRSA 5TH EDITION (REVISED). |
| REVISE AS REQUIRED. |
| |
| ORIGINAL COMMENT: |
| DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS |
| REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF |
| SPECIFYING SCREWS, THEN SPECIFY SIZE AND NUMBER OF |
| SCREWS. IF SPECIFYING ROOF TILE ADHESIVE, THEN SPECIFY |
| PADDY SIZE AND PRODUCT APPROVAL IS REQUIRED. |
| |
| 13- SELECTED ASSEMBLY ON PAGE 28-29 OF NOA 14-1030.02 |
| SUBMITTED DOESN'T MEET THE DESIGN PRESSURES FOR ALL |
| ROOF ZONES. NEED SIGNED AND SEALED RAS 117 |
| CALCULATIONS. SEE GENERAL LIMITATION #7 ON LAST PAGE OF |
| NOA. |
| NOTE: THIS MAY BE SUBMITTED LATER AS DEFERRED |
| SUBMITTAL, BUT BEFORE INSTALLATION. |
| |
| ORIGINAL COMMENT: |
| FLAT ROOF NOA 15-1020.01 SUBMITTED: CLEARLY MARK WHICH |
| APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY |
| COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. 1609 |
| FBC-BUILDING. IF THE SELECTED ASSEMBLY DOESN'T MEET THE |
| DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND |
| SEALED RAS 117 CALCULATIONS ARE REQUIRED. RAS 117 |
| CALCULATIONS ARE REQUIRED TO HAVE THE FLORIDA |
| ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN SIGNATURE, |
| COPIES OR OTHER FACSIMILES ARE NOT ACCEPTABLE. FAC |
| 61G15 - 23.002 DIGITAL SIGNATURES ARE ONLY ACCEPTABLE |
| FOR ELECTRONICALLY TRANSMITTED PLANS AND DOCUMENTS. |
| |
| 14- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.001 FOR: |
| NOTE: THIS MAY BE SUBMITTED LATER AS DEFERRED |
| SUBMITTAL, BUT BEFORE INSTALLATION. |
| |
| A)SHEET S1 DOESN'T SHOW WINDOW MULLION DETAIL AS |
| REFERENCED ON HE RESPONSE LETTER. CLEARLY IDENTIFY |
| MULLION SIZE ON PRODUCT APPROVAL. |
| |
| ORIGINAL COMMENT: |
| WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY MARK |
| MULLION SIZE TO VERIFY COMPLIANCE WITH THE CALCULATED |
| DESIGN PRESSURES. |
| |
| B) NO SUBMITTED. PROVIDE ACTUAL PRODUCT APPROVAL LISTED |
| ON THE NOA FOR ROOF TILE. |
| |
| ORIGINAL COMMENT: |
| ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF |
| RECORD ON ITEM #12 ABOVE. AND SPECIFY PADDY SIZE. SEE |
| ROOF TILE PRODUCT APPROVAL FOR LISTED ADHESIVES. |
| |
| C)NEED PRODUCT APPROVAL FOR ALL CONNECTORS SPECIFIED ON |
| ALL PLANS AND DETAILS NOT JUST THE ONES SHOWN ON THE |
| ROOF FRAMING PLAN. |
| |
| ORIGINAL COMMENT: |
| ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL |
| COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR |
| DESIGN PROFESSIONAL TO LIST THE FLORIDA PRODUCT |
| APPROVAL NUMBER NEXT TO EACH SPECIFIED CONNECTOR. |
| |
| 15- THERE ARE SOME PRODUCT APPROVALS THAT ARE NOT |
| REVIEWED (ENTRY DOOR). |
| |
| ORIGINAL COMMENT: |
| 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 16-NEW COMMENT: |
| BASED ON THE MECHANICAL PLANS SUBMITTED, PROVIDE |
| DETAILS AND SPECIFICATIONS SHOWING HOW THE A/C DUCTWORK |
| IS GOING TO BE INSTALLED. REMEMBER THAT THERE IS A FIRE |
| RATED FLOOR/CEILING ASSEMBLY SEPARATING THE APT ABOVE. |
| SEC. 711 FBC-BUILDING. |
| |
| |
| |
| NOTE: |
| ENGINEER OF RECORD TO PROVIDE RESPONSE LETTER |
| ADDRESSING EACH COMMENT TO AVOID PLAN REVIEW FEES AS |
| REQUIRED BY FLORIDA STATUTE 553.80(2)(B). |
| |
| ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY |
| REVIEWED DRAWINGS. DON'T STAPLE OLD DRAWINGS TO PLANS. |
| |
| |