Plan Review Notes For Permit 18021046 |
Permit Number |
18021046 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-03-16 11:40:13 | 1- FLAT ROOF NOA 15-1020.01 SUBMITTED: CLEARLY MARK | | WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO | | VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. | | 1609 FBC-BUILDING. IF THE SELECTED ASSEMBLY DOESN'T | | MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN | | SIGNED AND SEALED RAS 117 CALCULATIONS ARE REQUIRED. | | RAS 117 CALCULATIONS ARE REQUIRED TO HAVE THE FLORIDA | | ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN SIGNATURE, | | COPIES OR OTHER FACSIMILES ARE NOT ACCEPTABLE. FAC | | 61G15 - 23.002 DIGITAL SIGNATURES ARE ONLY ACCEPTABLE | | FOR ELECTRONICALLY TRANSMITTED PLANS AND DOCUMENTS. | | | | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | FAC 61G20-3.001 FOR: | | A) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF | | RECORD. AND SPECIFY PADDY SIZE. SEE ROOF TILE PRODUCT | | APPROVAL FOR LISTED ADHESIVES. | | | | | | APPROVED: | | 1) ENTEGRA ROOF TILE NOA 16-0112.08 | | |
|