Plan Review Notes
Plan Review Notes For Permit 18021046
Permit Number 18021046
Review Stop R
Sequence Number 1
Notes
Date Text
2018-03-16 11:40:131- FLAT ROOF NOA 15-1020.01 SUBMITTED: CLEARLY MARK
 WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 1609 FBC-BUILDING. IF THE SELECTED ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN
 SIGNED AND SEALED RAS 117 CALCULATIONS ARE REQUIRED.
 RAS 117 CALCULATIONS ARE REQUIRED TO HAVE THE FLORIDA
 ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN SIGNATURE,
 COPIES OR OTHER FACSIMILES ARE NOT ACCEPTABLE. FAC
 61G15 - 23.002 DIGITAL SIGNATURES ARE ONLY ACCEPTABLE
 FOR ELECTRONICALLY TRANSMITTED PLANS AND DOCUMENTS.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD. AND SPECIFY PADDY SIZE. SEE ROOF TILE PRODUCT
 APPROVAL FOR LISTED ADHESIVES.
  
  
 APPROVED:
 1) ENTEGRA ROOF TILE NOA 16-0112.08
  