Plan Review Notes
Plan Review Notes For Permit 18021046
Permit Number 18021046
Review Stop P
Sequence Number 1
Notes
Date Text
2018-03-14 08:45:191ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE WATER ISOMETRIC SHOW EXISTING AND NEW. PER
 WPB AMEND TO FBC 107.3.5.1.3(13)
  
 2. THE SOIL STACK FOR 2ND FLOOR IS NOT SHOWN ON 1ST
 FLOOR ISOMETRIC, THE LAUNDRY IS NOT SHOWN ON 2ND FLOOR
 ISOMETRIC SHOW ALL NEW AND EXISTING PIPING AND MARK IT
 AS EXISTING OR NEW. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 3. BACKFLOW REQUIRED ON WATER SERVICE SHOW ON WATER
 ISOMETRIC NEW OR EXISTING. PER WPB UTILITIES DEPARTMENT
 CROSS CONNECTION MANUAL
  
 4. THE COVER SHEET UNDER SCOPE OF WORK LISTED AS A
 SINGLE FAMILY HOME THIS DRELLING IS AN R2 OCCUPANCY PER
 FBC 310.4 PLEASE CLARIFY.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  