2018-03-20 09:15:17 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) SHEET CVR - THE PROPOSED PROJECT CHANGES A DUPLEX |
| INTO A TRIPLEX CREATING A NEW APARTMENT BUILDING. |
| |
| PER NFPA 101, CHAPTER 3, DEFINITIONS |
| |
| 3.3.36.3* APARTMENT BUILDING. A BUILDING OR PORTION |
| THEREOF |
| CONTAINING THREE OR MORE DWELLING UNITS WITH |
| INDEPENDENT |
| COOKING AND BATHROOM FACILITIES. (SAF-RES) |
| |
| PLEASE CORRECT. |
| |
| |
| 2) SHEET CVR - THERE IS NO APPLICABLE REFERNECED FIRE |
| CODE. |
| |
| THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| 6TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| APPLICABLE CODES OR STANDARDS. |
| FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| OF NFPA 13, 2013 EDITION. |
| FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| NFPA 72, 2013 EDITION. |
| CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| NFPA 241, 2013 EDITION. |
| FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| OF NFPA 10, 2013 EDITION. |
| ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION. |
| |
| PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT AND COMPLIANCE |
| |
| |
| 3) SHEET S 1 - A FIRE SPRINKLER SYSTEM IS REQUIRED. |
| |
| PER NFPA 101, CHAPTER 30, NEW APARTMENT BUILDINGS. |
| |
| 30.3.5 EXTINGUISHMENT REQUIREMENTS. |
| 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY |
| AN APPROVED, |
| SUPERVISED AUTOMATIC SPRINKLER SYSTEM INSTALLED IN |
| ACCORDANCE WITH |
| 30.3.5.2. |
| 30.3.5.2 WHERE AN AUTOMATIC SPRINKLER SYSTEM IS |
| INSTALLED, EITHER FOR |
| TOTAL OR PARTIAL BUILDING COVERAGE, THE SYSTEM SHALL BE |
| INSTALLED IN |
| ACCORDANCE WITH SECTION 9.7, AS MODIFIED BY 30.3.5.3 |
| AND 30.3.5.4. IN |
| BUILDINGS FOUR OR FEWER STORIES ABOVE GRADE PLANE, |
| SYSTEMS IN |
| ACCORDANCE WITH NFPA 13R, STANDARD FOR THE INSTALLATION |
| OF |
| SPRINKLER SYSTEMS IN LOW-RISE RESIDENTIAL OCCUPANCIES, |
| SHALL BE |
| PERMITTED. |
| |
| PLEASE PROVIDE FOR THE REQUIREMENT AS WELL AS 61G |
| DOCUMENTS PER FLORIDA STATUTE WITH THIS MASTER PERMIT. |
| |
| |
| |
| 4) THE FIRE SPRINKLER SYSTEM IS REQUIRED TO BE |
| SUPERVISED AND MONITORED. |
| |
| PER NFPA 101, CHAPTER 9, FIRE PREOTECTIONS SYSTEMS. |
| |
| 9.7.2 SUPERVISION. |
| 9.7.2.1* SUPERVISORY SIGNALS. |
| 9.7.2.1.1 WHERE SUPERVISED AUTOMATIC SPRINKLER SYSTEMS |
| ARE REQUIRED BY |
| ANOTHER SECTION OF THIS CODE, SUPERVISORY ATTACHMENTS |
| SHALL BE INSTALLED |
| AND MONITORED FOR INTEGRITY IN ACCORDANCE WITH NFPA 72, |
| NATIONAL FIRE |
| ALARM AND SIGNALING CODE, AND A DISTINCTIVE SUPERVISORY |
| SIGNAL SHALL BE |
| PROVIDED TO INDICATE A CONDITION THAT WOULD IMPAIR THE |
| SATISFACTORY |
| OPERATION OF THE SPRINKLER SYSTEM. |
| 9.7.2.1.2 SUPERVISORY SIGNALS SHALL SOUND AND SHALL BE |
| DISPLAYED EITHER AT |
| A LOCATION WITHIN THE PROTECTED BUILDING THAT IS |
| CONSTANTLY ATTENDED BY |
| QUALIFIED PERSONNEL OR AT AN APPROVED, REMOTELY LOCATED |
| RECEIVING |
| FACILITY. |
| 9.7.2.2 ALARM SIGNAL TRANSMISSION. |
| 9.7.2.2.1 WHERE SUPERVISION OF AUTOMATIC SPRINKLER |
| SYSTEMS IS REQUIRED |
| BY ANOTHER SECTION OF THIS CODE, WATERFLOW ALARMS SHALL |
| BE TRANSMITTED |
| TO AN APPROVED, PROPRIETARY ALARM-RECEIVING FACILITY, A |
| REMOTE STATION, A |
| CENTRAL STATION, OR THE FIRE DEPARTMENT. |
| |
| PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT AND COMPLIANCE |
| AS WELL AS SHOP DRAWING SUBMITTAL. |
| |
| |
| |
| 5) SHEET S 1 - THERE ARE MULTIPLE DIAMOND SHAPED |
| REFERNCES THAT DO NOT COINCIDE WITH ANY DRAWINGS OR |
| SHEETS. |
| |
| PLEASE REVIEW AND PROVIDE THEIR DRAWING REFERENCES. |
| |
| |
| |
| 6) SHEET S 1 - THERE APPEARS TO BE 1 HOUR RATED WALLS |
| THAT INTERSECT WITH BEARING WALLS. THE BEARING WALLS DO |
| NOT HAVE ANY RATING INDICATED. |
| |
| 30.3.7 SUBDIVISIONS OF BUILDING SPACES. BUILDINGS SHALL |
| BE |
| SUBDIVIDED IN ACCORDANCE WITH 30.3.7.1 OR 30.3.7.2. |
| 30.3.7.1 IN BUILDINGS NOT MEETING THE REQUIREMENT OF |
| 30.3.7.2, |
| DWELLING UNITS SHALL BE SEPARATED FROM EACH OTHER BY |
| WALLS AND |
| FLOORS CONSTRUCTED AS FIRE BARRIERS HAVING A MINIMUM |
| 1-HOUR FIRE |
| RESISTANCE RATING. |
| |
| 30.3.7.2 IN BUILDINGS PROTECTED THROUGHOUT BY AN |
| APPROVED, |
| SUPERVISED AUTOMATIC SPRINKLER SYSTEM, DWELLING UNITS |
| SHALL BE |
| SEPARATED FROM EACH OTHER BY WALLS AND FLOORS |
| CONSTRUCTED AS FIRE |
| BARRIERS HAVING A MINIMUM ?-HOUR FIRE RESISTANCE |
| RATING. |
| |
| PLEASE REVIEW AND CORRECT WITH APPLICABLE RATED |
| CONSTRUCTION AND LISTING. |
| |
| |
| |
| 7) SHEET S 1 - THERE IS NO INDICATION OF ANY RATING OF |
| THE STAIRWELL EXIT ACCESS. |
| |
| 30.3.6 CORRIDORS. |
| 30.3.6.1 WALLS. EXIT ACCESS CORRIDOR WALLS SHALL COMPLY |
| WITH |
| 30.3.6.1.1 OR 30.3.6.1.2. |
| 30.3.6.1.1 IN BUILDINGS NOT COMPLYING WITH 30.3.6.1.2, |
| EXIT ACCESS |
| CORRIDOR WALLS SHALL CONSIST OF FIRE BARRIERS IN |
| ACCORDANCE WITH |
| SECTION 8.3 THAT HAVE NOT LESS THAN A 1-HOUR FIRE |
| RESISTANCE RATING. |
| 30.3.6.1.2 IN BUILDINGS PROTECTED THROUGHOUT BY AN |
| APPROVED, |
| SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| WITH |
| 30.3.5.2, CORRIDOR WALLS SHALL HAVE A MINIMUM ?-HOUR |
| FIRE |
| RESISTANCE RATING. |
| |
| PLEASE REVIEW AND CORRECT. |
| |
| |
| |
| 8) SHEET S 1 - THERE ARE NO REFERNECES TO ANY RATING |
| FOR THE CEILING/FLOOR ASSEMBLY. |
| |
| 30.3.7 SUBDIVISIONS OF BUILDING SPACES. BUILDINGS SHALL |
| BE |
| SUBDIVIDED IN ACCORDANCE WITH 30.3.7.1 OR 30.3.7.2. |
| 30.3.7.1 IN BUILDINGS NOT MEETING THE REQUIREMENT OF |
| 30.3.7.2, |
| DWELLING UNITS SHALL BE SEPARATED FROM EACH OTHER BY |
| WALLS AND |
| FLOORS CONSTRUCTED AS FIRE BARRIERS HAVING A MINIMUM |
| 1-HOUR FIRE |
| RESISTANCE RATING. |
| |
| 30.3.7.2 IN BUILDINGS PROTECTED THROUGHOUT BY AN |
| APPROVED, |
| SUPERVISED AUTOMATIC SPRINKLER SYSTEM, DWELLING UNITS |
| SHALL BE |
| SEPARATED FROM EACH OTHER BY WALLS AND FLOORS |
| CONSTRUCTED AS FIRE |
| BARRIERS HAVING A MINIMUM ?-HOUR FIRE RESISTANCE |
| RATING. |
| |
| PLEASE REVIEW AND CORRECT. |
| |
| |
| 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |