Plan Review Notes
Plan Review Notes For Permit 18021046
Permit Number 18021046
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-03-20 09:15:17THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET CVR - THE PROPOSED PROJECT CHANGES A DUPLEX
 INTO A TRIPLEX CREATING A NEW APARTMENT BUILDING.
  
 PER NFPA 101, CHAPTER 3, DEFINITIONS
  
 3.3.36.3* APARTMENT BUILDING. A BUILDING OR PORTION
 THEREOF
 CONTAINING THREE OR MORE DWELLING UNITS WITH
 INDEPENDENT
 COOKING AND BATHROOM FACILITIES. (SAF-RES)
  
 PLEASE CORRECT.
  
  
 2) SHEET CVR - THERE IS NO APPLICABLE REFERNECED FIRE
 CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2013 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2013 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2013 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2013 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT AND COMPLIANCE
  
  
 3) SHEET S 1 - A FIRE SPRINKLER SYSTEM IS REQUIRED.
  
 PER NFPA 101, CHAPTER 30, NEW APARTMENT BUILDINGS.
  
 30.3.5 EXTINGUISHMENT REQUIREMENTS.
 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY
 AN APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM INSTALLED IN
 ACCORDANCE WITH
 30.3.5.2.
 30.3.5.2 WHERE AN AUTOMATIC SPRINKLER SYSTEM IS
 INSTALLED, EITHER FOR
 TOTAL OR PARTIAL BUILDING COVERAGE, THE SYSTEM SHALL BE
 INSTALLED IN
 ACCORDANCE WITH SECTION 9.7, AS MODIFIED BY 30.3.5.3
 AND 30.3.5.4. IN
 BUILDINGS FOUR OR FEWER STORIES ABOVE GRADE PLANE,
 SYSTEMS IN
 ACCORDANCE WITH NFPA 13R, STANDARD FOR THE INSTALLATION
 OF
 SPRINKLER SYSTEMS IN LOW-RISE RESIDENTIAL OCCUPANCIES,
 SHALL BE
 PERMITTED.
  
 PLEASE PROVIDE FOR THE REQUIREMENT AS WELL AS 61G
 DOCUMENTS PER FLORIDA STATUTE WITH THIS MASTER PERMIT.
  
  
  
 4) THE FIRE SPRINKLER SYSTEM IS REQUIRED TO BE
 SUPERVISED AND MONITORED.
  
 PER NFPA 101, CHAPTER 9, FIRE PREOTECTIONS SYSTEMS.
  
 9.7.2 SUPERVISION.
 9.7.2.1* SUPERVISORY SIGNALS.
 9.7.2.1.1 WHERE SUPERVISED AUTOMATIC SPRINKLER SYSTEMS
 ARE REQUIRED BY
 ANOTHER SECTION OF THIS CODE, SUPERVISORY ATTACHMENTS
 SHALL BE INSTALLED
 AND MONITORED FOR INTEGRITY IN ACCORDANCE WITH NFPA 72,
 NATIONAL FIRE
 ALARM AND SIGNALING CODE, AND A DISTINCTIVE SUPERVISORY
 SIGNAL SHALL BE
 PROVIDED TO INDICATE A CONDITION THAT WOULD IMPAIR THE
 SATISFACTORY
 OPERATION OF THE SPRINKLER SYSTEM.
 9.7.2.1.2 SUPERVISORY SIGNALS SHALL SOUND AND SHALL BE
 DISPLAYED EITHER AT
 A LOCATION WITHIN THE PROTECTED BUILDING THAT IS
 CONSTANTLY ATTENDED BY
 QUALIFIED PERSONNEL OR AT AN APPROVED, REMOTELY LOCATED
 RECEIVING
 FACILITY.
 9.7.2.2 ALARM SIGNAL TRANSMISSION.
 9.7.2.2.1 WHERE SUPERVISION OF AUTOMATIC SPRINKLER
 SYSTEMS IS REQUIRED
 BY ANOTHER SECTION OF THIS CODE, WATERFLOW ALARMS SHALL
 BE TRANSMITTED
 TO AN APPROVED, PROPRIETARY ALARM-RECEIVING FACILITY, A
 REMOTE STATION, A
 CENTRAL STATION, OR THE FIRE DEPARTMENT.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT AND COMPLIANCE
 AS WELL AS SHOP DRAWING SUBMITTAL.
  
  
  
 5) SHEET S 1 - THERE ARE MULTIPLE DIAMOND SHAPED
 REFERNCES THAT DO NOT COINCIDE WITH ANY DRAWINGS OR
 SHEETS.
  
 PLEASE REVIEW AND PROVIDE THEIR DRAWING REFERENCES.
  
  
  
 6) SHEET S 1 - THERE APPEARS TO BE 1 HOUR RATED WALLS
 THAT INTERSECT WITH BEARING WALLS. THE BEARING WALLS DO
 NOT HAVE ANY RATING INDICATED.
  
 30.3.7 SUBDIVISIONS OF BUILDING SPACES. BUILDINGS SHALL
 BE
 SUBDIVIDED IN ACCORDANCE WITH 30.3.7.1 OR 30.3.7.2.
 30.3.7.1 IN BUILDINGS NOT MEETING THE REQUIREMENT OF
 30.3.7.2,
 DWELLING UNITS SHALL BE SEPARATED FROM EACH OTHER BY
 WALLS AND
 FLOORS CONSTRUCTED AS FIRE BARRIERS HAVING A MINIMUM
 1-HOUR FIRE
 RESISTANCE RATING.
  
 30.3.7.2 IN BUILDINGS PROTECTED THROUGHOUT BY AN
 APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM, DWELLING UNITS
 SHALL BE
 SEPARATED FROM EACH OTHER BY WALLS AND FLOORS
 CONSTRUCTED AS FIRE
 BARRIERS HAVING A MINIMUM ?-HOUR FIRE RESISTANCE
 RATING.
  
 PLEASE REVIEW AND CORRECT WITH APPLICABLE RATED
 CONSTRUCTION AND LISTING.
  
  
  
 7) SHEET S 1 - THERE IS NO INDICATION OF ANY RATING OF
 THE STAIRWELL EXIT ACCESS.
  
 30.3.6 CORRIDORS.
 30.3.6.1 WALLS. EXIT ACCESS CORRIDOR WALLS SHALL COMPLY
 WITH
 30.3.6.1.1 OR 30.3.6.1.2.
 30.3.6.1.1 IN BUILDINGS NOT COMPLYING WITH 30.3.6.1.2,
 EXIT ACCESS
 CORRIDOR WALLS SHALL CONSIST OF FIRE BARRIERS IN
 ACCORDANCE WITH
 SECTION 8.3 THAT HAVE NOT LESS THAN A 1-HOUR FIRE
 RESISTANCE RATING.
 30.3.6.1.2 IN BUILDINGS PROTECTED THROUGHOUT BY AN
 APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH
 30.3.5.2, CORRIDOR WALLS SHALL HAVE A MINIMUM ?-HOUR
 FIRE
 RESISTANCE RATING.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 8) SHEET S 1 - THERE ARE NO REFERNECES TO ANY RATING
 FOR THE CEILING/FLOOR ASSEMBLY.
  
 30.3.7 SUBDIVISIONS OF BUILDING SPACES. BUILDINGS SHALL
 BE
 SUBDIVIDED IN ACCORDANCE WITH 30.3.7.1 OR 30.3.7.2.
 30.3.7.1 IN BUILDINGS NOT MEETING THE REQUIREMENT OF
 30.3.7.2,
 DWELLING UNITS SHALL BE SEPARATED FROM EACH OTHER BY
 WALLS AND
 FLOORS CONSTRUCTED AS FIRE BARRIERS HAVING A MINIMUM
 1-HOUR FIRE
 RESISTANCE RATING.
  
 30.3.7.2 IN BUILDINGS PROTECTED THROUGHOUT BY AN
 APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM, DWELLING UNITS
 SHALL BE
 SEPARATED FROM EACH OTHER BY WALLS AND FLOORS
 CONSTRUCTED AS FIRE
 BARRIERS HAVING A MINIMUM ?-HOUR FIRE RESISTANCE
 RATING.
  
 PLEASE REVIEW AND CORRECT.
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL