2018-03-06 07:26:22 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| LOADS. ALL LOADS SUPPLIED ARE THE SAME FOR EACH PANEL |
| EVEN THOUGH THERE ARE DIFFERENCES IN EACH UNIT. ALSO, |
| THE PANEL SCHEDULE SHOWS 10 KW HEAT FOR THE AHU, BUT |
| YOU HAVE INCLUDED 3.25 KW IN LOAD CALCULATION. THERE |
| SHOULD BE ONE LOAD CALCULATION FOR ENTIRE SERVICE, AND |
| THEN A LOAD CALCULATION FOR EACH SUB-PANEL ALSO. NEC |
| 220 |
| 2. PROVIDE ACCURATE RISER DIAGRAM, SHOWING ALL DETAILS |
| OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY |
| SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| INTERSYSTEM BONDING TERMINATION POINT. PLAN CURRENTLY |
| SHOWS DISCONNECT A FEEDING NOTHING, DISCONNECT B |
| FEEDING PANEL A, AND DISCONNECT C FEEDING PANEL B. ALSO |
| NEED TO SHOW WIRE SIZE FOR SERVICE LATERAL. PROVIDE |
| CORRECTIONS. NEC 215.5, 230, 250.50, 250.94, 408.30 |
| 3. PANEL C IS SHOWN IN 2 LOCATIONS, PROVIDE CORRECTION. |
| FBC 107.2.1 |
| 4. PLAN SHOWS AFCI COVERAGE FOR SOME RECEPTACLE OUTLETS |
| BUT NOT LIGHTING. THIS COVERAGE IS NOT TO CODE AND NOT |
| COMPLETE. CODE REQUIRES: ?BRANCH CIRCUITS THAT SUPPLY |
| 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS |
| INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS, |
| LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, |
| SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS, |
| LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI |
| PROTECTED.? PROVIDE CORRECTION. NEC 210.12 |
| 5. BREAKER FOR WATER HEATER IS STATED AS 30 AMP, WHICH |
| IS TOO LARGE FOR THIS LOAD. BREAKER SHOULD BE SIZED AT |
| 125% OF THE LOAD, WHICH WOULD REQUIRE A 25 AMP BREAKER. |
| PROVIDE CORRECTION. NEC 422.13 |
| 6. PROVIDE ACCURATE PANEL SCHEDULES, THE WIRE AND |
| BREAKER SIZE FOR THESE CIRCUITS, AND AFCI OR GFCI |
| PROTECTION WHERE APPLICABLE TO COMPLY WITH CODE. ALL |
| PANEL SCHEDULES PROVIDED ARE IDENTICAL EVEN THOUGH THE |
| UNITS ARE DIFFERENT. CIRCUITS SHOULD HAVE UNIQUE |
| IDENTIFICATION. NEC 210.8, 210.12, 215.5, 408.4 |
| 7. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D) |
| 8. SMOKE ALARMS MUST BE INSTALLED AT LEAST 3 FEET FROM |
| BATHROOM DOOR, 3 FEET FROM CEILING FANS, AND 3 FEET |
| FROM ANY MECHANICAL DUCT. PROVIDE CORRECTIONS. FBC RE |
| R314.3(4), NFPA 72:29.8.3.4 |
| 9. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND |
| SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN |
| THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE |
| INDICATING THE REQUIRED SEPARATE PERMITS AND DATA |
| SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS |
| PRESENT. FBC 105.1, 107.2.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |