2018-02-27 10:52:49 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| |
| 1) SHEET 1 OF 4 - IS THIS AN OCCUPANCY CLASSIFICATION |
| CHANGE? |
| |
| PLEASE PROVIDE THE EXISTING OCCUPANCY CLASSIFICATION |
| AND PROPOSED ONE. |
| |
| |
| |
| |
| 2) SHEET 1 OF 4 - THERE IS NO INDICATION OF COMPLIANCE |
| OR REVIEW OF COMLAINCE WITH ANY FIRE PREVENTION CODE. |
| |
| THE PROPOSED PROJECT SHALL MEET THE REQUIREMNTS OF THE |
| FLORIDA FIRE PREVENTION CODE, 2015 EDITION. |
| |
| PLEASE PROVIDE AN APPLICABLE NOTE OF COMPLAINACE AND |
| REVIEW. |
| |
| |
| |
| |
| 3) SHEET 1 OF 4 - THERE APPEARS TO BE ADJACENT |
| OCCUPANCY WALL SEPARATION. |
| |
| PLEASE PROVIDE THE ADJACENT OCCUPANCIES AND THE |
| REQUIRED FIRE RATING SEPARATION PER THE FFPC. |
| |
| |
| |
| |
| 4) SHEET 1 OF 4 - THERE IS NO INDICATION OF A DOOR |
| SCHEDULE. |
| |
| PLEASE PROVIDE A DOOR SCHEDULE INCLUDING LOCKS AND |
| HARDWARE AND ENSURE IT MEETS THE REQUIREMENT OF THE |
| FFPC INCLUDING MEANS OF EGRESS. |
| |
| |
| |
| |
| |
| 5) THERE IS NO SHEET 2 OF 4. |
| |
| PLEASE REVIEW AND PROVIDE OR ACCOUNT FOR. |
| |
| |
| |
| |
| 5) SHEET 3 OF 4 - THERE IS NO INDICATION OF EXIT |
| SIGNAGE. |
| |
| NFPA 101 CHAPTER 36, NEW MERCANTILE OCCUPANCIES |
| 36.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS |
| SHALL |
| BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8. |
| |
| 36.2.10 MARKING OF MEANS OF EGRESS. WHERE AN EXIT IS |
| NOT |
| IMMEDIATELY APPARENT FROM ALL PORTIONS OF THE SALES |
| AREA, MEANS OF |
| EGRESS SHALL HAVE SIGNS IN ACCORDANCE WITH SECTION |
| 7.10. |
| |
| NFPA 101 CHAPTER 7, MEANS OF EGRESS |
| |
| 7.8 ILLUMINATION OF MEANS OF EGRESS. |
| 7.8.1 GENERAL. |
| 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| PROVIDED IN |
| ACCORDANCE WITH SECTION 7.8 FOR EVERY BUILDING AND |
| STRUCTURE WHERE |
| REQUIRED IN CHAPTERS 11 THROUGH 43. FOR THE PURPOSES OF |
| THIS |
| REQUIREMENT, EXIT ACCESS SHALL INCLUDE ONLY DESIGNATED |
| STAIRS, AISLES, |
| CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING |
| TO AN EXIT. FOR THE |
| PURPOSES OF THIS REQUIREMENT, EXIT DISCHARGE SHALL |
| INCLUDE ONLY |
| DESIGNATED STAIRS, AISLES, CORRIDORS, RAMPS, |
| ESCALATORS, WALKWAYS, AND EXIT |
| PASSAGEWAYS LEADING TO A PUBLIC WAY. |
| 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| CONTINUOUS DURING THE |
| TIME THAT THE CONDITIONS OF OCCUPANCY REQUIRE THAT THE |
| MEANS OF EGRESS |
| BE AVAILABLE FOR USE, UNLESS OTHERWISE PROVIDED IN |
| 7.8.1.2.2. |
| 7.10.1.2 EXITS. |
| 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS |
| THAT OBVIOUSLY |
| AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED |
| BY AN APPROVED |
| SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT |
| ACCESS. |
| 7.10.1.2.2* HORIZONTAL COMPONENTS OF THE EGRESS PATH |
| WITHIN AN EXIT |
| ENCLOSURE SHALL BE MARKED BY APPROVED EXIT OR |
| DIRECTIONAL EXIT SIGNS |
| WHERE THE CONTINUATION OF THE EGRESS PATH IS NOT |
| OBVIOUS. |
| 7.10.1.3 EXIT DOOR TACTILE SIGNAGE. TACTILE SIGNAGE |
| SHALL BE |
| PROVIDED TO MEET ALL OF THE FOLLOWING CRITERIA, UNLESS |
| OTHERWISE |
| PROVIDED IN 7.10.1.4: |
| (1) TACTILE SIGNAGE SHALL BE LOCATED AT EACH EXIT DOOR |
| REQUIRING AN |
| EXIT SIGN. |
| (2) TACTILE SIGNAGE SHALL READ AS FOLLOWS: EXIT. |
| (3) TACTILE SIGNAGE SHALL COMPLY WITH ICC/ANSI A117.1, |
| AMERICAN |
| NATIONAL STANDARD FOR ACCESSIBLE AND USABLE BUILDINGS |
| AND |
| FACILITIES. |
| |
| |
| PLEASE PROVIDE PER FFFC, NFPA 101, CHAPTER 36 & 7 MEANS |
| OF EGRESS. |
| |
| |
| |
| |
| 6) THERE ARE NO INCIATIONS OF ANY EXISTING OR PROPOSED |
| FIRE SPRINKLER OR FIRE ALARM SYSTEMS. |
| |
| PLEASE REVIEW AND PROVIDE AND APPLICABLE NOTE ON SHEET |
| 1 OF 4. |
| |
| |
| |
| |
| 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |