Plan Review Notes
Plan Review Notes For Permit 18020938
Permit Number 18020938
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-02-27 10:52:49THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET 1 OF 4 - IS THIS AN OCCUPANCY CLASSIFICATION
 CHANGE?
  
 PLEASE PROVIDE THE EXISTING OCCUPANCY CLASSIFICATION
 AND PROPOSED ONE.
  
  
  
  
 2) SHEET 1 OF 4 - THERE IS NO INDICATION OF COMPLIANCE
 OR REVIEW OF COMLAINCE WITH ANY FIRE PREVENTION CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMNTS OF THE
 FLORIDA FIRE PREVENTION CODE, 2015 EDITION.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF COMPLAINACE AND
 REVIEW.
  
  
  
  
 3) SHEET 1 OF 4 - THERE APPEARS TO BE ADJACENT
 OCCUPANCY WALL SEPARATION.
  
 PLEASE PROVIDE THE ADJACENT OCCUPANCIES AND THE
 REQUIRED FIRE RATING SEPARATION PER THE FFPC.
  
  
  
  
 4) SHEET 1 OF 4 - THERE IS NO INDICATION OF A DOOR
 SCHEDULE.
  
 PLEASE PROVIDE A DOOR SCHEDULE INCLUDING LOCKS AND
 HARDWARE AND ENSURE IT MEETS THE REQUIREMENT OF THE
 FFPC INCLUDING MEANS OF EGRESS.
  
  
  
  
  
 5) THERE IS NO SHEET 2 OF 4.
  
 PLEASE REVIEW AND PROVIDE OR ACCOUNT FOR.
  
  
  
  
 5) SHEET 3 OF 4 - THERE IS NO INDICATION OF EXIT
 SIGNAGE.
  
 NFPA 101 CHAPTER 36, NEW MERCANTILE OCCUPANCIES
 36.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL
 BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8.
  
 36.2.10 MARKING OF MEANS OF EGRESS. WHERE AN EXIT IS
 NOT
 IMMEDIATELY APPARENT FROM ALL PORTIONS OF THE SALES
 AREA, MEANS OF
 EGRESS SHALL HAVE SIGNS IN ACCORDANCE WITH SECTION
 7.10.
  
 NFPA 101 CHAPTER 7, MEANS OF EGRESS
  
 7.8 ILLUMINATION OF MEANS OF EGRESS.
 7.8.1 GENERAL.
 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN
 ACCORDANCE WITH SECTION 7.8 FOR EVERY BUILDING AND
 STRUCTURE WHERE
 REQUIRED IN CHAPTERS 11 THROUGH 43. FOR THE PURPOSES OF
 THIS
 REQUIREMENT, EXIT ACCESS SHALL INCLUDE ONLY DESIGNATED
 STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING
 TO AN EXIT. FOR THE
 PURPOSES OF THIS REQUIREMENT, EXIT DISCHARGE SHALL
 INCLUDE ONLY
 DESIGNATED STAIRS, AISLES, CORRIDORS, RAMPS,
 ESCALATORS, WALKWAYS, AND EXIT
 PASSAGEWAYS LEADING TO A PUBLIC WAY.
 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 CONTINUOUS DURING THE
 TIME THAT THE CONDITIONS OF OCCUPANCY REQUIRE THAT THE
 MEANS OF EGRESS
 BE AVAILABLE FOR USE, UNLESS OTHERWISE PROVIDED IN
 7.8.1.2.2.
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS.
 7.10.1.2.2* HORIZONTAL COMPONENTS OF THE EGRESS PATH
 WITHIN AN EXIT
 ENCLOSURE SHALL BE MARKED BY APPROVED EXIT OR
 DIRECTIONAL EXIT SIGNS
 WHERE THE CONTINUATION OF THE EGRESS PATH IS NOT
 OBVIOUS.
 7.10.1.3 EXIT DOOR TACTILE SIGNAGE. TACTILE SIGNAGE
 SHALL BE
 PROVIDED TO MEET ALL OF THE FOLLOWING CRITERIA, UNLESS
 OTHERWISE
 PROVIDED IN 7.10.1.4:
 (1) TACTILE SIGNAGE SHALL BE LOCATED AT EACH EXIT DOOR
 REQUIRING AN
 EXIT SIGN.
 (2) TACTILE SIGNAGE SHALL READ AS FOLLOWS: EXIT.
 (3) TACTILE SIGNAGE SHALL COMPLY WITH ICC/ANSI A117.1,
 AMERICAN
 NATIONAL STANDARD FOR ACCESSIBLE AND USABLE BUILDINGS
 AND
 FACILITIES.
  
  
 PLEASE PROVIDE PER FFFC, NFPA 101, CHAPTER 36 & 7 MEANS
 OF EGRESS.
  
  
  
  
 6) THERE ARE NO INCIATIONS OF ANY EXISTING OR PROPOSED
 FIRE SPRINKLER OR FIRE ALARM SYSTEMS.
  
 PLEASE REVIEW AND PROVIDE AND APPLICABLE NOTE ON SHEET
 1 OF 4.
  
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL