2018-03-01 06:56:11CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLANS ARE REQUIRED TO BE DESIGNED AND SIGNED AND
 SEALED BY A LICENSED ENGINEER OR ARCHITECT. PLANS
 FURNISHED BY AN INTERIOR DESIGNER ARE NOT ACCEPTABLE.
 PROVIDE CORRECTION. FS 471.003(2)(H); 471.025; FBC
 107.2.1, 107.3.5
 2. A FULL REVIEW IS NOT POSSIBLE AT THIS TIME DUE TO A
 SUBSTANTIAL LACK OF INFORMATION. FBC 107.2.1
 3. VALUE STATED ON PERMIT APPLICAITON APPEARS LOW.
 PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE OF
 WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  