Plan Review Notes
Plan Review Notes For Permit 18020938
Permit Number 18020938
Review Stop B
Sequence Number 1
Notes
Date Text
2018-02-28 10:55:512017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18020938
 ADD: 1401 CLARE AVENUE, SUITE :
 CONT: TIM GIVENS BUILDING & REMODELING
 TEL: 561-533-5828
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. FEB. 28/ 2018
 ACTION: DENIED
  
 1) THE SUBMITTED PLANS NOR THE PERMIT APPLICATION
 PROVIDE WHICH SUITE WORK IS TO BE COMPLETED UNDER THIS
 PERMIT.
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
  
 2017 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW AND
 EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS IDENTIFICATION.
  
 2) THE SUBMITTED PLANS STATE THERE ARE 4 SHEETS 1 OF 4
 FOR EXAMPLE, MISSING SHEET 2 OF 4 IN ALL THREE SETS.
 107.2.1.3 ADDITIONAL INFORMATION.
  
 3) PLEASE BE AWARE UNDER PERMIT 16090638/ REVISION
 17011285 (AS BUILT PLANS) THIS UNIT WAS CLASSIFIED AS A
 BUSINESS OCCUPANCY WITH AN EXISTING HANDICAPPED
 RESTROOM AND A COUNTER WITH BREAKROOM SINK. THE
 SUBMITTED PLANS DO NOT SHOW THIS ARRANGEMENT NOR DO
 THEY SHOW A DEMOLITION PLAN WITH THE REMOVAL OF THESE
 SYSTEMS NOR IS THERE A DEMOLITION PERMIT FOR THIS UNIT
 SHOWING THE REMOVAL OF THESE ELEMENTS.
 FURTHER MORE ADDITIONAL WORK HAS OCCURRED MAKING A TENT
 EFFECT(POLES, CANVAS AND ELECTRICAL FIXTURES AND HUNG
 LIGHTING), AT THE DOUBLE DOOR ENTRY AND CANVAS ON
 WALLS. 4 X THE FEE WILL BE CHARGED AGAINST THIS PERMIT
 FOR WORK COMPLETED WITHOUT THE BENEFIT OF A PERMIT.
  
 109.4 WORK COMMENCING BEFORE PERMIT ISSUANCE. ANY
 PERSON WHO COMMENCES ANY WORK ON A BUILDING, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL OR PLUMBING SYSTEM BEFORE
 OBTAINING THE BUILDING OFFICIAL?S APPROVAL OR THE
 NECESSARY PERMITS SHALL BE SUBJECT TO A PENALTY FEE IN
 ADDITION TO THE REQUIRED PERMIT FEES, AS SET IN
 APPROVED SCHEDULE OF FEES.
  
 4) SINCE UNDER THE AS BUILT REVISION 17101285 THE
 TENANT SPACE IN QUESTION WAS NO LONGER A VANILLA BOX AN
 OCCUPANCY WAS ASSIGNED (BUSINESS) AND UNISEX RESTROOM
 WAS SHOWN ON THE PLANS. THIS IS NOW CONSIDERED A CHANGE
 OF OCCUPANCY AND WILL NEED TO COMPLY WITH THE 2017
 EXISTING BUILDING CODE SECTION
 1001.2.2.1 PARTIAL CHANGE OF OCCUPANCY. WHERE THE
 OCCUPANCY CLASSIFICATION OR GROUP OF A PORTION OF AN
 EXISTING BUILDING IS CHANGED, SECTION 1012 SHALL APPLY.
  
 THE PLANS ARE NOT DISCLOSING THE MINIMUM INFORMATION
 FOR COMMERCIAL BUILDING PLAN REVIEW FOR BUILDINGS.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLES 504.3, TABLE 504.4 & TABLE 506.2).
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 FIRE SPRINKLERED OR NOT?
 IS FIRE SPRINKLERS REQUIRED?
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 VERTICAL ACCESSIBILITY
 TOILET AND BATHING FACILITIES
 DRINKING FOUNTAINS
 INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES/ WALLS AND CEILING (FLAME
 SPREAD/SMOKE DEVELOPMENT)
 LIGHT AND VENTILATION
 SANITATION MISSING RESTROOMS.
 SPECIAL SYSTEMS: (VERTICAL ACCESSIBILITY)
 ELEVATORS
 ESCALATORS
 LIFTS
  
 5) THE SUBMITTED PLAN WAS CREATED BY AN INTERIOR
 DECORATOR MARGARET B KAYWELL ID 0005475THE SCOPE OF THE
 PROJECT FAR EXCEEDS THE LIMITATIONS OF THIS LICENSE.
  
 5A) MISSING REQUIRED STATEMENT ON THE PLANS: 481.2131.
 A REGISTERED INTERIOR DESIGNER SHALL CONTAIN A
 STATEMENT THAT THE DOCUMENT IS NOT AN ARCHITECTURAL OR
 ENGINEERING STUDY, DRAWING, SPECIFICATION, OR DESIGN
 AND IS NOT TO BE USED FOR CONSTRUCTION OF ANY
 LOAD-BEARING COLUMNS, LOAD-BEARING FRAMING OR WALLS OF
 STRUCTURES, OR ISSUANCE OF ANY BUILDING PERMIT, EXCEPT
 AS OTHERWISE PROVIDED BY LAW.
  
 5B) FLORIDA STATUTE 481.2131(1). UNDER THE DEFINITIONS
 481.203 FOR INTERIOR DESIGN(8) ?INTERIOR DESIGN?
 SPECIFICALLY EXCLUDES THE DESIGN OF OR THE
 RESPONSIBILITY FOR ARCHITECTURAL AND ENGINEERING WORK,
 EXCEPT FOR SPECIFICATION OF FIXTURES AND THEIR LOCATION
 WITHIN INTERIOR SPACES. AS USED IN THIS SUBSECTION,
 ?ARCHITECTURAL AND ENGINEERING INTERIOR CONSTRUCTION
 RELATING TO THE BUILDING SYSTEMS? INCLUDES, BUT IS NOT
 LIMITED TO, CONSTRUCTION OF STRUCTURAL, MECHANICAL,
 PLUMBING, HEATING, AIR-CONDITIONING, VENTILATING,
 ELECTRICAL, OR VERTICAL TRANSPORTATION SYSTEMS, OR
 CONSTRUCTION WHICH MATERIALLY AFFECTS LIFESAFETY
 SYSTEMS PERTAINING TO FIRESAFETY PROTECTION SUCH AS
 FIRE-RATED SEPARATIONS BETWEEN INTERIOR SPACES,
 FIRE-RATED VERTICAL SHAFTS IN MULTISTORY STRUCTURES,
 FIRE-RATED PROTECTION OF STRUCTURAL ELEMENTS, SMOKE
 EVACUATION AND COMPARTMENTALIZATION, EMERGENCY INGRESS
 OR EGRESS SYSTEMS, AND EMERGENCY ALARM SYSTEMS.
 UNDER COMMENT # 4 THESE ARE THE AREAS NOT SHOWN ON THE
 PLAN, AND UNDER THE INTERIOR DESIGN LICENSE NOT IN THE
 SCOPE OF THEIR LICENSURE.
  
 6) PLEASE PROVIDE A LIFE SAFETY PLAN FOR THIS TENANT
 SPACE SHOWING BOTH A MEANS OF EGRESS AS WELL AS THE
 ACCESSIBLE MEANS OF EGRESS TO THE PUBLIC WAY. PLEASE
 INCLUDE THE ADJACENT TENANT SPACE WHERE YOU HAVE TO GO
 THROUGH THE ADJACENT TENANT SPACE TO AN EXIT. PROVIDE
 THE TYPE OF OCCUPANCIES ADJACENT TO THE MERCANTILE
 OCCUPANCY. PLEASE ALSO INCLUDE COMMON PATH OF TRAVEL
 AND EXIT ACCESS TRAVEL TO THE EXIT DISCHARGE.
 2017 FBC-B TABLE 1006.2.1. PLEASE BE AWARE THAT FOR AN
 ACCESSIBLE MEANS OF EGRESS YOU ARE AT 79 FEET FROM THE
 FURTHEST POINT IN THE TENANT SPACE TO THE DOUBLE ENTRY
 DOORS. YOU STILL HAVE TO GO THROUGH A SECOND TENANT
 SPACE BEFORE YOU GET TO AN EXIT DISCHARGE.
 TABLE 1017.2 EXIT ACCESS TRAVEL DISTANCE.
  
 7)2017 FBC-B 1016.2 EGRESS THROUGH INTERVENING SPACES.
 EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH
 THIS SECTION.
 (2).EGRESS FROM A ROOM OR SPACE SHALL NOT PASS THROUGH
 ADJOINING OR INTERVENING ROOMS OR AREAS, EXCEPT WHERE
 SUCH ADJOINING ROOMS OR AREAS AND THE AREA SERVED ARE
 ACCESSORY TO ONE OR THE OTHER, ARE NOT A GROUP H
 OCCUPANCY AND PROVIDE A DISCERNIBLE PATH OF EGRESS
 TRAVEL TO AN EXIT.
  
 8) PLEASE NOTE WITH THE CITY BUILDING INSPECTORS BEING
 AT THE SITE AT PICTURES WERE TAKEN OF A CANVAS TENT
 LIKE CEILING ASSEMBLY AND CANVAS ON THE TENANT WALLS
 PLEASE PROVIDE COMPLIANCE WITH TEXTILE WALL AND CEILING
 COVERINGS.
  
 8A) 2017 FBC-B 803.5 TEXTILE WALL COVERINGS. WHERE USED
 AS INTERIOR WALL FINISH MATERIALS, TEXTILE WALL
 COVERINGS, INCLUDING MATERIALS HAVING WOVEN OR
 NONWOVEN, NAPPED, TUFTED, LOOPED OR SIMILAR SURFACE AND
 CARPET AND SIMILAR TEXTILE MATERIALS, SHALL BE TESTED
 IN THE MANNER INTENDED FOR USE, USING THE PRODUCT
 MOUNTING SYSTEM, INCLUDING ADHESIVE, AND SHALL COMPLY
 WITH THE REQUIREMENTS OF SECTION 803.1.2, 803.1.3 OR
 803.1.4.
  
 8B) 2017 FBC-B 803.6 TEXTILE CEILING COVERINGS. WHERE
 USED AS INTERIOR CEILING FINISH MATERIALS, TEXTILE
 CEILING COVERINGS, INCLUDING MATERIALS HAVING WOVEN OR
 NONWOVEN, NAPPED, TUFTED, LOOPED OR SIMILAR SURFACE AND
 CARPET AND SIMILAR TEXTILE MATERIALS, SHALL BE TESTED
 IN THE MANNER INTENDED FOR USE, USING THE PRODUCT
 MOUNTING SYSTEM, INCLUDING ADHESIVE, AND SHALL COMPLY
 WITH THE REQUIREMENTS OF SECTION 803.1.2 OR 803.1.4.
  
 8C) SHOW COMPLIANCE WITH FBC-B 803.11 INTERIOR FINISH
 REQUIREMENTS BASED ON GROUP.
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 10) A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN
 SINCE THERE WAS A GREAT DEFICIENCY IN PLANS AND
 REQUIRED DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE
 THERE MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW
 PLANS AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  