2018-02-28 08:27:13 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 18020933 |
| ADD: 1009 BANYAN BLVD. |
| CONT: THE CARPENTER?S SON |
| TEL: 561-452-2191 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. FEB. 28/ 2018 |
| ACTION: DENIED |
| |
| 1) THE PLANS DO NOT STATE TO WHICH CODE THEY WERE |
| CREATED. PLEASE NOTE ON DEC. 31/ 2017 THE 2017 FLORIDA |
| BUILDING CODE THE 6TH EDITION WAS ADOPTED STATEWIDE. |
| PLEASE LIST ON THE LIFE SAFETY SHEET. |
| |
| 2) UNDER THE 2017 FBC-EXISTING BUILDING CODE, THE |
| DESIGNER OF RECORD HAS NOT LISTED WHICH METHOD THE |
| PLANS WERE CREATED. 2017 FBC-EXISTING BUILDING CODE |
| SECTION 301.1. THE ALTERATION, CHANGE OF OCCUPANCY, |
| ADDITION OR RELOCATION OF ALL EXISTING BUILDINGS SHALL |
| COMPLY WITH ONE OF THE METHODS LISTED IN SECTIONS |
| 301.1.1 THROUGH 301.1.3 AS SELECTED BY THE APPLICANT. |
| SECTIONS 301.1.1 THROUGH 301.1.3 SHALL NOT BE APPLIED |
| IN COMBINATION WITH EACH OTHER. PLEASE NOTE FOR THIS |
| ROOM IT IS CONSIDERED A CHANGE OF OCCUPANCY. |
| |
| 3) FOR THIS PLAN REVIEW TO OCCUR A CHOICE OF COMPLIANCE |
| METHOD WAS USED, THE WORK AREA METHOD. 2017 EXIST. |
| BLDG. CODE 301.1.2 WORK AREA COMPLIANCE METHOD. |
| REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY |
| AND RELOCATED BUILDINGS COMPLYING WITH THE APPLICABLE |
| REQUIREMENTS OF CHAPTERS 5 THROUGH 13 OF THIS CODE |
| SHALL BE CONSIDERED IN COMPLIANCE WITH THE PROVISIONS |
| OF THIS CODE. |
| |
| 3A) EXIST. BLDG. CODE 1001.2.2.1 PARTIAL CHANGE OF |
| OCCUPANCY. WHERE THE OCCUPANCY CLASSIFICATION OR GROUP |
| OF A PORTION OF AN EXISTING BUILDING IS CHANGED, |
| SECTION 1012 SHALL APPLY. |
| |
| 3B) SHEET 6 OF 6 THE LIFE SAFETY PLAN INDICATES THIS |
| CHANGE OF OCCUPANCY IS FROM STORAGE TO BUSINESS |
| OCCUPANCY. PLEASE NOTE THE PLANS INDICATE THE USE FOR |
| THIS ROOM IS A CONFERENCE ROOM. THE FLOOR PLAN SHEET 2 |
| OF 6 IS DIMENSIONED AND 836 SQ. FT. AND THE 1ST FLOOR |
| IS 5,495 SQ. FT. THE CONFERENCE ROOM IS OVER 10% OF THE |
| FLOOR AREA AND OVER 750 SQ. FT. CREATING A MIXED USE |
| BUILDING AND THE OCCUPANCY FOR THE CONFERENCE ROOM |
| BEING A3 NOT A BUSINESS USE. PLEASE CORRECT. |
| |
| SEE 2017 FBC-B 508.1. EACH PORTION OF A BUILDING SHALL |
| BE INDIVIDUALLY CLASSIFIED IN ACCORDANCE WITH SECTION |
| 302.1. WHERE A BUILDING CONTAINS MORE THAN ONE |
| OCCUPANCY GROUP, THE BUILDING OR PORTION THEREOF SHALL |
| COMPLY WITH THE APPLICABLE PROVISIONS OF SECTION 508.2, |
| 508.3 OR 508.4, OR A COMBINATION OF THESE SECTIONS. |
| |
| 3C) THE DESIGNER OF RECORD WILL ALSO NEED TO INDICATE |
| IF THE NEW CONFERENCE ROOM WILL MEET WHICH SECTION OF |
| THE 2017 FBC-B CODE: |
| 2017 FBC-EXIT. BLDG. CODE 1012.1.1.1 CHANGE OF |
| OCCUPANCY CLASSIFICATION WITHOUT SEPARATION |
| 2017 FBC-EXIT. BLDG. CODE 1012.1.1.2 CHANGE OF |
| OCCUPANCY CLASSIFICATION WITH SEPARATION. |
| |
| 4) BOTH SHEETS 5 OF 6 AND 6 OF 6 BOTH SHOW A SINGLE |
| INSWING DOOR INTO THE CONFERENCE ROOM FROM THE INTERIOR |
| EXIT ACCESS CORRIDOR. PLEASE SHOW COMPLIANCE WITH: |
| 2017 FBC-B SECTION 1010.1.2.1 DIRECTION OF SWING. PIVOT |
| OR SIDE-HINGED SWINGING DOORS SHALL SWING IN THE |
| DIRECTION OF EGRESS TRAVEL WHERE SERVING A ROOM OR AREA |
| CONTAINING AN OCCUPANT LOAD OF 50 OR MORE PERSONS. |
| |
| 5) 2017 FBC-EXIT. BLDG. CODE 1012.1.4 ACCESSIBILITY. |
| ALL BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY |
| CLASSIFICATION SHALL COMPLY WITH SECTION 1012.8. |
| EXIST. BLDG. CODE. 1012.8 ACCESSIBILITY EXISTING |
| BUILDINGS THAT UNDERGO A CHANGE OF GROUP OR OCCUPANCY |
| CLASSIFICATION SHALL COMPLY WITH THE PROVISIONS OF THE |
| FLORIDA BUILDING CODE, ACCESSIBILITY. |
| |
| 5A) PLEASE SHOW HOW COMPLIANCE WITH THE REQUIRED |
| ACCESSIBLE MEANS OF EGRESS WILL BE OBTAINED. |
| 2014 FBC-ACCESSIBILITY CODE. 206.4.1 PUBLIC ENTRANCES. |
| (DOORWAYS). IN ADDITION TO ENTRANCES REQUIRED BY |
| 206.4.2 THROUGH 206.4.9, AT LEAST 60 PERCENT OF ALL |
| PUBLIC ENTRANCES SHALL COMPLY WITH 404. BARRIERS AT |
| COMMON OR EMERGENCY ENTRANCES AND EXITS OF BUSINESS |
| ESTABLISHMENTS CONDUCTING BUSINESS WITH THE GENERAL |
| PUBLIC THAT ARE EXISTING, UNDER CONSTRUCTION, OR UNDER |
| CONTRACT FOR CONSTRUCTION WHICH WOULD PREVENT A PERSON |
| FROM USING SUCH ENTRANCES OR EXITS SHALL BE REMOVED. |
| 2 REQUIRED MEANS OF EGRESS REQUIRED X 0.60% = 1.2 OR 2 |
| ACCESSIBLE MEANS OF EGRESS. THE FLOOR PLAN 5 OF 6 SHOWS |
| 2 EXIT DOORS BUT NOT THE ACCESSIBLE EXIT DISCHARGE FROM |
| THE BUILDING ACCESSIBLE FOR A WHEELCHAIR. |
| |
| 5B) SHEET 2 OF 6 & 6 OF 6 SHOWS WHAT APPEARS TO BE A |
| SINK AND CABINETRY MAYBE A BREAK AREA. THE PLANS DO NOT |
| SHOW COMPLIANCE WITH THE 2017 FBC-ACCESS. CODE SECTION |
| 606 SINKS. |
| 606.2 CLEAR FLOOR SPACE. |
| 606.3HEIGHT. |
| 606.4 FAUCETS. |
| 606.5 EXPOSED PIPES AND SURFACES. |
| |
| 5C) THE PLANS ARE ALSO MISSING SIGNAGE FOR EXIT |
| DOORWAYS. SIGNAGE 703. 703.1 SIGNS SHALL COMPLY WITH |
| 703. WHERE BOTH VISUAL AND TACTILE CHARACTERS ARE |
| REQUIRED, EITHER ONE SIGN WITH BOTH VISUAL AND TACTILE |
| CHARACTERS, OR TWO SEPARATE SIGNS, ONE WITH VISUAL, AND |
| ONE WITH TACTILE CHARACTERS, SHALL BE PROVIDED. |
| |
| SIGNAGE TACTILE CHARACTERS ABOVE FINISH FLOOR OR GROUND |
| 2014 ACCESSIBILITY CODE. 703.4.1 HEIGHT ABOVE FINISH |
| FLOOR OR GROUND. TACTILE CHARACTERS ON SIGNS SHALL BE |
| LOCATED 48 INCHES MINIMUM ABOVE THE FINISH FLOOR OR |
| GROUND SURFACE, MEASURED FROM THE BASELINE OF THE |
| LOWEST TACTILE CHARACTER AND 60 INCHES MAXIMUM ABOVE |
| THE FINISH FLOOR OR GROUND SURFACE, MEASURED FROM THE |
| BASELINE OF THE HIGHEST TACTILE CHARACTER. |
| |
| SIGNAGE. 703.4.1 HEIGHT ABOVE FINISH FLOOR OR GROUND. |
| TACTILE CHARACTERS ON SIGNS SHALL BE LOCATED 48 INCHES |
| MINIMUM ABOVE THE FINISH FLOOR OR GROUND SURFACE, |
| MEASURED FROM THE BASELINE OF THE LOWEST TACTILE |
| CHARACTER AND 60 INCHES MAXIMUM ABOVE THE FINISH FLOOR |
| OR GROUND SURFACE, MEASURED FROM THE BASELINE OF THE |
| HIGHEST TACTILE CHARACTER. |
| |
| 6) THE PLAN SHEET 3 OF 6 INDICATE AN EXTERIOR WALL THAT |
| HAS NEW DRYWALL BUT NO INSULATION. THE PLANS DO NOT |
| INDICATE WHEN THIS SPACE WAS USED FOR STORAGE IF THERE |
| WAS A/C IN THIS ROOM, NOT SHOWN ON THE PLANS. SHEET 3 |
| OF 6 SHOWS NEW FURRING STRIPS ATTACHED TO CONCRETE |
| BLOCK WORK AND DRYWALL. THE PLANS DO NOT INDICATE THE |
| USE OF INSULATION IN THIS WALL. |
| 2017 EXIST. BLDG. CODE SECTION1013 ENERGY CONSERVATION. |
| SEE THE FLORIDA BUILDING CODE, ENERGY CONSERVATION. |
| C401.2 APPLICATION. |
| COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE |
| FOLLOWING: |
| 1.THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1, EXCLUDING |
| SECTION 9.4.1.1(G) OF THE STANDARD. |
| 2.THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN |
| ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH |
| SECTION C406 AND TENANT SPACES SHALL COMPLY WITH |
| SECTION C406.1.1. |
| 3.THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404, |
| C405.2, C405.3, C405.5, C405.6 AND C407. THE BUILDING |
| ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 PERCENT |
| OF THE STANDARD REFERENCE DESIGN BUILDING. |
| C402.1.3 INSULATION COMPONENT R-VALUE-BASED METHOD. |
| BUILDING THERMAL ENVELOPE OPAQUE ASSEMBLIES SHALL MEET |
| THE REQUIREMENTS OF SECTIONS C402.2 AND C402.4 BASED ON |
| THE CLIMATE ZONE SPECIFIED IN CHAPTER 3. |
| |
| 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |