Plan Review Notes
Plan Review Notes For Permit 18020933
Permit Number 18020933
Review Stop B
Sequence Number 1
Notes
Date Text
2018-02-28 08:27:132017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18020933
 ADD: 1009 BANYAN BLVD.
 CONT: THE CARPENTER?S SON
 TEL: 561-452-2191
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. FEB. 28/ 2018
 ACTION: DENIED
  
 1) THE PLANS DO NOT STATE TO WHICH CODE THEY WERE
 CREATED. PLEASE NOTE ON DEC. 31/ 2017 THE 2017 FLORIDA
 BUILDING CODE THE 6TH EDITION WAS ADOPTED STATEWIDE.
 PLEASE LIST ON THE LIFE SAFETY SHEET.
  
 2) UNDER THE 2017 FBC-EXISTING BUILDING CODE, THE
 DESIGNER OF RECORD HAS NOT LISTED WHICH METHOD THE
 PLANS WERE CREATED. 2017 FBC-EXISTING BUILDING CODE
 SECTION 301.1. THE ALTERATION, CHANGE OF OCCUPANCY,
 ADDITION OR RELOCATION OF ALL EXISTING BUILDINGS SHALL
 COMPLY WITH ONE OF THE METHODS LISTED IN SECTIONS
 301.1.1 THROUGH 301.1.3 AS SELECTED BY THE APPLICANT.
 SECTIONS 301.1.1 THROUGH 301.1.3 SHALL NOT BE APPLIED
 IN COMBINATION WITH EACH OTHER. PLEASE NOTE FOR THIS
 ROOM IT IS CONSIDERED A CHANGE OF OCCUPANCY.
  
 3) FOR THIS PLAN REVIEW TO OCCUR A CHOICE OF COMPLIANCE
 METHOD WAS USED, THE WORK AREA METHOD. 2017 EXIST.
 BLDG. CODE 301.1.2 WORK AREA COMPLIANCE METHOD.
 REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY
 AND RELOCATED BUILDINGS COMPLYING WITH THE APPLICABLE
 REQUIREMENTS OF CHAPTERS 5 THROUGH 13 OF THIS CODE
 SHALL BE CONSIDERED IN COMPLIANCE WITH THE PROVISIONS
 OF THIS CODE.
  
 3A) EXIST. BLDG. CODE 1001.2.2.1 PARTIAL CHANGE OF
 OCCUPANCY. WHERE THE OCCUPANCY CLASSIFICATION OR GROUP
 OF A PORTION OF AN EXISTING BUILDING IS CHANGED,
 SECTION 1012 SHALL APPLY.
  
 3B) SHEET 6 OF 6 THE LIFE SAFETY PLAN INDICATES THIS
 CHANGE OF OCCUPANCY IS FROM STORAGE TO BUSINESS
 OCCUPANCY. PLEASE NOTE THE PLANS INDICATE THE USE FOR
 THIS ROOM IS A CONFERENCE ROOM. THE FLOOR PLAN SHEET 2
 OF 6 IS DIMENSIONED AND 836 SQ. FT. AND THE 1ST FLOOR
 IS 5,495 SQ. FT. THE CONFERENCE ROOM IS OVER 10% OF THE
 FLOOR AREA AND OVER 750 SQ. FT. CREATING A MIXED USE
 BUILDING AND THE OCCUPANCY FOR THE CONFERENCE ROOM
 BEING A3 NOT A BUSINESS USE. PLEASE CORRECT.
  
 SEE 2017 FBC-B 508.1. EACH PORTION OF A BUILDING SHALL
 BE INDIVIDUALLY CLASSIFIED IN ACCORDANCE WITH SECTION
 302.1. WHERE A BUILDING CONTAINS MORE THAN ONE
 OCCUPANCY GROUP, THE BUILDING OR PORTION THEREOF SHALL
 COMPLY WITH THE APPLICABLE PROVISIONS OF SECTION 508.2,
 508.3 OR 508.4, OR A COMBINATION OF THESE SECTIONS.
  
 3C) THE DESIGNER OF RECORD WILL ALSO NEED TO INDICATE
 IF THE NEW CONFERENCE ROOM WILL MEET WHICH SECTION OF
 THE 2017 FBC-B CODE:
 2017 FBC-EXIT. BLDG. CODE 1012.1.1.1 CHANGE OF
 OCCUPANCY CLASSIFICATION WITHOUT SEPARATION
 2017 FBC-EXIT. BLDG. CODE 1012.1.1.2 CHANGE OF
 OCCUPANCY CLASSIFICATION WITH SEPARATION.
  
 4) BOTH SHEETS 5 OF 6 AND 6 OF 6 BOTH SHOW A SINGLE
 INSWING DOOR INTO THE CONFERENCE ROOM FROM THE INTERIOR
 EXIT ACCESS CORRIDOR. PLEASE SHOW COMPLIANCE WITH:
 2017 FBC-B SECTION 1010.1.2.1 DIRECTION OF SWING. PIVOT
 OR SIDE-HINGED SWINGING DOORS SHALL SWING IN THE
 DIRECTION OF EGRESS TRAVEL WHERE SERVING A ROOM OR AREA
 CONTAINING AN OCCUPANT LOAD OF 50 OR MORE PERSONS.
  
 5) 2017 FBC-EXIT. BLDG. CODE 1012.1.4 ACCESSIBILITY.
 ALL BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH SECTION 1012.8.
 EXIST. BLDG. CODE. 1012.8 ACCESSIBILITY EXISTING
 BUILDINGS THAT UNDERGO A CHANGE OF GROUP OR OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH THE PROVISIONS OF THE
 FLORIDA BUILDING CODE, ACCESSIBILITY.
  
 5A) PLEASE SHOW HOW COMPLIANCE WITH THE REQUIRED
 ACCESSIBLE MEANS OF EGRESS WILL BE OBTAINED.
 2014 FBC-ACCESSIBILITY CODE. 206.4.1 PUBLIC ENTRANCES.
 (DOORWAYS). IN ADDITION TO ENTRANCES REQUIRED BY
 206.4.2 THROUGH 206.4.9, AT LEAST 60 PERCENT OF ALL
 PUBLIC ENTRANCES SHALL COMPLY WITH 404. BARRIERS AT
 COMMON OR EMERGENCY ENTRANCES AND EXITS OF BUSINESS
 ESTABLISHMENTS CONDUCTING BUSINESS WITH THE GENERAL
 PUBLIC THAT ARE EXISTING, UNDER CONSTRUCTION, OR UNDER
 CONTRACT FOR CONSTRUCTION WHICH WOULD PREVENT A PERSON
 FROM USING SUCH ENTRANCES OR EXITS SHALL BE REMOVED.
 2 REQUIRED MEANS OF EGRESS REQUIRED X 0.60% = 1.2 OR 2
 ACCESSIBLE MEANS OF EGRESS. THE FLOOR PLAN 5 OF 6 SHOWS
 2 EXIT DOORS BUT NOT THE ACCESSIBLE EXIT DISCHARGE FROM
 THE BUILDING ACCESSIBLE FOR A WHEELCHAIR.
  
 5B) SHEET 2 OF 6 & 6 OF 6 SHOWS WHAT APPEARS TO BE A
 SINK AND CABINETRY MAYBE A BREAK AREA. THE PLANS DO NOT
 SHOW COMPLIANCE WITH THE 2017 FBC-ACCESS. CODE SECTION
 606 SINKS.
 606.2 CLEAR FLOOR SPACE.
 606.3HEIGHT.
 606.4 FAUCETS.
 606.5 EXPOSED PIPES AND SURFACES.
  
 5C) THE PLANS ARE ALSO MISSING SIGNAGE FOR EXIT
 DOORWAYS. SIGNAGE 703. 703.1 SIGNS SHALL COMPLY WITH
 703. WHERE BOTH VISUAL AND TACTILE CHARACTERS ARE
 REQUIRED, EITHER ONE SIGN WITH BOTH VISUAL AND TACTILE
 CHARACTERS, OR TWO SEPARATE SIGNS, ONE WITH VISUAL, AND
 ONE WITH TACTILE CHARACTERS, SHALL BE PROVIDED.
  
 SIGNAGE TACTILE CHARACTERS ABOVE FINISH FLOOR OR GROUND
 2014 ACCESSIBILITY CODE. 703.4.1 HEIGHT ABOVE FINISH
 FLOOR OR GROUND. TACTILE CHARACTERS ON SIGNS SHALL BE
 LOCATED 48 INCHES MINIMUM ABOVE THE FINISH FLOOR OR
 GROUND SURFACE, MEASURED FROM THE BASELINE OF THE
 LOWEST TACTILE CHARACTER AND 60 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND SURFACE, MEASURED FROM THE
 BASELINE OF THE HIGHEST TACTILE CHARACTER.
  
 SIGNAGE. 703.4.1 HEIGHT ABOVE FINISH FLOOR OR GROUND.
 TACTILE CHARACTERS ON SIGNS SHALL BE LOCATED 48 INCHES
 MINIMUM ABOVE THE FINISH FLOOR OR GROUND SURFACE,
 MEASURED FROM THE BASELINE OF THE LOWEST TACTILE
 CHARACTER AND 60 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 OR GROUND SURFACE, MEASURED FROM THE BASELINE OF THE
 HIGHEST TACTILE CHARACTER.
  
 6) THE PLAN SHEET 3 OF 6 INDICATE AN EXTERIOR WALL THAT
 HAS NEW DRYWALL BUT NO INSULATION. THE PLANS DO NOT
 INDICATE WHEN THIS SPACE WAS USED FOR STORAGE IF THERE
 WAS A/C IN THIS ROOM, NOT SHOWN ON THE PLANS. SHEET 3
 OF 6 SHOWS NEW FURRING STRIPS ATTACHED TO CONCRETE
 BLOCK WORK AND DRYWALL. THE PLANS DO NOT INDICATE THE
 USE OF INSULATION IN THIS WALL.
 2017 EXIST. BLDG. CODE SECTION1013 ENERGY CONSERVATION.
 SEE THE FLORIDA BUILDING CODE, ENERGY CONSERVATION.
 C401.2 APPLICATION.
 COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE
 FOLLOWING:
 1.THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1, EXCLUDING
 SECTION 9.4.1.1(G) OF THE STANDARD.
 2.THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN
 ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH
 SECTION C406 AND TENANT SPACES SHALL COMPLY WITH
 SECTION C406.1.1.
 3.THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404,
 C405.2, C405.3, C405.5, C405.6 AND C407. THE BUILDING
 ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 PERCENT
 OF THE STANDARD REFERENCE DESIGN BUILDING.
 C402.1.3 INSULATION COMPONENT R-VALUE-BASED METHOD.
 BUILDING THERMAL ENVELOPE OPAQUE ASSEMBLIES SHALL MEET
 THE REQUIREMENTS OF SECTIONS C402.2 AND C402.4 BASED ON
 THE CLIMATE ZONE SPECIFIED IN CHAPTER 3.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  