2018-03-13 10:32:15 | 1ST REVIEW: FBC 2017 5TH EDITION |
| 1ST REVIEW FBC 2017 EXISTING BUILDING |
| |
| FAILED. |
| |
| 1) PLEASE PROVIDE CLEAR PLANS REGARDING THE ALTERATION |
| TO ELECTRICAL AND BATHROOM KITCHEN REMODELING. IS THERE |
| TO BE A SHOWER PAN REPLACEMENT? CONTRACT INDICATES SO. |
| IF SO PROVIDE DETAIL. WIL THE KITCHEN CABINETS BE |
| ALTERED OR IS THE ARRANGEMENT TO BE THE SAME? DRAWINGS |
| ARE TO BE SIGNED BY THE PERSON RESPONSIBLE. THE |
| ELECTRICIAN, PLUMBER, AND OR BUILDING CONTRACTOR MY |
| DEVELOP DESIGN DOCUMENTS, BUT SUCH PERSON MUST INDICATE |
| LICENSE NUMBER IF APPLICABLE, PRINT NAME, AND SIGN THE |
| DESIGN. |
| |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE |
| OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 2) THE PLUMBING PLAN REVIEW REQUESTS DEMONSTRATION OF |
| COMPLIANCE WITH FAIR HOUSING. PLEASE BE ADVISED OF THE |
| APPLICABILITY WHICH YOU MAY DETERMINE AT THE WEB |
| ADDRESS BELOW. |
| |
| HTTPS://CODES.ICCSAFE.ORG/PUBLIC/DOCUMENT/FAC2017/FAIR- |
| HOUSING-ACCESSIBILITY-GUIDELINES-DESIGN-GUIDELINES-FOR- |
| ACCESSIBLE-ADAPTABLE-DWELLINGS |
| |
| 3) FLOORING - THE SOUND INSULATION PRODUCT DATA SHEET |
| PROVIDED IS INSUFFICIENT AS A SUBMITTAL TO DEMONSTRATE |
| COMPLIANCE WITH: |
| FBC 603.1 FLAME SPREAD; INSULATION BETWEEN A FINISHED |
| FLOOR AND SOLID DECKING W/O AN INTERVENING SPACE |
| W/FLAME SPREAD INDEX OF 200 OR LESS. |
| FBC 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| THIS PRODUCT IS FOR USE WITH WOOD FLOORS, NOT TILE. |
| PROVIDE TEST REPORTS FROM A THIRD PARTY TESTING AGENCY |
| FOR A SOUND INSULATION PRODUCT TO DEMONSTRATE |
| COMPLIANCE WITH THE ABOVE CRITERIA. IT MUST BE |
| CONSISTENT WITH THE PROPOSED INSTALLATION AND THE |
| ASSEMBLY OF THE FLOOR CEILING ASSEMBLY IN PLACE AT THE |
| BUILDING. THIS IS A 6" OR 8" FLOOR CEILING SLAB WITH NO |
| SUSPENDED CEILING BELOW. YOU MAY VERIFY VIA PUBLIC |
| RECORDS REQUEST OR PERHAPS THE BUILDING MANAGEMENT CAN |
| PROVIDE THE DATA TO YOU. |
| |
| |
| STEVEN KENNEDY, CBO |
| ASSISTANT BUILDING OFFICIAL |
| (561) 805-6710 |
| [email protected] |
| |