2018-03-12 15:15:413/12/2018 **1ST REVIEW DENIED **
  
 1. SIGNATURE OF AN ARCHITECT-ENGINEER IS REQUIRED, NOT
 IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE
 61G15-23.001, FLORIDA STATUTE 471.
 2. WHAT IS THE TURNOVER TIME OF THE POOL VOLUME PER DAY
 FBC B 454.1.6.2
 3. PLEASE PROVIDE THE MANUFACTURES SPECIFICATION FOR
 THE MAIN DRAIN GRATE AND SPA DRAIN GATE TO VERIFY
 COMPLIANCE WITH ASME/ANSI A112.19.8 COMPLIANT
 COVER/GRATE
 4. THE MINIMUM GPM OF 73 GPM SHOWN ON SHEET 1 FOR THE
 POOL IS VALID FOR A BATHING LOAD OF 15 PERSONS. YOU
 LIST THE BATHING LOAD AS 20 PERSONS WHICH REQUIRES A
 MINIMUM FLOW OF 1000 GPM PER FBC B SEC. 454.1.1.1
 SIZING, PLEASE CLARIFY THIS.
 5. PLEASE PROVIDE MANUFACTURES SPECIFICATION ON PUMP
 AND HEATER FBC B SEC. 454.1.6.5.14 HEATERS.
 6. PLEASE PROVIDE A COMPLETE PIPING DIAGRAM WPB
 AMENDMENTS TO THE FBC SEC. 107.5.1.3 (13) COMMERCIAL
 PLUMBING.
 7. IF THE PUMP IS LOCATED ABOVE THE WATER LEVEL OF THE
 POOL, THE PUMP SHALL BE SELF-PRIMING FBC 454.1.6.5.4.
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 A SEPARATE PERMIT AND REVIEW SHALL BE REQUIRED FOR GAS.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  