Plan Review Notes
Plan Review Notes For Permit 18020842
Permit Number 18020842
Review Stop B
Sequence Number 1
Notes
Date Text
2018-02-23 11:07:35PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THIS STRUCTURE IS LOCATED IN EXPOSURE CATEGORY B
 WITH A VULT WIND SPEED OF 170 MPH. THE ROOFING SYSTEM
 THAT WAS INDICATED DOES NOT MEET THE REQUIRED DESIGN
 PRESSURES FOR THE PERIMETER AND CORNER ROOF AREAS. THE
 TPO SYSTEM SPECIFIED ON PAGES 7 AND 8 OF NOA NO.
 14-0326.08 HAS A MAXIMUM DESIGN PRESSURE OF -45 PSF AND
 CAN NOT BE INCREASED BY ENHANCED FASTENING PER
 LIMITATION NUMBER 9 ON PAGE 22.
  