Plan Review Notes
Plan Review Notes For Permit 18020832
Permit Number 18020832
Review Stop M
Sequence Number 2
Notes
Date Text
2018-04-17 12:25:422ND REVIEW FBC-2017 MECHANICAL, EXISTING BUILDING CODE
 PERMIT #18020832
 4/17/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1 & S-1: THE RTU-1 LOCATION AND IT'S
 POSITION ON THE ROOF AS SHOWN ON THE PLANS DO NOT
 MATCH. PLEASE NOTE THAT THAT IF THE UNIT IS LOCATED
 LESS THAN 10' FROM THE ROOF EDGE (AS SHOWN ON S-1), A
 42" HIGH PARAPET OR GUARD IS REQUIRED IN ACCRODANCE
 WITH SECTION 301.11.
  
 2) M-2 & S-1: THE CURB AND RTU INSTALLATION DETAILS-
 TYPES, SIZES, AND SPACINGS OF ANCHORS, STRAPS, AND
 FASTENERS AS SHOWN IN THE PLANS ARE IN CONFLICT. PLEASE
 CORRECT.
  
 3) REFER TO BUILDING REVIEW COMMENTS AND RESOLVE THE
 CONFLICT WITH THE WALL AND ROOF INSULATIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  