Plan Review Notes
Plan Review Notes For Permit 18020832
Permit Number 18020832
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2018-04-10 12:07:06THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) A GAS GENERATOR AND GAS REGULATOR IS INDICATED.
 THESE ARE NO APPROVED UNDER THIS PERMIT.
  
 THESE INSTALLATIONS SHALL BE UNDER SEPARATE SHOP
 DRAWINGS.
  
 PLEASE ENSURE ALL MANUFACTURES SPEC ARE PROVIDED AND A
 SITE PLAN SHOWING ALL OPENINGS WITH DIMENSIONS FROM THE
 EXHAUST.
  
 IF THE GENERATOR WILL BE POWERING ANY LIFE SAFETY
 SYSTEM, ENSURE IT MEETS THE REQUIREMENTS OF NFPA 110.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  