2018-04-16 16:48:15 | BUILDING PLAN REVIEW |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER, PX3169 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 2ND REVIEW |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. PLAN PAGE A-1 WALL LEGEND D STATES DOOR TO BE |
| REMOVED AT MEZZANINE. NOTE AT DOOR STATES TO USE WALL |
| TYPE A FOR DOOR INFILL. THERE IS ALSO A SETION OF WALL |
| TO BE INFILLED WITH WALL TYPE A ADJACENT TO DOOR D. |
| WALL SECTION A TERMINATES AT SECOND FLOOR DECK, SEE |
| DETAIL 1, A-1. PROVIDE DETAIL FOR WALL THAT TERMINATES |
| AT ROOF DECK. THESE WALLS SHALL BE 1 HOUR RATED. |
| |
| 2. COVER PAGE DETAIL 1, CS-1 SHOWS CEILING INSULATION |
| R-38 HELD WITH STRAPPING. PLAN PAGE A-1 SHOWS ICYNENE |
| SPRAY FOAM TO ENTIRE DECK. PLEASE CLARIFY. IF ICYNENE |
| IS USED, STATE R VALUE AND PROVIDE ICC-ES REPORT. ALSO |
| IDENTIFY TYPE OF THERMAL BARRIER TO BE USED FOR THE |
| ICYNENE PRODUCT. |
| |
| 3. PROVIDE CURRENT REFERENCE STANDARD FOR THERMAX |
| INSULATION TO BE USED AS WALL INSULATION. MIAMI DADE |
| NOA 02-0703.03 REFERENCED IN THE TECHNICAL DATA |
| PROVIDED FOR INSULATED WALLS HAS EXPIRED. |
| |
| 4. PLATFORM LIFT - |
| 4A. PROVIDE LEGIBLE PLAN. PRINT TOO SMALL TO READ. |
| 4B. PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS |
| WITH FASTENER SCHEDULE TO MEET EXISTING SITE |
| CONDITIONS, |
| 4C. PROVIDE ELEVATION DRAWING OF PLATFORM LIFT SITE |
| CONDITIONS. SHOW ELEVATION OF FINISHED FLOOR, TOP OF |
| STAIRS, TOP OF CONCRETE SLAB AND PAVEMENT. |
| |
| 5. MECHANICAL DESIGNER TO DEMONSTRATE THE NEW |
| MECHANICAL CURB WILL COMPLY WITH THE DESIGN PARAMETERS |
| SPECIFIED ON PLAN PAGE S-1 BY THE STRUCTURAL ENGINEER |
| OF RECORD. |
| 5A. PER NOTE 9, PLAN PAGE M-2, DESIGNER TO SPECIFY TYPE |
| AND SIZE OF FASTENERS AT MECHANICAL CURB TO ROOF |
| ATTACHMENT. |
| |
| 6. OVERHEAD DOOR PARAMENTERS TO BE PLACED ON DOOR |
| SCHEDULE. DESIGNER TO REVIEW AND APPROVE PRODUCT |
| APPROVALS. |
| |
| 7. ADA PARKING DETAIL PROVIDED FOR YOUR REVIEW AND USE. |
| |
| NOTE: WELDER CERTIFICATIONS TO BE ON-SITE AT TIME OF |
| INSPECTION. |
| |
| |
| |
| |