Plan Review Notes For Permit 18020832 |
Permit Number |
18020832 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-03-16 16:11:43 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #18020832 | | 3/16/18 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE INPUT DATA REPORT ATTACHED WITH THE FLORIDA | | ENERGYGAUGE COMPLIANCE REPORT LISTS R-VALUES FOR THE | | WALLS AND ROOF, AND DIRECTIONAL ORIENTATIONS FOR THE | | WALLS THAT DO NOT MATCH WITH THE ARCHITECTURAL PLANS. | | THE ARCHITECT OF RECORD MUST REVIEW THE ENERGY REPORT, | | MAKE CORRECTIONS, AND THEN PROVIDE HIS CERTIFICATION | | SIGNATURE ON PAGE 4 OF THE REPORT. | | | | 2) M-2: THE RTU INSTALLATION DETAILS ARE INCOMPLETE: A) | | PROVIDE THE WIND LOAD DESIGN CRITERIA IN ACCORDANCE | | WITH SECTION1609 FBC-17 BUILDING. B) PROVIDE ENGINEERED | | STRUCTURAL DRAWINGS FOR CREATING THE RTU ROOF OPENINGS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|