Plan Review Notes For Permit 18020832 |
Permit Number |
18020832 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-02-26 11:25:09 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | | | 1) A GAS GENERATOR AND GAS REGULATOR IS INDICATED. | | THESE ARE NO APPROVED UNDER THIS PERMIT. | | | | THESE INSTALLATIONS SHALL BE UNDER SEPARATE SHOP | | DRAWINGS. | | | | PLEASE ENSURE ALL MANUFACTURES SPEC ARE PROVIDED AND A | | SITE PLAN SHOWING ALL OPENINGS WITH DIMENSIONS FROM THE | | EXHAUST. | | | | IF THE GENERATOR WILL BE POWERING ANY LIFE SAFETY | | SYSTEM, ENSURE IT MEETS THE REQUIREMENTS OF NFPA 110. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|