Plan Review Notes For Permit 18020762 |
Permit Number |
18020762 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-03-15 08:24:55 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE SPECIFICATIONS SUBMITTED ARE FOR A 24 KW KOHLER | | GENERATOR WITH MODEL NUMBER 24 RCL. THE AMERICAST | | GENERATOR PAD ENGINEERING DOES NOT LIST THE 24 KW | | KOHLER, MODEL 24 RCL. SUBMIT TWO SETS OF ENGINEERING | | AND SPECIFICATIONS THAT MATCH. FBC 107.2.1 | | |
|