2018-02-28 16:17:48 | DENIED |
| |
| 1. PE PIPE UNDER CONCRETE SLAB SHALL BE ENCASED IN A |
| PROTECTIVE SLEEVE, SHOW ON THE ISOMETIC PLANS WHERE AND |
| HOW LONG FBC FG G2415.6 UNDERGROUND PENETRATIONS. |
| |
| 2. TABLES SUBMITTED ARE AND ARE NOT THE RECENTLY |
| APPROVED. THE COPY OF THE TABLE FBC FG 2009 IS FROM AN |
| OUTDATED FUEL GAS CODE. THE FUEL GAS CODE IN EFFECT IS |
| THE 2017 FBC FUEL GAS. SUBMIT TWO COPIES OF THE CORRECT |
| SIZING TABLE. WPB AMENDMENTS TO THE FBC SEC. 107.2.1. |
| |
| 3. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS THE |
| TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH |
| APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH |
| APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF |
| PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE |
| EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE |
| SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE |
| REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES |
| 2017 FBC FUEL GAS SECS. 401.4, 401.8, 402.1, 402.2, |
| 402.3 OR 2017 FBC FUEL GAS RES. SECS.G2412.4, G2412.8, |
| G2413.1, G2413.2, G2413.3. |
| |
| 4. THE MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR |
| SHALL BE ONSITE FOR FINAL GAS INSPECTION. BTU RATING ON |
| DORMANT FLEX LINE MUST NOT BE EXCEEDED. |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |