2018-02-27 14:38:49 | 1. PLEASE SUBMIT THE LATEST VERSION OF THE 'AUTO-CALC |
| CERTIFIED COST ESTIMATE FORM' FOR SUBMISSION TO CITY OF |
| WEST PALM BEACH PUBLIC WORKS DEPARTMENT FOR ADDITIONAL |
| WORK PROPOSED. THIS FORM CAN BE DOWNLOADED FROM THE |
| FOLLOWING LINK: HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING- |
| PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS |
| |
| 2. FIRE HYDRANT FLOW TEST DATA FROM EXISTING FIRE |
| HYDRANT WILL BE REQUIRED PART OF THE PLAN SUBMITTAL. |
| SHOW HYDRANT FLOW TEST DATA RESULT ON THE PLANS. |
| |
| 3. SUBMIT ESTIMATES FOR FIRE DEMAND, BOTH AVERAGE AND |
| PEAK FLOW WITH PEAKING FACTOR. SHOW PROJECTED DEMANDS |
| ON THE UTILITY PLAN SHEET. |
| |
| 4. AS-BUILT SHOWS A 30-INCH SANITARY SEWER, NOT A |
| 28-INCH STORM DRAINAGE. CONTACT ENGINEERING SERVICES |
| DEPARTMENT FOR AS-BUILT INFORMATION. |
| |
| 5. ONE FIRELINE CANNOT SERVICE THREE DIFFERENT |
| PROPERTIES. PLEASE SUBMIT A PERMIT FOR EACH PROPERTY |
| AND EACH PROPERTY HAS TO HAVE ITS OWN PRIVATE FIRELINE. |
| |
| 6. PRIVATE FIRELINES CANNOT BE CONSTRUCTED WITHIN |
| CITY'S ALLEYWAY. |
| |
| 7. SHOW SURVEY DATUM USED IN THE PLANS. CITY USES NGVD |
| 1929, PLEASE PROVIDE CONVERSION FOR NAVD 1988. |
| |
| 8. SHOW EXISTING WATER AND SEWER SERVICE CONNECTIONS |
| INCLUDE MATERIAL AND SIZE. |
| |
| 9. FOR THE FINAL WATER AND SEWER PLANS, INCLUDE A NOTE |
| THAT: AS OF DECEMBER 20, 2015 THE CITY OF WEST PALM |
| BEACH CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, |
| MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD |
| FREE." FOR MORE INFORMATION REFER TO THE LINK BELOW: |
| HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI |
| CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL |
| |