2018-03-12 11:52:12 | 1) SUBMIT TWO SETS OF PLANS THAT CLEARLY REFLECT THE |
| ENTIRE SCOPE OF WORK TO BE DONE. SUBMIT TWO COPIES OF |
| AN EXISTING FLOOR PLAN AND ALSO A PROPOSED FLOOR PLAN. |
| WPB AMEND. TO FBC SEC. 107.1, 107.2.1. |
| 2) COMPLY WITH WPB AMEND. TO FBC 107.3.5 FOR MINIMUM |
| PLAN REVIEW CRITERIA FOR BUILDINGS. |
| 3) THE PLANS DO NOT INDICATE TO WHAT CODE THEY WERE |
| DEVELOPED. THE PLANS SHALL COMPLY WITH THE 2017 |
| FBC-EXISTING BUILDING CODE AND THE OTHER APPLICABLE |
| VOLUMES OF THE 2017 FBC. THE LEVEL OF ALTERATION SHALL |
| BE NOTED ON THE PLANS PER SEC. 301.1 OF THE 2017 |
| FBC-EXISTING BUILDING CODE. |
| 4) 2017 FBC-EXISTING BUILDING CODE SEC. 301.1 - THE |
| ALTERATION OF ALL EXISTING BUILDINGS SHALL COMPLY WITH |
| ONE OF THE METHODS LISTED IN SECS.301.1.1 THROUGH |
| 301.1.3 AS SELECTED BY THE APPLICANT. |
| 5) SUBMIT PLANS/DETAILS SHOWING HOW COMPLIANCE WITH THE |
| 2017 FBC-ACCESSIBILITY CODE WILL BE ACCOMPLISHED. |
| 6) THE HEIGHT OF THE LUNCH ROOM CABINET COUNTERTOP AND |
| SINK SHALL COMPLY WITH THE 2017 FBC-ACCESSIBILITY SECS. |
| 212 & 606. |
| 7) ONE OF THE SUBMITTED PLAN SHEETS IS DONE IN PENCIL. |
| PLANS DONE IN PENCIL ARE NOT AN ACCEPTED FORMAT. WPB |
| AMEND. TO FBC SEC.107.1. |
| 8) THE NOTE FOR THE SCOPE OF PLUMBING WORK FOR THE |
| LUNCH ROOM ON THE SECOND FLOOR IS INCOMPLETE AND IS |
| VAGUE. CLARIFY THE COMPLETE SCOPE OF PLUMBING WORK TO |
| BE DONE. WPB AMEND. TO FBC SEC. 10.2.1. |
| 9) THE PLANS FOR THE 2ND FLOOR BATHROOM ALTERATION |
| SHALL SHOW THE LOCATION OF ALL EXISTING PLUMBING |
| FIXTURES AND ANY NEW LOCATIONS OF THE FIXTURES, |
| LOCATIONS OF STALL PARTITIONS, THE LENGTH AND WIDTH |
| DIMENSIONS OF ALL PLUMBING FIXTURE STALLS, ETC. |
| 10) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE TYPE |
| OF PLUMBING FIXTURES TO BE INSTALLED. NEW FIXTURES |
| SHALL COMPLY WITH THE 2017 FBC- PLUMBING SEC. 604.4 FOR |
| MAXIMUM WATER FLOW AND CONSUMPTION. |
| 11) NEW FAUCETS SHALL COMPLY WITH 2017 FBC-PLUMBING |
| SEC.605.2.1. FOR LEAD CONTENT AND SHALL COMPLY WITH NSF |
| 372. |
| |
| NOTE: BECAUSE OF THE LACK OF REQUIRED INFORMATION ON |
| THE SUBMITTED DRAWINGS A COMPREHENSIVE PLAN REVIEW |
| COULD NOT BE DONE. RE- REVIEW OF CORRECTED DOCUMENTS |
| MAY RESULT IN ADDITIONAL PLAN REVIEW COMMENTS BEING |
| GENERATED. |
| |