Plan Review Notes
Plan Review Notes For Permit 18020637
Permit Number 18020637
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-02-21 12:04:17PERMIT # 18020637
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) HAND DRAWN LAYOUT DOES NOT MEET THE REQUIREMENTS OF
 THE REQUIRED SITE PLAN FOR PLAN REVIEW. PROVIDE A LIFE
 SAFETY PLAN SHOWING ALL OCCUPANCY TYPES, OCCUPANT
 LOADS, FIRE RATED WALLS, EXIT SIGNS, EMERGENCY
 LIGHTING, TRAVEL DISTANCES, COMMON PATH OF TRAVEL ETC.
  
 2) 2 COPIES OF ALL DOCUMENTS AND PLANS IS REQUIRED.
  
 3) INFORMATION PROVIDED IS NOT SUFFICIENT TO COMPLETE A
 PROPER PLAN REVIEW. ADDITIONAL COMMENTS MAY BE PROVIDED
 UPON RESUBMISSION OF UPDATED PLANS.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  