2018-02-22 12:31:41 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 18020637 |
| ADD: 1045 CHARLOTTE AVE. |
| CONT: 489 EXEMPT. CITY OF WEST PALM BEACH |
| TEL: 561-797-5541 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURS. FEB. 22/ 2018 |
| ACTION: DENIED |
| |
| 1) 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 107.2.1.4 QUALITY OF BUILDING PLANS. |
| BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH |
| SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE |
| MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND |
| SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR |
| OTHER ITEMS RELATED TO RECORDS MANAGEMENT. ELECTRONIC |
| MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS |
| OF FLORIDA STATUTES. |
| |
| 2) . SINCE THE CITY OF WEST PALM BEACH IS APPLYING FOR |
| A PERMIT AND GOING FOR THE CONTRACTOR EXEMPTION UNDER F |
| S 489.103(3) THE PERSON CREATING THE PLANS STILL HAS TO |
| TAKE OWNERSHIP OF THE PLANS. THE CONTRACTOR (QUALIFIER) |
| THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO |
| IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE |
| PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR |
| THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN. |
| 107.3.4.3 CERTIFICATION BY CONTRACTOR. |
| 3) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| THE EXAMINATION OF THE DOCUMENTS BY THE |
| BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM |
| CRITERIA AND DOCUMENTS: A FLOOR PLAN WITH THE |
| FOLLOWING: |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 107.3.5.1.1 BUILDING |
| |
| 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| SHALL BE DETERMINED. |
| 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| (SEE TABLE 503). |
| 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL |
| INCLUDE THE FOLLOWING COMPONENTS: |
| FIRE-RESISTANT SEPARATIONS |
| FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS |
| FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE |
| RESISTANCE |
| 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: |
| SCHEMATIC FIRE SPRINKLERS |
| STANDPIPES |
| RISER DIAGRAM |
| 6. LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL |
| INCLUDE THE FOLLOWING REQUIREMENTS: |
| OCCUPANT LOAD AND EGRESS CAPACITIES |
| 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| OCCUPANCY LOAD |
| GROSS |
| NET |
| MEANS OF EGRESS |
| EXIT ACCESS |
| EXIT |
| EXIT DISCHARGE |
| STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION |
| DOORS |
| EMERGENCY LIGHTING AND EXIT SIGNS |
| CONSTRUCTION REQUIREMENTS |
| HORIZONTAL EXITS/EXIT PASSAGEWAYS |
| 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE |
| FOLLOWING: |
| SITE REQUIREMENTS |
| ACCESSIBLE ROUTE |
| VERTICAL ACCESSIBILITY |
| TOILET AND BATHING FACILITIES |
| DRINKING FOUNTAINS |
| EQUIPMENT |
| SPECIAL OCCUPANCY REQUIREMENTS |
| |
| 11. INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT) |
| LIGHT AND VENTILATION |
| SANITATION |
| 12. SPECIAL SYSTEMS: |
| ELEVATORS |
| ESCALATORS |
| LIFTS |
| |
| 4) THE PLANS DO NOT INDICATE TO WHAT CODE THEY WERE |
| DEVELOPED NOR DO THEY INDICATE UNDER THE 2017 |
| FBC-EXISTING BUILDING CODE TO WHICH METHOD AND OR |
| ALTERATION LEVEL THEY WERE DESIGNED. |
| |
| 2017 FBC-EXIST. BUILD. CODE 301.1. THE ALTERATION OF |
| ALL EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE |
| METHODS LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS |
| SELECTED BY THE APPLICANT. SECTIONS 301.1.1 THROUGH |
| 301.1.3 SHALL NOT BE APPLIED IN COMBINATION WITH EACH |
| OTHER. |
| |
| 5) PLEASE BE AWARE THE VALUE OF THE PROJECT MAYBE |
| UNDERVALUED AND WOULD NEED TO COMPLY WITH: |
| 108.3* BUILDING PERMIT VALUATION. IF, IN THE OPINION OF |
| THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF |
| BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER |
| ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL |
| REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL, |
| PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE |
| WORK (EXCAVATION AND BACKFILL FOR BUILDINGS), |
| ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD |
| AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION |
| REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF |
| NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| 6) PLEASE ALSO SHOW HOW COMPLIANCE WITH THE 2017 |
| ACCESSIBILITY CODE WILL BE ACCOMPLISHED SEE SECTION: |
| |
| 202.4.1 DISPROPORTIONATE COST. |
| ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF |
| TRAVEL TO THE ALTERED AREA WILL BE DEEMED |
| DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE |
| COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE |
| PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS |
| EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF |
| TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING |
| AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE |
| ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING |
| RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, |
| ENLARGING TOILET STALLS, INSULATING PIPES, OR |
| INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS |
| ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH |
| AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, |
| INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT |
| TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING |
| AN INACCESSIBLE DRINKING FOUNTAIN. |
| |
| 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF |
| DISPROPORTIONALITY. WHEN THE COST OF ALTERATIONS |
| NECESSARY TO MAKE THE PATH OF TRAVEL TO THE ALTERED |
| AREA FULLY ACCESSIBLE IS DISPROPORTIONATE TO THE COST |
| OF THE OVERALL ALTERATION, THE PATH OF TRAVEL SHALL BE |
| MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE MADE |
| ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE COSTS. IN |
| CHOOSING WHICH ACCESSIBLE ELEMENTS TO PROVIDE, PRIORITY |
| SHOULD BE GIVEN TO THOSE ELEMENTS THAT WILL PROVIDE THE |
| GREATEST ACCESS, IN THE FOLLOWING ORDER: (I) AN |
| ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE ROUTE TO THE |
| ALTERED AREA; (III) AT LEAST ONE ACCESSIBLE RESTROOM |
| FOR EACH SEX OR A SINGLE UNISEX RESTROOM; (IV) |
| ACCESSIBLE TELEPHONES; (V) ACCESSIBLE DRINKING |
| FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL |
| ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND |
| ALARMS. |
| |
| 7) PERMIT APPLICATION O/ B SIGNATURE NOT NOTARIZED. |
| VALUE OVER $2,500.00 IN VALUE. |
| |
| 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| |
| JAMES A. WITMER BN, PX, CBO |