Plan Review Notes
Plan Review Notes For Permit 18020610
Permit Number 18020610
Review Stop P
Sequence Number 1
Notes
Date Text
2018-03-02 13:04:531ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT.A3.0.2 DETAIL #7 THE REAR WALL GRAB BAR SHALL BE
 36 INCHES LONG MINIMUM AND EXTEND FROM THE CENTERLINE
 OF THE WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND
 24 INCHES MINIMUM ON THE OTHER SIDE. PER FBC ACC
 604.5.2
  
 2. SHT.A3.0.2 DETAIL #8 SHOWS A SHOWER SEAT PLEASE SHOW
 ON DETAIL #6 IT SHALL COMPLY WITH FBC ACC 608.5.1 ,
 608.3.2
  
 3. SHT.A3.0.2 DETAIL #3 THE SIDE WALL GRAB BAR SHALL BE
 42 INCHES LONG MINIMUM, LOCATED 12 INCHES MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE
 REAR WALL.
  
 4. SHT.A3.0.2 DETAIL #6 SHOW CLEAR FLOOR SPACE FOR
 LAVATORY. PER FBC ACC 606.2
  
 5. PLEASE SHOE CODE COMPLIANCE FOR FBC ACC 608.5.2
 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS.
 IN STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS, THE
 CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE
 LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN 48
 INCHES ABOVE THE SHOWER FLOOR. WHERE A SEAT IS
 PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT
 SHALL BE INSTALLED ON THE BACK WALL ADJACENT TO THE
 SEAT WALL AND SHALL BE LOCATED 27 INCHES MAXIMUM FROM
 THE SEAT WALL.
  
 6. PLEASE PROVIDE A WATER AND SANITARY ISOMETRIC
 DRAWING. PER WPB AMEND TO FBC 107.2.1.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  