Plan Review Notes
Plan Review Notes For Permit 18020610
Permit Number 18020610
Review Stop M
Sequence Number 1
Notes
Date Text
2018-02-20 15:51:131ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18020610
 2/20/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M-1.0: EXHAUST REQUIRED FOR THE LOCKER ROOM- TABLE
 403.1.1.
  
 2) M-1.0: VERIFY THAT THE 36"X48" ACCESS PANEL IS LARGE
 ENOUGH TO REMOVE AND REPLACE THE AIR HANDLER- SECTION
 306.1.
  
 3) M-2.0: CORRECT NOTE #13 WHICH IS REFERENCING THE
 OUTDATED 2014 FLORIDA ENERGY CONSERVATION CODE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  