2018-02-20 13:36:40 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| PANEL WHICH INCLUDES INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| ESTIMATED VALUES ARE NOT ACCEPTABLE DUE TO LABELING |
| REQUIREMENT OF NEC 110.24. THIS CAN BE PROVIDED AS A |
| DEFERRED SUBMITTAL PRIOR TO INSPECTION IF DESIRED. IF |
| SO, PROVIDE NOTE TO THAT AFFECT. NEC 110.9, 110.10 |
| 2. PROVIDE NOTE TO INDICATE MARKING OF HIGH-LEG PER |
| CODE. NEC 110.15 |
| 3. RECEPTACLE CONTROL DETAILED ON PLAN DOES NOT MEET |
| CODE REQUIREMENTS. PROVIDE RECEPTACLE CONTROL REQUIRED |
| BY ASHREA 90.1: 8.4.2. PER THIS REQUIREMENT, THE |
| FOLLOWING SHALL BE AUTOMATICALLY CONTROLLED: 1) AT |
| LEAST 50% OF ALL 125-VOLT, 15 AND 20 AMP RECEPTACLES, |
| IN ALL PRIVATE OFFICES, CONFERENCE ROOMS, ROOMS USED |
| PRIMARILY FOR PRINTING AND/OR COPYING FUNCTIONS, BREAK |
| ROOMS, CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT |
| LEASE 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR |
| MODULAR FURNITURE NOT SHOWN ON THE CONSTRUCTION |
| DOCUMENTS. FBC EC C405.6.1 |
| 4. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| SERVICE. SHOW ON PLAN. NEC 250.94 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |