Plan Review Notes For Permit 18020563 |
Permit Number |
18020563 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-02-17 13:41:31 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. PRODUCT APPROVAL IS INCOMPLETE. ALL PAGES WHICH | | APPLY TO ALL ASSEMBLIES SHOULD BE INCLUDED. THE PAGES | | APPLICABLE TO THE ASSEMBLY SHOULD BE INCLUDED. THE | | DESIGN PRESSURES FOR B, OPEN WERE PROVIDED, THIS | | PROJECT IS C, ENCLOSED. | | | | 2. EXPOSURE B IS APPLICABLE WHEN THERE ARE SINGLE | | FAMILY SIZED DWELLINGS IN THE UPWIND DIRECTION FOR 1200 | | FEET MINIMUM, WHICH IS NOT THE CASE FOR THIS STRUCTURE, | | PLEASE SEE AERIAL AND CHANGE EXPOSURE TO C OR CONTACT | | ME TO DISCUSS, FBC B 1609. | | | | |
|