2018-08-21 04:18:36 | 1) SHT. A -1 - PLUMBING RISERS - SUBMIT TWO COPIES OF A |
| CODE COMPLIANT SANITARY RISER DIAGRAM. 2ND REQUEST. |
| NOTHING HAS BEEN DONE TO THE SANITARY RISERS TO CORRECT |
| THE DEFICIENCIES. |
| PLUMBING RISER - MASTER BATHROOM: |
| A)THE DOUBLE LAVATORIES SHALL BE STACKED AND |
| VENTED.2017 FBCR-SEC.P3101.2 P3101.2.1. |
| B) THE MASTER BATHROOM SANITARY RISER SHOWS AN EXISTING |
| SANITARY LINE FOR "BASEMENT PLUMBING" BUT THERE IS NO |
| REFERENCE TO A BASEMENT NOR IS A BASEMENT SHOWN IN |
| THESE PLANS . CLARIFY. |
| 2) SIZE ALL SECTIONS OF THE SANITARY DRAINAGE LINES AND |
| VENT LINES ON BOTH SANITARY RISER DIAGRAMS.2ND REQUEST. |
| 3) THE PLANS SHOW A MASTER BATHROOM AND AN EXISTING |
| BATHROOM BUT THE SANITARY RISER DIAGRAMS ARE FOR A |
| MASTER BATH AND ALSO A NEW STORAGE BATH. CLARIFY.THE |
| STORAGE ROOM IS SHOWN ON SHEET A-2 BUT HAS BEEN OMITTED |
| FROM OTHER SHEETS. CLARIFY. |
| 4) SHT. A-2 - ADDITION ROOF PLAN - SUBMIT ADDITIONAL |
| INFORMATION AS TO HOW THE SIZE OF THE SCUPPERS WERE |
| CALCULATED. THERE IS NO TABLE IN THE PLUMBING CODE FOR |
| SIZING SCUPPERS. THE ROOF PLAN REFERS TO TABLE 1106.3 |
| OF THE FLORIDA PLUMBING CODE FOR THE SIZING OF THE |
| SCUPPERS. THIS TABLE IS FOR SIZING VERTICAL LEADERS, |
| NOT SCUPPERS. SCUPPERS SHALL BE SIZED IN ACCORDANCE |
| WITH 2017 FBC-PLUMBING SEC.1108.3, 1101.7. NOTE: THERE |
| IS NO TABLE THAT SPECIFIES THE SQUARE FOOTAGE OF THE |
| ROOF BEING DRAINED. ALL THE TABLES ARE BASED ON THE |
| FLOW RATE.2017 FBC SEC.1101.7, 1108.1. |
| 5) THE SIZE OF THE MASTER BATH SHOWER SHALL COMPLY WITH |
| 2017 FBCR SEC.P2708.1. |
| 6) PLUMBING FIXTURES SHALL BE SPACED IN ACCORDANCE WITH |
| 2017 FBCR SEC.P2705.1. |
| |
| NOTE: I SUGGEST CONTACTING THIS PLAN REVIEWER TO |
| DISCUSS THE COMMENTS SO COMPLIANCE CAN BE ACHIEVED AND |
| THE PLUMBING CAN BE APPROVED. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |
| [email protected] |
| |
| |