| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| |
| 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY |
| SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, |
| 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, |
| E3609.3; FBC 107.2.1 (NOT PROVIDED ON SHEET A-2 AS |
| MENTIONED IN RESPONSE.) |
| 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC RE |
| E3706.2, E3902 (NOT PROVIDED ON SHEET A-2 AS MENTIONED |
| IN RESPONSE.) |
| 3. CORRECTED. |
| 4. CORRECTED. |
| 5. CORRECTED. |
| 6. CORRECTED. |
| 7. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 |
| (NOT PROVIDED ON SHEET A-2 AS MENTIONED IN RESPONSE.) |
| 8. CORRECTED. |
| 9. CORRECTED. |
| 10. CORRECTED. |
| 11. PROVIDE FULL FLOOR PLAN SHOWING SMOKE ALARMS IN |
| EACH LOCATION REQUIRED PER CODE. SHOW ON PLAN ALL |
| EXISTING ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, |
| SHOW AS NEW INSTALLATIONS. SMOKE ALARMS MUST BE |
| INSTALLED AT LEAST 3 FEET FROM BATHROOM DOOR, 3 FEET |
| FROM CEILING FANS, AND 3 FEET FROM ANY MECHANICAL DUCT. |
| PROVIDE CORRECTIONS. FBC RE R314.3(4), NFPA |
| 72:29.8.3.4; FBC R314.3, FBC 107.2.1 (NOT PROVIDED AS |
| MENTIONED IN RESPONSE.) |
| 12. CORRECTED. |
| 13. CORRECTED. |
| 14. CORRECTED. |
| 15. FEE ADDED. |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| PHIL PETTY |
| CHIEF ELECTRICAL INSPECTOR |
| 561-805-6742 |
| [email protected] |
| |