2018-06-13 18:10:17 | PLAN |
| REVIEW COMMENTS |
| |
| 4TH REVIEW: FBC SIXTH EDITION (2017) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1A) THE RESPONSE LETTER FROM THE ARCHITECT (DESIGNER OF |
| RECORD) ONLY ADDRESSES THE ADDITION TO THE EXISTING |
| SINGLE FAMILY DWELLING AND THE SITE PLAN ON SHEET A-1 |
| HAS A NOTE THAT STATES THAT THE WORK AREA FOR THIS |
| PERMIT IS THE MASTER BEDROOM AND OPEN PORCH ADDITION. |
| HOWEVER, THE PLANS STILL HAVE THE STORAGE BUILDING |
| SHOWN ON THEM. PLEASE CLARIFY. FBC 107.2.1 IF THE |
| STORAGE BUILDING IS NOT PART OF THIS PERMIT, ALL |
| DRAWINGS AND NOTES THAT PERTAIN TO IT NEED TO BE |
| REMOVED FROM THE PLANS OR CROSSED OUT BY THE DESIGNER |
| OF RECORD. |
| |
| 1) (PARTIAL COMPLIANCE. ASCE 7-16-2018 IS SPECIFIED ON |
| THE PLANS. THE 2016 EDITION OF ASCE 7 HAS NOT BEEN |
| ADOPTED INTO THE 2017 FLORIDA BUILDING CODE (SIXTH |
| EDITION). ASCE 7 - 10 IS THE EDITION THAT IS REFERENCED |
| IN THE 2017 FBC. FBC-R CHAPTER 46 REFERENCED STANDARDS. |
| PLEASE REVISE PLANS ACCORDINGLY.) FBC 107.3.5.3 - |
| PROVIDE WIND DESIGN CRITERIA. (THE COMPONENT AND |
| CLADDING PRESSURES FOR THE ROOF AND WALLS ON SHEET A-2 |
| ARE NOT CORRECT.) SPECIFY THE COMPONENT AND CLADDING |
| DESIGN PRESSURES PURSUANT TO FBC-R301.2.1 ( THE ROOF |
| SHEATHING FASTENERS ARE SPECIFIED AS RSRS 01. NAILS. |
| CLARIFY.) SPECIFY THE ROOF SHEATHING FASTENING PER |
| FBC-R803.2.3.1 (COMPLIED.) SPECIFY THE CODE EDITION AND |
| THE LEVEL OF ALTERATION FOR THE ADDITION ON THE PLANS.) |
| |
| 2) FBC ENERGY CONSERVATION - SECT. R103.1.1.2 CODE |
| COMPLIANCE CERTIFICATION. THE BUILDING'S OWNER, THE |
| OWNER'S ARCHITECT, OR OTHER AUTHORIZED AGENT LEGALLY |
| DESIGNATED BY THE OWNER SHALL CERTIFY THAT THE BUILDING |
| IS IN COMPLIANCE WITH THE CODE, AS PER SECTION 553.907, |
| FLORIDA STATUTES, PRIOR TO RECEIVING THE PERMIT TO |
| BEGIN CONSTRUCTION OR RENOVATION. FBC ENERGY |
| CONSERVATION SECTIONS R101.5.1.1.1 OR R101.5.1.1.2. |
| SUBMIT TWO SETS OF ENERGY COMPLIANCE FORMS AS REQUIRED. |
| (ONE SET IS REQUIRED FOR THE ADDITION TO THE EXISTING |
| DWELLING AND ANOTHER SET IS REQUIRED FOR THE NEW |
| STORAGE BUILDING.) |
| |
| 3) COMPLIED. |
| |
| 4) COMPLIED. NO HEATING OR COOLING WAS SPECIFIED FOR |
| THE NEW STORAGE STRUCTURE, WHICH SHALL NOT BE USED AS |
| HABITABLE SPACE. |
| |
| 5) COMPLIED. |
| |
| 6) COMPLIED. |
| |
| 7) ( SPECIFY THE SIZE AND SPACING OF THE VERTICAL |
| REINFORCING FOR THE PARAPET.) PROVIDE STRUCTURAL |
| CONSTRUCTION DETAILS FOR THE PARAPETS ON THE PLANS. |
| FBC-R301.1 |
| |
| 8) PROVIDE STRUCTURAL CONSTRUCTION DETAILS FOR THE |
| BEAMS AT THE PROPOSED COVERED PORCH ON THE PLANS. |
| FBC-R301.1 |
| |
| 9) (SPECIFY THE FASTENER TYPE, SPACING AND EMBED DEPTH |
| OF THE FASTENERS THAT WILL ATTACH THE LEDGERS.) PROVIDE |
| STRUCTURAL DETAILS FOR THE WALL LEDGERS FOR THE ROOF |
| RAFTERS AT THE PROPOSED PORCH AND MASTER BEDROOM |
| ADDITION. FBC-R301.1 |
| |
| 10) COMPLIED. |
| |
| 11) PROVIDE WINDOW AND DOOR BUCK DETAILS ON THE PLANS. |
| FBC-R609.7.2.1 |
| |
| 12) (THE ROOF SCUPPERS ARE REQUIRED TO BE LEVEL WITH |
| THE ROOF SURFACE. FBC 1503.4.2 ONLY THE OVERFLOW |
| SCUPPERS ARE SHOWN AT 4" ABOVE THE ROOF SURFACE ON THE |
| PLANS. NO CALCULATIONS ARE PROVIDED.) SPECIFY THE SIZES |
| OF THE ROOF SCUPPERS ON THE PLANS AND PROVIDE ROOF |
| SCUPPER SIZING CALCULATIONS. FBC-R903.4 & FBC 107.2.1.3 |
| |
| 13) SPECIFY THE SIZE AND LOCATION OF THE OVERFLOW |
| SCUPPERS ON THE PLANS. FBC-R903.4 |
| |
| 14) SHOW COMPLIANCE WITH FBC-R318.5 FOR SCUPPER |
| COLLECTORS AND DOWNSPOUTS THAT DISCHARGE AT LEAST ONE |
| FOOT FROM THE STRUCTURE WALLS. |
| |
| 15) COMPLIED. |
| |
| 16) COMPLIED. |
| |
| 17) COMPLIED. |
| |
| 18) COMPLIED. |
| |
| 19) COMPLIED. |
| |
| 20) COMPLIED. |
| |
| 21) COMPLIED. |
| |
| 22) COMPLIED. |
| |
| 23) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT |
| A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| COMMENTS HAS BEEN ADDRESSED. NOTE: DUE TO THE |
| INFORMATION THAT IS MISSING FROM THE CONSTRUCTION |
| DOCUMENTS ADDITIONAL COMMENTS MAY RESULT. |
| |
| 24) NEW COMMENT. THE ROOF SLOPE IS SPECIFIED AS 1/8" ON |
| THE PLANS. FBC - R905.11.1 REQUIRES A MINIMUM SLOPE OF |
| 1/4" PER FOOT FOR A BUILT UP ROOF ON NEW CONSTRUCTION. |
| |
| 25) NEW COMMENT. AN 8X8 COLUMN WITH ONE #5 VERTICAL BAR |
| IS SHOWN ON SHEET A-2 AT THE COVERED PORCH. CLARIFY. |
| FBC-R301.1 |
| |
| 26) NEW COMMENT. THE COLUMN PAD NOTE ON SHEET A-2 |
| APPEARS TO HAVE A TYPO. IS THIS MEET TO BE #4S AT 6" |
| O.C. E.W. (EACH WAY) RATHER THAN E.A. |
| |
| 27) NEW COMMENT. ON OF THE DOWN SPOUTS FOR THE ROOF |
| SCUPPERS IS SHOWN ON SHEET A-3 AT THE OPEN AREA OF THE |
| COVER PORCH. FBC 107.2.1 |
| |
| 28) NEW COMMENT. SEE R STOP FOR ROOFING MATERIALS |
| COMMENTS. |
| |
| 29) FLORIDA STATUTE 553.80(2)(B) STATES THAT IF A LOCAL |
| GOVERNMENT FINDS IT NECESSARY, IN ORDER TO ENFORCE |
| COMPLIANCE WITH THE FLORIDA BUILDING CODE AND ISSUE A |
| PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY THE CODE |
| THREE OR MORE TIMES FOR FAILURE TO CORRECT A CODE |
| VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH |
| REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE |
| PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION A |
| FEE OF FOUR TIMES THE AMOUNT OF THE PORTION OF THE FEE |
| ATTRIBUTED TO PLAN REVIEW. |
| |
| |
| |
| |