Plan Review Notes
Plan Review Notes For Permit 18020559
Permit Number 18020559
Review Stop B
Sequence Number 4
Notes
Date Text
2018-06-13 18:10:17PLAN
 REVIEW COMMENTS
  
 4TH REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1A) THE RESPONSE LETTER FROM THE ARCHITECT (DESIGNER OF
 RECORD) ONLY ADDRESSES THE ADDITION TO THE EXISTING
 SINGLE FAMILY DWELLING AND THE SITE PLAN ON SHEET A-1
 HAS A NOTE THAT STATES THAT THE WORK AREA FOR THIS
 PERMIT IS THE MASTER BEDROOM AND OPEN PORCH ADDITION.
 HOWEVER, THE PLANS STILL HAVE THE STORAGE BUILDING
 SHOWN ON THEM. PLEASE CLARIFY. FBC 107.2.1 IF THE
 STORAGE BUILDING IS NOT PART OF THIS PERMIT, ALL
 DRAWINGS AND NOTES THAT PERTAIN TO IT NEED TO BE
 REMOVED FROM THE PLANS OR CROSSED OUT BY THE DESIGNER
 OF RECORD.
  
 1) (PARTIAL COMPLIANCE. ASCE 7-16-2018 IS SPECIFIED ON
 THE PLANS. THE 2016 EDITION OF ASCE 7 HAS NOT BEEN
 ADOPTED INTO THE 2017 FLORIDA BUILDING CODE (SIXTH
 EDITION). ASCE 7 - 10 IS THE EDITION THAT IS REFERENCED
 IN THE 2017 FBC. FBC-R CHAPTER 46 REFERENCED STANDARDS.
 PLEASE REVISE PLANS ACCORDINGLY.) FBC 107.3.5.3 -
 PROVIDE WIND DESIGN CRITERIA. (THE COMPONENT AND
 CLADDING PRESSURES FOR THE ROOF AND WALLS ON SHEET A-2
 ARE NOT CORRECT.) SPECIFY THE COMPONENT AND CLADDING
 DESIGN PRESSURES PURSUANT TO FBC-R301.2.1 ( THE ROOF
 SHEATHING FASTENERS ARE SPECIFIED AS RSRS 01. NAILS.
 CLARIFY.) SPECIFY THE ROOF SHEATHING FASTENING PER
 FBC-R803.2.3.1 (COMPLIED.) SPECIFY THE CODE EDITION AND
 THE LEVEL OF ALTERATION FOR THE ADDITION ON THE PLANS.)
  
 2) FBC ENERGY CONSERVATION - SECT. R103.1.1.2 CODE
 COMPLIANCE CERTIFICATION. THE BUILDING'S OWNER, THE
 OWNER'S ARCHITECT, OR OTHER AUTHORIZED AGENT LEGALLY
 DESIGNATED BY THE OWNER SHALL CERTIFY THAT THE BUILDING
 IS IN COMPLIANCE WITH THE CODE, AS PER SECTION 553.907,
 FLORIDA STATUTES, PRIOR TO RECEIVING THE PERMIT TO
 BEGIN CONSTRUCTION OR RENOVATION. FBC ENERGY
 CONSERVATION SECTIONS R101.5.1.1.1 OR R101.5.1.1.2.
 SUBMIT TWO SETS OF ENERGY COMPLIANCE FORMS AS REQUIRED.
 (ONE SET IS REQUIRED FOR THE ADDITION TO THE EXISTING
 DWELLING AND ANOTHER SET IS REQUIRED FOR THE NEW
 STORAGE BUILDING.)
  
 3) COMPLIED.
  
 4) COMPLIED. NO HEATING OR COOLING WAS SPECIFIED FOR
 THE NEW STORAGE STRUCTURE, WHICH SHALL NOT BE USED AS
 HABITABLE SPACE.
  
 5) COMPLIED.
  
 6) COMPLIED.
  
 7) ( SPECIFY THE SIZE AND SPACING OF THE VERTICAL
 REINFORCING FOR THE PARAPET.) PROVIDE STRUCTURAL
 CONSTRUCTION DETAILS FOR THE PARAPETS ON THE PLANS.
 FBC-R301.1
  
 8) PROVIDE STRUCTURAL CONSTRUCTION DETAILS FOR THE
 BEAMS AT THE PROPOSED COVERED PORCH ON THE PLANS.
 FBC-R301.1
  
 9) (SPECIFY THE FASTENER TYPE, SPACING AND EMBED DEPTH
 OF THE FASTENERS THAT WILL ATTACH THE LEDGERS.) PROVIDE
 STRUCTURAL DETAILS FOR THE WALL LEDGERS FOR THE ROOF
 RAFTERS AT THE PROPOSED PORCH AND MASTER BEDROOM
 ADDITION. FBC-R301.1
  
 10) COMPLIED.
  
 11) PROVIDE WINDOW AND DOOR BUCK DETAILS ON THE PLANS.
 FBC-R609.7.2.1
  
 12) (THE ROOF SCUPPERS ARE REQUIRED TO BE LEVEL WITH
 THE ROOF SURFACE. FBC 1503.4.2 ONLY THE OVERFLOW
 SCUPPERS ARE SHOWN AT 4" ABOVE THE ROOF SURFACE ON THE
 PLANS. NO CALCULATIONS ARE PROVIDED.) SPECIFY THE SIZES
 OF THE ROOF SCUPPERS ON THE PLANS AND PROVIDE ROOF
 SCUPPER SIZING CALCULATIONS. FBC-R903.4 & FBC 107.2.1.3
  
 13) SPECIFY THE SIZE AND LOCATION OF THE OVERFLOW
 SCUPPERS ON THE PLANS. FBC-R903.4
  
 14) SHOW COMPLIANCE WITH FBC-R318.5 FOR SCUPPER
 COLLECTORS AND DOWNSPOUTS THAT DISCHARGE AT LEAST ONE
 FOOT FROM THE STRUCTURE WALLS.
  
 15) COMPLIED.
  
 16) COMPLIED.
  
 17) COMPLIED.
  
 18) COMPLIED.
  
 19) COMPLIED.
  
 20) COMPLIED.
  
 21) COMPLIED.
  
 22) COMPLIED.
  
 23) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED. NOTE: DUE TO THE
 INFORMATION THAT IS MISSING FROM THE CONSTRUCTION
 DOCUMENTS ADDITIONAL COMMENTS MAY RESULT.
  
 24) NEW COMMENT. THE ROOF SLOPE IS SPECIFIED AS 1/8" ON
 THE PLANS. FBC - R905.11.1 REQUIRES A MINIMUM SLOPE OF
 1/4" PER FOOT FOR A BUILT UP ROOF ON NEW CONSTRUCTION.
  
 25) NEW COMMENT. AN 8X8 COLUMN WITH ONE #5 VERTICAL BAR
 IS SHOWN ON SHEET A-2 AT THE COVERED PORCH. CLARIFY.
 FBC-R301.1
  
 26) NEW COMMENT. THE COLUMN PAD NOTE ON SHEET A-2
 APPEARS TO HAVE A TYPO. IS THIS MEET TO BE #4S AT 6"
 O.C. E.W. (EACH WAY) RATHER THAN E.A.
  
 27) NEW COMMENT. ON OF THE DOWN SPOUTS FOR THE ROOF
 SCUPPERS IS SHOWN ON SHEET A-3 AT THE OPEN AREA OF THE
 COVER PORCH. FBC 107.2.1
  
 28) NEW COMMENT. SEE R STOP FOR ROOFING MATERIALS
 COMMENTS.
  
 29) FLORIDA STATUTE 553.80(2)(B) STATES THAT IF A LOCAL
 GOVERNMENT FINDS IT NECESSARY, IN ORDER TO ENFORCE
 COMPLIANCE WITH THE FLORIDA BUILDING CODE AND ISSUE A
 PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY THE CODE
 THREE OR MORE TIMES FOR FAILURE TO CORRECT A CODE
 VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH
 REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE
 PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION A
 FEE OF FOUR TIMES THE AMOUNT OF THE PORTION OF THE FEE
 ATTRIBUTED TO PLAN REVIEW.
  
  
  
  