2018-04-20 17:48:12****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 DENIED BY BUILDING - ONE SET OF PLANS HAVE A DATE OF
 2/1/18, THE OTHER SET HAS A DATE OF 4/4/18, APPEAR THE
 SAME, COMMENTS NOT ADDRESSED (SAME PLANS SUBMITTED AS
 PREVIOUS REVIEWS)
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.3.5.3 - PROVIDE WIND DESIGN CRITERIA.
 SPECIFY THE COMPONENT AND CLADDING DESIGN PRESSURES
 PURSUANT TO FBC-R301.2.1 SPECIFY THE ROOF SHEATHING
 FASTENING PER FBC-R803.2.3.1 (SPECIFY THE CODE EDITION
 AND THE LEVEL OF ALTERATION FOR THE ADDITION ON THE
 PLANS.)
  
 2ND REVIEW - WIND DESIGN CRITERIA SHOULD INCLUDE
 EXPOSURE CLASSIFICATION (MINIMUM EXPOSURE C).
  
 2-6) OK
  
 7) PROVIDE STRUCTURAL CONSTRUCTION DETAILS FOR THE
 PARAPETS ON THE PLANS. FBC-R301.1
  
 8) PROVIDE STRUCTURAL CONSTRUCTION DETAILS FOR THE
 BEAMS AT THE PROPOSED COVERED PORCH ON THE PLANS.
 FBC-R301.1
  
 9) PROVIDE STRUCTURAL DETAILS FOR THE WALL LEDGERS FOR
 THE ROOF RAFTERS AT THE PROPOSED PORCH AND MASTER
 BEDROOM ADDITION. FBC-R301.1
  
 10) SPECIFY THE STRUCTURAL CONNECTORS THAT WILL BE USED
 TO ANCHOR THE ROOF RAFTERS FOR THE ADDITION AND THE NEW
 CABANA BUILDING. PROVIDE A ROOF CONNECTOR SCHEDULE ON
 THE PLANS. FBC-R301.1
  
 11) PROVIDE WINDOW AND DOOR BUCK DETAILS ON THE PLANS.
 FBC-R609.7.2.1
  
 12) SPECIFY THE SIZES OF THE ROOF SCUPPERS ON THE PLANS
 AND PROVIDE ROOF SCUPPER SIZING CALCULATIONS.
 FBC-R903.4 & FBC 107.2.1.3
  
 13) SPECIFY THE SIZE AND LOCATION OF THE OVERFLOW
 SCUPPERS ON THE PLANS. FBC-R903.4
  
 14) SHOW COMPLIANCE WITH FBC-R318.5 FOR SCUPPER
 COLLECTORS AND DOWNSPOUTS THAT DISCHAGE AT LEAST ONE
 FOOT FROM THE STRUCTURE WALLS.
  
 15) SHOW THE DOOR AND WINDOW LINTELS AND PROVIDE A
 LINTEL SCHEDULE ON THE PLANS. PROVIDE A DROP BEAM
 DETAIL FOR THE POURED TIE BEAM IF THIS METHOD IS USED
 RATHER THAN LINTELS. FBC-R606.10
  
 16) COMPLIED.
  
 17) COMPLIED.
  
 18) COMPLIED.
  
 19) COMPLIED.
  
 20) COMPLIED.
  
 21) SPECIFY THE SIZE AND LOCATIONS OF THE WATER HEATERS
 FOR BOTH THE MAIN HOUSE AND THE STORAGE BUILDING ON THE
 PLANS. FBC-R306.4
  
 22) IN ORDER TO VERIFY THE VALUATION OF THIS PROJECT,
 PROVIDE A COPY OF THE SIGNED CONTRACT. FBC 109.3
 BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. THE
 CONTRACT THAT WAS SUBMITTED INCLUDES A POOL AND SPA
 THAT REQUIRES A SEPARATE PERMIT. PROVIDE THE VALUE OF
 THE POOL AND SPA, SO THAT IT CAN BE DEDUCTED FROM THE
 CONTRACT VALUE.
  
 23) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED. NOTE: DUE TO THE
 INFORMATION THAT IS MISSING FROM THE CONSTRUCTION
 DOCUMENTS ADDITIONAL COMMENTS MAY RESULT.
  
  
  