Plan Review Notes For Permit 18020559 |
Permit Number |
18020559 |
|
Review Stop |
R |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-06-14 15:11:38 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1. A ROOF SUB PERMIT WAS SUBMITTED. INDICATE WHICH | | ASSEMBLY IS PROPOSED AND PROVIDE ENGINEERING FOR ZONE 2 | | AND 3 IF APPLICABLE. IF THIS INFORMATION IS NOT | | PROVIDED, THE ROOF SUB PERMIT APPLICATION WILL BE | | VOIDED AND A ROOF SUB PERMIT WITH ALL REQUIRED | | INFORMATION (PRODUCT APPROVAL, ASSEMBLY PROPOSED, AND | | ENGINEERING IF APPLICABLE) WILL BE REQUIRED PRIOR TO | | INSTALLATION. | | | | 2) TWO SETS OF A ROOFING PRODUCT APPROVAL WERE | | SUBMITTED. THE PROPOSED ASSEMBLY WAS NOT INDICATED. FBC | | 107.2.1 | | | | 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC | | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE | | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER | | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH | | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS | | AND MAXIMUM DESIGN PRESSURES FOR THE ROOFING MATERIALS. | | | | | | | | |
|