Plan Review Notes
Plan Review Notes For Permit 18020428
Permit Number 18020428
Review Stop B
Sequence Number 3
Notes
Date Text
2018-02-22 17:58:47RESIDENTIAL (R3) ALTERATION, THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017).
  
 1- ACCORDING TO ENGINEER CALCULATIONS SUBMITTED THE
 DESIGN PRESSURES SHOWN IN THE INSTALLATION SCHEDULE
 SEEM TO BE TOO LOW FOR A BUILDING LOCATED IN EXPOSURE C
 IF THE OPENINGS ARE LOCATED IN AND END ZONE OF 10 FT
 AND A MEAN ROOF HEIGHT OF 27FT. ENGINEER TO REVISE
 DESIGN PRESSURES AS REQUIRED. SEC. R301.1
 FBC-RESIDENTIAL, 6TH EDITION (2017).
  
 2- ENGINEER CALCULATIONS NEED THE FOLLOWING:
 A) ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY
 61G15-23.003 F.A.C. PLEASE SUBMIT ORIGINAL
 CALCULATIONS, NOT VIA E-MAIL.
  
 B) CALCULATIONS NEED A TITLE BLOCK WITH ALL THE
 ENGINEER'S INFORMATION AS REQUIRED BY 61G15-23.001(4)
 F.A.C.
  
 3- INSTALLATION SCHEDULE CALLS FOR NOTE #2 FOR TOP
 CONNECTION "U". THE CORRECT NOTE TO REFERENCE IS NOTE
 #3 NOT NOTE #2. REVISE/CLARIFY AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
  