2018-02-15 15:13:11RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017).
  
 1- REVISED INSTALLATION SCHEDULE SUBMITTED:
 A) THE DESIGN CRITERIA INFORMATION SHOWN DOESN'T MATCH
 ACTUAL BUILDING. ALSO, THERE IS INFORMATION IN THE
 DESIGN CRITERIA THAT DOESN'T SEEM TO APPLY FOR THIS
 PROJECT. IF USING THIS INFORMATION, THEN PROVIDE
 COMPLETE SITE SPECIFIC SIGNED AND SEALED CALCULATIONS
 USING ONLY THE REQUIRED INFORMATION TO OBTAIN THE
 DESIGN PRESSURES. SEC. 107.2.1.3 CITY AMENDMENTS.
 NOTE: IF USING THE FBC TABLES, THEN JUST SPECIFY THE
 CURRENT CODE (2017), BUILDING MEAN ROOF HEIGHT,
 LOCATION OF OPENINGS (END OR INTERIOR) AND BUILDING
 EXPOSURE.
  
 B) INSTALLATION SCHEDULE IS MISSING THE GLASS
 SEPARATION DISTANCE. SEC. R301.1 FBC-RESIDENTIAL.
 GLASS SEPARATION IS REQUIRED TO BE IN THE INSTALLATION
 SCHEDULE. THE PURPOSE OF THE INSTALLATION SCHEDULE IS
 TO INCLUDE ALL THE PROPOSED INSTALLATION TO FACILITATE
 REVIEW AND INSPECTIONS. SEE CITY INSTALLATION SCHEDULE
 SAMPLE THAT SHOWS ALL THE INFORMATION THAT IS REQUIRED
 TO BE INCLUDED. CONTRACTOR MAY USE THE CITY
 INSTALLATION SCHEDULE OR PROVIDE ANY OTHER FORMAT AS
 LONG AS ALL THE REQUIRED INFORMATION IS INCLUDED.
  
 C) CLARIFY WHAT DOES CONNECTION TYPE 3/8"WM SPECIFIED
 FOR OPENINGS #1 AND #2 ON TOP CONNECTION STANDS FOR?.
 DETAIL SECTION "A" DOESN'T SPECIFY THIS. SEC. 107.2.1
 CITY AMENDMENTS.
  
 D) CLARIFY WHAT DOES CONNECTION TYPE "ADJ SILL"
 SPECIFIED FOR ALL OPENINGS AT BOTTOM CONNECTION STANDS
 FOR?. DETAIL SECTION "H" DOESN'T SPECIFY THIS. SEC.
 107.2.1 CITY AMENDMENTS.
  
 E) SIZE OF LAG SCREWS SPECIFIED ON TOP CONNECTION USING
 SECTION OR TYPE "U" IS NOT CLEAR. INSTALLATION SCHEDULE
 CALLS FOR THREE 5/16 X 3 LAG SCREWS, WHILE NOTE BELOW
 THE INSTALLATION SCHEDULE CALLS FOR THREE 5/16 X 3.5"
 LAGS. REVISE AS REQUIRED TO MATCH. NOTE: THE SPECIFIED
 SCREW NEEDS TO HAVE MIN. 2" PENETRATION OF THREADED
 AREA. SEE SECTION DETAIL "U" AND REVISE LAG SCREW SIZE
 TO INCLUDE THE THICKNESS OF THE EXISTING SOFFIT. SEC.
 107.2.1 CITY AMENDMENTS.
  
 F) PROVIDE COMPLETE SPECIFICATIONS FOR TYPE OF ANCHOR
 TO BE USED. SPECIFY ANCHOR DIAMETER AND LENGTH TO
 VERIFY COMPLIANCE WITH THE PRODUCT APPROVAL
 REQUIREMENTS FOR MINIMUM EMBEDMENT. SEC. R301.1
 FBC-RESIDENTIAL. NOTE: ANCHOR TYPE SPECIFIED AT BOTTOM
 CONNECTION OF OPENINGS #3 AND #4 IS TAPCON. ACCORDING
 TO SPECIFICATION #1(A) ON PAGE 13 OF 20 THE CONCRETE
 NEEDS TO HAVE A MINIMUM STRENGTH OF 3KSI. IT LOOKS LIKE
 THESE ACCORDION SHUTTERS ARE GOING TO BE MOUNTED ON THE
 PATIO SLAB. TYPICALLY, PATIO CONCRETE SLABS DON'T HAVE
 THE STRUCTURAL CONCRETE STRENGTH OF 3KSI. THEREFORE THE
 TAPCON MAY NOT BE USED. IT LOOKS LIKE THE 1/4" BLUE TAP
 CONCRETE ANCHORS ONLY REQUIRE 2KSI CONCRETE STRENGTH.
 THIS CONNECTOR MAY BE USED INSTEAD. REVISE ANCHOR TYPE
 AND SPACING AS REQUIRED OR PROVIDE PROOF THAT THE PATIO
 CONCRETE SLAB HAS 3KSI STRENGTH.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]