2018-04-16 16:04:15 | 2ND REVIEW: FBC 2017 6TH EDITION |
| |
| PLUMBING COMMENTS: PREVIOUS COMMENT NOT COMPLIED WITH. |
| |
| 19. PROVIDE SE (SESCO) SOVENT TITE RUFF DESIGN MANUAL. |
| PER WPB AMEND TO FBC 107.2.1 |
| DESIGN MANUAL WAS NOT IN SUBMITTAL PLEASE DOWN LOAD |
| MANUAL UNDER SUPPORTING DOCUMENTS |
| |
| 20. PROVIDE A PLAN REVIEW AND APPROVAL OF THE SE |
| (SESCO) TITE RUFF SOVENT SYSTEM FOR THIS PROJECT. PER |
| FBC PL 316.1.3 AND 919.1 |
| PLEASE PROVIDE DOCUMENTATION FROM THE MANUFACTURE |
| STATING THEY REVIEWED AND APPROVED YOUR DESIGN. |
| |
| 30. SANITARY PIPING OVER THE KITCHEN AREA SHALL BE |
| SHIELDED TO INTERCEPT POTENTIAL DRIPS OR LEAKS. PER US |
| FOOD CODE CH 5 AND FBC EX 1010.2 |
| COULD NOT LOCATE NOTE ON PLAN PLEASE PROVIDE SHEET |
| NUMBER SHOULD BE LOCATED ON BOTH ISOMETRIC AND FLOOR |
| PLAN AND AND PROVIDE DETAIL OF WHAT TYPE OF SHIELDING |
| OR PAN WILL BE USED. |
| |
| NEW COMMENT: |
| 1. SHT. 702 SHOWS THE CONDENSATE RECOVERY PUMP |
| DISCHARGING INTO THE SANITARY ALL CONDENSATE SHALL |
| DISCHARGE TO STORM OR TO PERMEABLE GROUND IT IS |
| PROHIBITED TO DISCHARGE TO THE SANITARY. PER CITY OF |
| WPB CODE OF ORDINANCE SEC. 90-126. (5) |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |