Plan Review Notes
Plan Review Notes For Permit 18020254
Permit Number 18020254
Review Stop P
Sequence Number 2
Notes
Date Text
2018-04-16 16:04:152ND REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENT NOT COMPLIED WITH.
  
 19. PROVIDE SE (SESCO) SOVENT TITE RUFF DESIGN MANUAL.
 PER WPB AMEND TO FBC 107.2.1
 DESIGN MANUAL WAS NOT IN SUBMITTAL PLEASE DOWN LOAD
 MANUAL UNDER SUPPORTING DOCUMENTS
  
 20. PROVIDE A PLAN REVIEW AND APPROVAL OF THE SE
 (SESCO) TITE RUFF SOVENT SYSTEM FOR THIS PROJECT. PER
 FBC PL 316.1.3 AND 919.1
 PLEASE PROVIDE DOCUMENTATION FROM THE MANUFACTURE
 STATING THEY REVIEWED AND APPROVED YOUR DESIGN.
  
 30. SANITARY PIPING OVER THE KITCHEN AREA SHALL BE
 SHIELDED TO INTERCEPT POTENTIAL DRIPS OR LEAKS. PER US
 FOOD CODE CH 5 AND FBC EX 1010.2
 COULD NOT LOCATE NOTE ON PLAN PLEASE PROVIDE SHEET
 NUMBER SHOULD BE LOCATED ON BOTH ISOMETRIC AND FLOOR
 PLAN AND AND PROVIDE DETAIL OF WHAT TYPE OF SHIELDING
 OR PAN WILL BE USED.
  
 NEW COMMENT:
 1. SHT. 702 SHOWS THE CONDENSATE RECOVERY PUMP
 DISCHARGING INTO THE SANITARY ALL CONDENSATE SHALL
 DISCHARGE TO STORM OR TO PERMEABLE GROUND IT IS
 PROHIBITED TO DISCHARGE TO THE SANITARY. PER CITY OF
 WPB CODE OF ORDINANCE SEC. 90-126. (5)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  