Plan Review Notes For Permit 18020254 |
Permit Number |
18020254 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-05-16 15:03:24 | GAS PROVISO: | | | | 1. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | | 2. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, LENGTH, | | SIZE AND TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL | | GAS CODE SEC. 502 THRU 505. SUBMIT CALCULATIONS FOR | | COMBUSTION AIR PER THE FBC-2014 FUEL GAS CODE SEC. 304. | | FOR BOILERS | | | | 3. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | FBC-2014 FUEL GAS CODE SEC. 304. FOR BOILER AND DRYERS | | | | PROVIDE BEFORE ROUGH INSPECTION. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|