Plan Review Notes
Plan Review Notes For Permit 18020254
Permit Number 18020254
Review Stop B
Sequence Number 2
Notes
Date Text
2018-04-04 08:22:512017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18020254
 ADD: 1675 PALM BEACH LAKES BLVD.
 CONT: STRATICON LLC
 TEL: 772-210-0200 STRATICON
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
  
 2ND REVIEW
 DATE: WED. APRIL 04/ 2018
 ACTION: DENIED
  
 1) 2ND REQUEST. THRESHOLD BUILDING / FL S. S. 553.71(7)
 ?THRESHOLD BUILDING".
 THE RESPONSE IS THAT THE THRESHOLD DOCUMENTS WERE
 SUBMITTED UNDER THE BUCK HOIST PERMIT. PLEASE NOTE THE
 SUBMITTED FORMS DATED MARCH 29, 2017 WERE NOT COMPLETE
 IN REQUIRED SIGNATURES.
 THE CERTIFIED INSPECTION CO. LINE IS LEFT BLANK, NO
 NOTARY WORK, CONTRACTOR SIGNATURE WITH NO NOTARY WORK,
 MISSING THE ARCHITECT AND ENGINEERS SIGNATURE AND SEAL
 AND NOTARY WORK, YOU SHOULD UPDATE YOUR SITE INSPECTOR
 INFORMATION WHO IS STILL WITH THE COMPANY, MIKE ADAIR
 IS NOW A CITY INSPECTOR.
  
  
 THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING. PLEASE
 UPDATE FILES SINCE THEIR MAYBE ADDITIONAL PERSONNEL TO
 ACT AS THE JOBSITE INSPECTOR.
 THRESHOLD BUILDING / FL S. S. 553.71(7) ?THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 1A)2ND REQUEST. 109.3.6.1 THRESHOLD INSPECTION PLAN.
 THE ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ TYPED)
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 1B) 2ND REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT
 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE
 THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT
 BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO
 THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT
 ISSUANCE WILL TAKE PLACE.
  
 1C)COMPLIED. THRESHOLD BLDG., REQUIRED STATEMENT:
 W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 1D) 2ND REQUEST. FOR THE SPECIAL INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
 UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED
 FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA.
  
 1E) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 1F) NOTICE ONLY. FOR DIGITAL PLANS, AFTER PERMIT
 ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE
 PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN
 E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU
 MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE
 PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE
 OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO
 PRINT MAYBE IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 1G) NOTICE ONLY. 110.3.7.4.3 ALL SHORING AND RESHORING
 PROCEDURES, PLANS AND DETAILS SHALL BE SUBMITTED TO THE
 ENFORCEMENT AGENCY FOR RECORDKEEPING. EACH SHORING AND
 RESHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED
 AND CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 1H)NOTICE ONLY. PLEASE CALL THE CITY OF WEST PALM
 BEACHS AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN
 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 1I) NOTICE ONLY. 109.3.6 THRESHOLD BUILDINGS, OPERATING
 GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT
 THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
  
  
  
  
 2) SHEET 042-LS-111 & 045-A-111:
  
 2A-2E) COMPLIED.
  
 2F) PROVISO: PLEASE NOTE WITH BOTH EXIT PASSAGE WAYS
 119 & 120 THE ONLY ALLOWABLE PENETRATIONS ARE THOUGH
 ALLOWED UNDER SECTION FBC-B 1024.6 PENETRATIONS INTO OR
 THROUGH AN EXIT PASSAGEWAY ARE PROHIBITED EXCEPT FOR
 EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 AND ELECTRICAL RACEWAY SERVING THE EXIT PASSAGEWAY AND
 TERMINATING AT A STEEL BOX NOT EXCEEDING 16 SQUARE
 INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE PROTECTED
 IN ACCORDANCE WITH SECTION 714. THERE SHALL NOT BE
 PENETRATIONS OR COMMUNICATING OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT PASSAGEWAYS.
  
 2G-2K) COMPLIED.
  
  
 2L) 2ND REQUEST. SEMI-COMPLIED. THE RESPONSE INDICATES
 NEW UPDATES FOR WALL TYPE L & L1 ON SHEET A5.02. PLEASE
 NOTE THIS SHEET IS NOT IN ORDER, FOUND IT LATER IN THE
 REVIEW.
  
 2M) COMPLIED.
  
 2N) SHEET A-407 NOTICE ONLY!!! SHEET A4.07 MENS STALL
 STILL 7 FEET. SHEET A-4.08 WOMENS STALL CORRECTED 7
 FOOT 1 INCH.
 1ST REVIEW COMMENT. THE ENLARGED MENS & WOMENS RESTROOM
 ON SHEET A407 & A-408 MEASURE 7-0 OVERALL. THE LAYOUT
 JUST BARELY MEETS THE REQUIREMENT FOR THE CLEAR FLOOR
 SPACE UNDER THE ACCESSIBILITY CODE SECTION 604.3.1.
 DEPENDING ON THE SIZE LAV TO BE INSTALLED THE CLEAR
 FLOOR SPACE MAY NOT BE ACHIEVED!!!
  
 2O-Q) COMPLIED.
  
 2R) 2ND REQUEST. SHEET 042-LS-111 THE FLOOR PLAN SHOWS
 A DINING AND BAR AREA, PLEASE PROVIDE COMPLIANCE WITH
 THE 2017 ACCESSIBILITY CODE 226.1 WHERE DINING SURFACES
 ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT
 LEAST 5 PERCENT OF THE SEATING SPACES AND STANDING
 SPACES AT THE DINING SURFACES SHALL COMPLY WITH 902.
  
 2S) 2ND REQUEST. 226.2 DISPERSION. DINING SURFACES AND
 WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE
 DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING
 DINING SURFACES AND WORK SURFACES.
  
 2T) 2ND REQUEST. 206.2.5 206.2.5 RESTAURANTS AND
 CAFETERIAS. IN RESTAURANTS AND CAFETERIAS, AN
 ACCESSIBLE ROUTE SHALL BE PROVIDED TO ALL DINING AREAS,
 INCLUDING RAISED OR SUNKEN DINING AREAS, AND OUTDOOR
 DINING AREAS.
 902.1 .DINING SURFACES AND WORK SURFACES SHALL COMPLY
 WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. DINING
 SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, TABLES,
 LUNCH COUNTERS, AND BOOTHS.
 2T)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 2T)(2) 2ND REQUEST. 902.3 HEIGHT. THE TOPS OF DINING
 SURFACES AND WORK SURFACES SHALL BE 28 INCHES MINIMUM
 AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 2U) PROVISO, NOTICE ONLY! POOL, GENERATOR, KITCHEN
 HOODS, SUPPRESSION, GAS, FENCES, SIGNS, FIRE
 SPRINKLERS, FIRE ALARMS, LANDSCAPING, IRRIGATION
 PERMITS ARE NOT REVIEWED UNDER THE MAIN BUILDING PERMIT
 AND ALL REQUIRE A SEPARATE REVIEW AND FEE.
  
 2V)COMPLIED.
  
 2W) 2ND REQUEST. SHEET 005-GN-1 BUILDING CODE SUMMARY
 INDICATES THE PLANS WERE DEVELOPED A CONSTRUCTION TYPE
 II-A, THIS ONLY ALLOWS UNDER THE 2014 CODE TABLE 503 A
 4 STORY BUILDING WITH ONE STORY INCREASE, IT WOULD BE
 REQUIRED TO BE A CONSTRUCTION TYPE I-B . UNDER THE 2017
 FBC-B TABLE 504.4 THE BUILDING TYPE WOULD ALSO BE
 REQUIRED TO BE I-B ALLOWABLE 12 STORIES WITH A FULL
 NFPA 13 SYSTEM, UNDER THE 2017 WITH FIRE SPRINKLERS A
 LL-A BUILDING IS ONLY ALLOWED TO BE 5 STORIES. .
  
 2X) COMPLIED. R-1 TRANSIENT A STAY30 DAYS OR LESS, SEE
 FBC-B 310.3 & 310.4.
  
 2Y)2ND REQUEST. SHEETS 042-ALS-111 NOR SHEET
 045-A-111-A SHOW THE LOCATION OF THE FIRE PUMP
 LOCATION. SHEET E-101 SHOWS THE FIRE PUMP IN THE
 MECHANICAL/ ELECTRICAL ROOM 127. PLEASE SHOW COMPLIANCE
 WITH:
 2017 FBC-B [F]403.3.4 FIRE PUMP ROOM. FIRE PUMPS SHALL
 BE LOCATED IN ROOMS PROTECTED IN ACCORDANCE WITH
 SECTION 913.2.1. 913.2.1 PROTECTION OF FIRE PUMP ROOMS.
 FIRE PUMPS SHALL BE LOCATED IN ROOMS THAT ARE SEPARATED
 FROM ALL OTHER AREAS OF THE BUILDING BY 2-HOUR FIRE
 BARRIERS CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR
 2-HOUR HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE
 WITH SECTION 711, OR BOTH.
 EXCEPTIONS:
 1.IN OTHER THAN HIGH-RISE BUILDINGS, SEPARATION BY
 1-HOUR FIRE BARRIERS CONSTRUCTED IN ACCORDANCE WITH
 SECTION 707 OR 1-HOUR HORIZONTAL ASSEMBLIES CONSTRUCTED
 IN ACCORDANCE WITH SECTION 711, OR BOTH, SHALL BE
 PERMITTED IN BUILDINGS EQUIPPED THROUGHOUT WITH AN
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION
 903.3.1.1 OR 903.3.1.2.
  
 3) SHEET 046-A-111-B:
  
 3A) 2ND REQUEST. THE COVERED ENTRY PORT COCHERE SHOWS
 THE USE OF A LULA LIFT, PLEASE PROVIDE CONFIRMATION THE
 LIFT MEETS THE LIMITED-USE/LIMITED-APPLICATION
 ELEVATORS SHALL COMPLY WITH 408 AND WITH ASME A17.1
 REFERENCED STANDARDS.
  
 3B) 2ND REQUEST. SHEET 046-A-111-B SHOWS A NEW FIRE
 COMMAND ROOM.
 [F]403.4 EMERGENCY SYSTEMS. THE DETECTION, ALARM AND
 EMERGENCY SYSTEMS OF HIGH-RISE BUILDINGS SHALL COMPLY
 WITH SECTIONS 403.4.1 THROUGH 403.4.8.
  
 3C)) 2ND REQUEST. [F]403.4.1 SMOKE DETECTION. SMOKE
 DETECTION SHALL BE PROVIDED IN ACCORDANCE WITH SECTION
 907.2.13.1.
  
 3D) 2ND REQUEST. [F]403.4.2 FIRE ALARM SYSTEM. A FIRE
 ALARM SYSTEM SHALL BE PROVIDED IN ACCORDANCE WITH
 SECTION 907.2.13.
  
 3E) 2ND REQUEST. [F]403.4.3 STANDPIPE SYSTEM. A
 HIGH-RISE BUILDING SHALL BE EQUIPPED WITH A STANDPIPE
 SYSTEM AS REQUIRED BY SECTION 905.3.
  
 3F)) 2ND REQUEST. [F]403.4.4 EMERGENCY VOICE/ALARM
 COMMUNICATION SYSTEM. AN EMERGENCY VOICE/ALARM
 COMMUNICATION SYSTEM SHALL BE PROVIDED IN ACCORDANCE
 WITH SECTION 907.5.2.2.
  
 3G) 2ND REQUEST. [F]403.4.5 EMERGENCY RESPONDER RADIO
 COVERAGE. EMERGENCY RESPONDER RADIO COVERAGE SHALL BE
 PROVIDED IN ACCORDANCE WITH THE FLORIDA FIRE PREVENTION
 CODE.
  
 3H)SEMI-COMPLIED. [F]403.4.6 FIRE COMMAND. A FIRE
 COMMAND CENTER COMPLYING WITH SECTION 911 SHALL BE
 PROVIDED IN A LOCATION APPROVED BY THE FIRE DEPARTMENT.
  
 3I) 2ND REQUEST. 403.4.7 SMOKE REMOVAL. TO FACILITATE
 SMOKE REMOVAL IN POST-FIRE SALVAGE AND OVERHAUL
 OPERATIONS, BUILDINGS AND STRUCTURES SHALL BE EQUIPPED
 WITH NATURAL OR MECHANICAL VENTILATION FOR REMOVAL OF
 PRODUCTS OF COMBUSTION IN ACCORDANCE WITH ONE OF THE
 FOLLOWING:
 1.EASILY IDENTIFIABLE, MANUALLY OPERABLE WINDOWS OR
 PANELS SHALL BE DISTRIBUTED AROUND THE PERIMETER OF
 EACH FLOOR AT NOT MORE THAN 50-FOOT (15 240 MM)
 INTERVALS. THE AREA OF OPERABLE WINDOWS OR PANELS SHALL
 BE NOT LESS THAN 40 SQUARE FEET (3.7 M2) PER 50 LINEAR
 FEET (15 240 MM) OF PERIMETER.
  
 EXCEPTIONS:
 1.IN GROUP R-1 OCCUPANCIES, EACH SLEEPING UNIT OR SUITE
 HAVING AN EXTERIOR WALL SHALL BE PERMITTED TO BE
 PROVIDED WITH 2 SQUARE FEET (0.19 M2) OF VENTING AREA
 IN LIEU OF THE AREA SPECIFIED IN ITEM 1.
 2.WINDOWS SHALL BE PERMITTED TO BE FIXED PROVIDED THAT
 GLAZING CAN BE CLEARED BY FIRE FIGHTERS.
 2.MECHANICAL AIR-HANDLING EQUIPMENT PROVIDING ONE
 EXHAUST AIR CHANGE EVERY 15 MINUTES FOR THE AREA
 INVOLVED. RETURN AND EXHAUST AIR SHALL BE MOVED
 DIRECTLY TO THE OUTSIDE WITHOUT RECIRCULATION TO OTHER
 PORTIONS OF THE BUILDING.
 3.ANY OTHER APPROVED DESIGN THAT WILL PRODUCE
 EQUIVALENT RESULTS.
  
 3J) 2ND REQUEST. [F]403.4.8 STANDBY AND EMERGENCY
 POWER. A STANDBY POWER SYSTEM COMPLYING WITH SECTION
 2702 AND SECTION 3003 SHALL BE PROVIDED FOR THE STANDBY
 POWER LOADS SPECIFIED IN SECTION 403.4.8.3. AN
 EMERGENCY POWER SYSTEM COMPLYING WITH SECTION 2702
 SHALL BE PROVIDED FOR THE EMERGENCY POWER LOADS
 SPECIFIED IN SECTION 403.4.8.4.
  
 3K) 2ND REQUEST. [F]403.4.8.1 EQUIPMENT ROOM. IF THE
 STANDBY OR EMERGENCY POWER SYSTEM INCLUDES A GENERATOR
 SET INSIDE A BUILDING, THE SYSTEM SHALL BE LOCATED IN A
 SEPARATE ROOM ENCLOSED WITH 2-HOUR FIRE BARRIERS
 CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR
 HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH
 SECTION 711, OR BOTH. SYSTEM SUPERVISION WITH MANUAL
 START AND TRANSFER FEATURES SHALL BE PROVIDED AT THE
 FIRE COMMAND CENTER.
  
 4A-D) COMPLIED. MATRIX PROVIDING THE TOTAL AMOUNT OF
 SLEEPING ROOMS ACCESSIBILITY.
  
 5) THE 2ND FLOOR LEVEL, SHEETS 043-LS-121, 050-A-121 &
 051-A-122:
 5A-F) COMPLIED.
  
 6-7) COMPLIED.
  
 8) PROVISO/ DEFERRED SUBMITTAL. SHEET A104-A-601 DOOR
 STYLE 20 IS A SLIDING BARN DOOR AND TRACK SYSTEM,
 HARDWARE GROUP 11 INDICATES ADA COMPLIANT PULLS. THE
 DOOR HAS TO MAINTAIN A 32 INCH CLEAR OPENING AS WELL AS
 THE HARDWARE MEET COMPLIANCE WITH :
 2017 ACCESS. CODE 404.2.7 DOOR AND GATE HARDWARE.
 HANDLES, PULLS, LATCHES, LOCKS, AND OTHER OPERABLE
 PARTS ON DOORS AND GATES SHALL COMPLY WITH 309.4.
 OPERABLE PARTS OF SUCH HARDWARE SHALL BE 34 INCHES
 MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND. WHERE SLIDING DOORS ARE IN THE FULLY OPEN
 POSITION, OPERATING HARDWARE SHALL BE EXPOSED AND
 USABLE FROM BOTH SIDES.
  
 9) COMPLIED.
  
 10) PROVISO/ DEFERRED SUBMITTAL. WINDOWS ARE UNDER A
 SEPARATE PERMITS BUT THERE WILL BE OTHER COMPONENTS AND
 CLADDING REQUIREMENTS. 2017 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (C) PANEL WALLS: WALL LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 11) PROVISO/ DEFERRED SUBMITTAL. W. P. B. 107.3.4.1
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 12) 2ND REQUEST. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 ONE SET OF PLANS WILL HAVE TO BE TAKEN (BY THE
 CONTRACTOR OR REPRESENTATIVE) TO THE PALM BEACH COUNTY
 IMPACT FEE OFFICE LOCATED AT 2300 N. JOG RD. ROOMS
 2W01-2W14 WEST PALM BEACH, FL. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE
 PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE
 CALL (561)233-5025 FOR MORE INFORMATION.
  
 13) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  